What is in it
Rockwell Automation's user manual for the Bulletin 1305 Adjustable Frequency AC Drive (Series C), rated 0.37 to 4 kW (0.5 to 5 Hp), firmware 6.01 and up. It covers receiving and storage, mounting and wiring (power, control, grounding, EMI/RFI and motor cable length), the optional Human Interface Module, start-up, every programming parameter, fault codes and troubleshooting, plus a block diagram and specifications, serial communications with PLC and SLC controllers, accessories and CE conformity.
Its parts
- Information and Precautions
- Installation/Wiring
- HIM
- Start-Up
- Programming
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the Allen-Bradley user manual for the Bulletin 1305 adjustable frequency AC drive, Series C, firmware 6.01 and up. It covers the 200-230 V AC drives -AA02A, -AA03A, -AA04A, -AA08A and -AA12A and the 380-460 V AC drives -BA01A, -BA02A, -BA03A, -BA04A, -BA06A and -BA09A. It explains installation, control wiring, start-up, programming, fault codes and accessories.
- Type
- Adjustable frequency AC drive, Series C, firmware 6.01 and up; family spans 0.37…4 kW (0.5…5 Hp) p. 1
- Catalog code
- B: 380-460V three-phase; enclosure code A: IP 30 (NEMA Type 1) p. 13
- Output frequency
- 0.00 to 400.00 Hz, programmable p. 138
- Ambient temperature
- 0 to 50 °C (optional enclosures 0 to 40 °C); storage -40 to 70 °C p. 139
- Control inputs
- Contact closure with internal 5V supply: start, stop, reverse, jog, enable, SW1 to SW3 for 7 preset speeds p. 139
- Analog inputs
- 0 to 10 V DC (100 K Ohms) and 4 to 20 mA (250 Ohms), 10 bit, non-isolated p. 139
- Outputs
- Form A relay 115V AC/30V DC, 5A resistive, 2A inductive; open collector 24V DC, 50 mA; analog 0 to 10V DC p. 140
- Overload
- 150% for 60 seconds; current limit programmable from 20% to 150% p. 140
- Accel/decel
- 0.1 to 3600 seconds, 2 accel and 2 decel times p. 141
- HIM
- Optional, 16 character 2 line backlit LCD; drive suffix HAP (programmer only), HA1 (analog speed pot) or HA2 (digital up-down keys) p. 13, 142
- Communications
- Optional Remote I/O, RS232/RS422/RS485/DF1/DH485 or DeviceNet (1203-GK5) adapters; 250 mA max. for all adapters p. 142, 159
- Fault codes
- F5 overvolt, F7 overload, F8 overtemp, F12 overcurrent, F38 to F40 phase-to-ground in U, V, W p. 130
- Control wire
- Belden 8760, 8770 or 9460 (or equiv.), 18 AWG shielded p. 35
What this manual walks you through
- Reading the nameplate and catalog number p. 12, 13
- Checking drive and HIM firmware compatibility p. 12
- Storing the drive before installation p. 10
- Wiring control terminal block TB2 for two-wire, three-wire and MOP control p. 33, 34, 35
- Clearing a fault p. 125
- Looking up fault codes and corrective actions p. 126, 127, 128, 129, 130
- Drive specifications and derating p. 138, 139, 140, 141, 142
- Choosing HIMs, cables and communication modules p. 159
- Line reactors, isolation transformers, brake kits and CE filters p. 160
Good to know
- The drive has no speed-sensitive overload protection or thermal memory retention. p. 3
- Never apply external voltage to the contact closure inputs. p. 35
- Control inputs of two or more drives must not be connected in parallel. p. 35
- Output current must be derated when the PWM frequency is set above 4 kHz. p. 138
- Above 1,000 m, derate by 6% of drive rated amps per 1000 m. p. 139
Questions this manual answers
How do I clear a fault on a 1305 drive?
Fix the cause first, then cycle power, cycle the stop signal, or cycle the [Clear Fault] parameter. p. 125
What does fault F12 mean on a 1305 drive?
The hardware trip circuit detected overcurrent; check for a short circuit at the drive output or an excessive motor load. p. 130
What causes a Drive Reset Fault F22 at power-up?
The Start input is closed while the Stop input is open and [Run On Power Up] is disabled; check the stop wiring at TB2 terminal 8. p. 127
Which HIM fits the 1305 drive?
The 1201-HAP programmer-only module or the 1201-HA1 with analog speed potentiometer, among others in the accessory table. p. 159
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 21 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Pages 5 to 85-8
- 1 - Information and Precautions9-14
- 2 - Installation/Wiring, pages 15 to 2215-22
- 2 - Installation/Wiring, pages 23 to 3023-30
- 2 - Installation/Wiring, pages 31 to 3831-38
- 3 - HIM, pages 39 to 4839-48
- 3 - HIM, pages 49 to 5849-58
- 4 - Start-Up59-68
- 5 - Programming, pages 69 to 7869-78
- 5 - Programming, pages 79 to 8879-88
- 5 - Programming, pages 89 to 9889-98
- 5 - Programming, pages 99 to 10899-108
- 5 - Programming, pages 109 to 118109-118
- 5 - Programming, pages 119 to 124119-124
- 6 - Troubleshooting125-136
- A - Block Diagram & Specifications137-142
- B - Serial Communications, pages 143 to 150143-150
- B - Serial Communications, pages 151 to 158151-158
- Pages 159 to 164159-164
- Pages 165 to 170165-170
The file