The text of a manual · part 20 of 21
User Manual: 1305 Adjustable Frequency AC Drive (Series C), pages 159 to 164
Pages 159 to 164 of 170: C - Drive Accessories; D - CE Conformity
The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1305-BA03A
Page 159
Drive Accessories
Appendix C
Table C.1 Accessories Bulletin 1201 Descriptions Door Mount Bezel Kit
Use With Bulletin 1305 Drives
IP30 (NEMA Type 1) Cat. No. 1201-DMA
IP66 NEMA Type 12 (ULType 4X Indoor) Cat. No. –
IP30 NEMA Type 1/12 (Enhanced) Cat. No. –
Hand Held) (Enhanced) Cat. No. –
Blank Cover
1201-HAB
–
–
–
Human Interface Module – Programmer Only
1201-HAP
1201-HJP
1201-HJPE
1201-HHPE
Human Interface Module – Analog Speed Potentiometer
1201-HA1
–
–
–
–
–
1201-HJ3E
1201-HH3E
1201-HA2
1201-HJ2
–
–
Cat. No.
Cat. No.
Cat. No.
Cat. No.
–
–
–
Human Interface Module – Programmer/Run Time Functions Human Interface Module – Digital Up–Down Speed Control Bulletin 1202 Descriptions
Use With
Communication Cable (Male-Male) for Port 2 0.33 Meter (1.1 Feet) 1 Meter (3.3 Feet) 3 Meter (9.8 Feet) 9 Meter (29.5 Feet) Communication Cable (Male-Female) for Port 1 0.33 Meter (1.1 Feet) 1 Meter (3.33 Feet) 3 Meter (9.8 Feet) 9 Meter (29.5 Feet) Bulletin 1203 Descriptions
Human Interface Module and Communications Modules
Single Point Remote I/O Communication Module ➀
Human Interface Module and Communications Modules
1202-C03 1202-C10 1202-C30 1202-C90 –
–
–
Use With
1202-H03 1202-H10 H10 1202-H30 1202-H90 Cat. No.
Cat. No.
Cat. No.
Cat. No.
Bulletin 1305 Drives
1203-GD1/GK1
–
–
–
1203-GD2/GK2
–
–
–
DeviceNet Communication Module ➁
1203-GK5
–
–
–
2 Port Splitter 4 Port Splitter
1203-SG2 1203-SG4
–
–
–
SLC/SCANport Module
1203-SM1
–
–
–
Flex I/O SCANport Terminal Base Flex I/O SCANport Module
1203-FB1 1203-FM1
–
–
–
RS232/RS422/RS485/DF1/DH485 Serial Communication Module ➀
➀ Separately powered AC/DC.
➁ Separately powered DC only.
Page 160
Drive Accessories
C-2
Table C.2 Accessories Drive Output Ratings Dynamic Brake Kits ➁ (Kits must not be wired in parallel) HP kW
Accessory
Specifications
Line Reactor
Iron core, 3% Impedance, 600V, Class H insulation, 115_C rise, copper wound, 50/60 Hz, terminal blocks, UL, CSA
Isolation Transformer
230V/230V or 460V/460V, Delta primary/Wye secondary, Class H insulation, 150_C rise, aluminum wound, 60 Hz, "5% taps, (1) N.C. thermostat per coil, UL, CSA
0.5-1 2-3
Terminators
NEMA 4, 460V units – Refer to “Motor Lead Lengths” for proper selection.
0.5-1 2-3 5
Drive Out. Ratings
Input Line Reactors
Isolation Transformer
Terminators
HP kW
Open Style
NEMA Type 1
NEMA Type 1
NEMA Type 4
0.5 0.75 1 2 3
0.37 0.55 0.75 1.5 2.2
1321-3R4-B 1321-3R4-A 1321-3R4-A 1321-3R8-A 1321-3R12-A
1321-3RA4-B 1321-3RA4-A 1321-3RA4-A 1321-3RA8-A 1321-3RA12-A
1321-3T003-AA 1321-3T003-AA 1321-3T005-AA 1321-3T005-AA 1321-3T005-AA
–– –– –– –– ––
1321-3T003-BB 1321-3T003-BB 1321-3T005-BB 1321-3T005-BB 1321-3T005-BB 1321-3T005-BB 1321-3T005-BB 1321-3T007-BB
–– –– 1204-TFA1 1204-TFA1 or TFB2 1204-TFA1 or TFB2 1204-TFA1 or TFB2 1204-TFA1 or TFB2 1204-TFA1
230V AC
460V AC 0.5 0.75 1 2 3➀ 3 5➀ 5
0.37 0.55 0.75 1.5 2.2 2.2 4.0 4.0
1321-3R2-B 1321-3R2-A 1321-3R2-A 1321-3R4-B 1321-3R4-B 1321-3R8-B 1321-3R8-B 1321-3R12-B
1321-3RA2-B 1321-3RA2-A 1321-3RA2-A 1321-3RA4-B 1321-3RA4-B 1321-3RA8-B 1321-3RA8-B 1321-3RA12-B
230V AC 0.37-0.75 1.5-2.2
Not Required 1305-KAA12 460V AC
0.37-0.75 1.5-2.2 4.0
1305-KBA03 1305-KBA06 1305-KBA09 ➂
CE Conformance Filters
RFI Filters, Kits, and Metal Conduit Plates Required to Meet CE Directives
Filter (RFB) Metal Plate Kit (MP)
0.5 – 0.75 HP (230V)
1305-RFB-05-A 1305-MP-05-A
1 HP (230V)
1305-RFB-05-A 1305-MP-06-A
2 HP (230V), 0.5 – 3 HP (460V)
1305-RFB-08-B 1305-MP-08-B
3 HP (230V), 5 HP (460V)
1305-RFB-12-C 1305-MP-12-C
Note: Spare plastic parts are available – contact factory. ➀ Input reactor only. ➁ [DB Enable] should be set to ‘‘Enable” when applying external dynamic brake kits. ➂ For use with Series C or B Drives only. DO NOT use with Series A Drives.
Page 161
CE Conformity
Appendix D
EMC DIRECTIVE
REQUIREMENTS FOR CONFORMING INSTALLATION
This apparatus is tested to meet Council Directive 89/336 Electromagnetic Compatibility (EMC) using a technical construction file and the following standards, in whole or in part:
The following six items are required for CE conformance:
D EN 50081-1, -2 – General Emission Standard D EN 50082-1, -2 – General Immunity Standard Table D.1 EMC Directives Marked for all applicable directives Emissions
EN55 011/CISPR 11 Level B
Immunity
EN50 082-1:1992 (IEC 801-2, IEC 801-3, IEC 801-4) EN50 082-2:1995 (EN 61000-4-2, ENV 50140/50204, EN 61000-4-4, ENV 50141, EN 61000-4-8, IEC 801-6)
Important: The conformity of the drive and filter to any standard does not guarantee that the entire installation will conform. Many other factors can influence the total installation and only direct measurements can verify total conformity.
1. CE marked product in NEMA Type 1 (IP30) configuration. 2. Filter and Metal Plate Kit catalog numbers are listed in Table D.2 on the following page. One Filter and one Metal Plate Kit are required. The metal bonding plate MUST be inserted and bonded to the drive heatsink.
3. Grounding as shown on page D-3. The Green & Yellow ground wire connects to the TB1 GRD terminals and the shield terminates at the compact strain relief connector with double saddle clamp (see item 5).
4. Maximum cable length (drive to motor) of 75 meters (250 feet). For applications greater than 9 meters (30 feet), refer to recommendations tabulated in ”Motor Lead Lengths” (see Chapter 2).
5. Input power (source to filter) and output power (drive to motor) wiring must be in braided shielded cable with a coverage of 75% or better, metal conduit or other with equivalent or better attenuation, mounted with appropriate connectors. For shielded cable it is recommended to use a compact strain relief connector with a double saddle clamp for filter and drive input and a compact strain relief connector with EMI protection for motor output.
6. Control (I/O) and signal wiring must be in shielded cable connected to the drive with a compact strain relief connector with EMI protection.
Page 162
D-2
CE Conformity
FILTER
RFI Filter Installation
Table D.2 Filter and Metal Plate Kit Selection
Important: Refer to the instructions supplied with the filter for details.
Filter 1305-RFB-5-A
Metal Plate Kit 1305-MP-05-A
1305-RFB-8-B
1305-MP-06-A 1305-MP-08-B
1305-RFB-12-C
1305-MP-12-C
AC Drive Type 1305-AA02 1305-AA03 1305-AA04 1305-AA08 1305-BA01 1305-BA02 1305-BA03 1305-BA04 1305-BA06 1305-AA12 1305-BA09
The RFI filter must be connected between the incoming AC supply line and the drive input terminal. RFI Filter Leakage Current The RFI filter may cause ground leakage currents. Therefore a solid ground connection must be provided.
!
ATTENTION: To guard against possible equipment damage, RFI filters can only be used with AC supplies that are nominally balanced with respect to ground. In some installations, three-phase supplies are occasionally connected in a 3-wire configuration with one phase grounded (Grounded Delta). The filter must not be used in Grounded Delta supplies, nor should they be used in single-phase input applications.
Page 163
CE Conformity
D-3
ELECTRICAL CONFIGURATION Figure D.1 Electrical Configuration Conduit/4-Wire Cable R(L1) Shield* U RFI Filter
S(L2) Motor
V T(L3)
W
GRD Frame
Frame
Ground Rod
GROUNDING RFI Filter Grounding Important: Shield must be terminated in cable clamp to frame. Ground wire must be connected to GRD terminal.
GRD
GRD GRD = Earth Ground
Important: For use with a 1305 drive with metal conduit entry panel (frame). Using an RFI filter may result in relatively high ground leakage currents. Therefore, the filter must be permanently installed and solidly grounded to the supply neutral. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. The integrity of this connection should be periodically checked. Refer to the instruction manual for RFI filters for CE compliance and for proper installation instructions.
Page 164
CE Conformity
D-4
Figure D.3 Required Knockout Assignments
MECHANICAL CONFIGURATION
Frame A
Figure D.2 Mechanical Configuration
Three-Phase Input ➀
(1305-AA02A, AA03A, AA04A)
Terminal Block Cover Adapter
Additional Control
Control I/O
Terminal Block Cover Motor Output
Filter Input
Grounding Bracket
18.6 (0.73) - 4 Plcs. L SE C ES
JO
Frames B and C
G
(1305-AA08A, AA12A, BA01A, BA02A, BA03A, BA04A, BA06A, BA09A)
Control I/O
Optional Brake
To Motor ➀ Cable Supplied with Filter ➀ ➀ Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/armor must be bonded to the metal conduit panel. See requirements 5 and 6 on page D-1 for details.
Filter Input
Motor Output
18.6 (0.73) - 4 Plcs. Grounding Bracket