Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 12 of 21

User Manual: 1305 Adjustable Frequency AC Drive (Series C): 5 - Programming, pages 89 to 98

Pages 89 to 98 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1305-BA03A

Page 89

Programming

5-21

Advanced Setup Group (continued) [Analog Invert] This parameter enables the inverting function for the 0-10 Volt and 4-20mA analog input signal at TB2.

Parameter # 84 Parameter Type Read & Write Units Text

Factory Default ‘‘Disabled” Settings ‘‘Enabled” ‘‘Disabled”

Figure 5.12 Analog Invert

Maximum Input Commands [Minimum Freq] Minimum Input Commands [Maximum Freq] Maximum Input Commands [Maximum Freq] Minimum Input Commands [Minimum Freq]

[Maximum Frequency] ' Disabled

Drive Output Enabled [Minimum Frequency] ' y 0V 4 mA

[4-20mA Loss Sel] This parameter selects the drives reaction to a loss of a 4-20mA signal when the active [Frequency Source] is 4-20mA. Important: The drive output contacts can be used to issue an alarm signal by setting [Output 1 Config] or [Output 2 Config] to “alarm”. Important: Loss of signal is defined as a signal < 3.5 mA or a signal > 20.5 mA.

Parameter # 81 Parameter Type Read & Write Units Text y 10 V 20 mA

Factory Default ‘‘Stop/Fault” Settings ‘‘Stop/Fault” ‘‘Hold/Alarm” ‘‘Max/Alarm” ‘‘Pre1/Alarm” ‘‘Min/Alarm”

Drive Stops and Issues ‘‘Hz Err Fault” (F29) Drive Maintains Last Output Freq and sets an Alarm bit Drive Outputs [Maximum Freq] and sets Alarm bit Drive Outputs [Preset Freq 1] and sets an Alarm bit Drive Outputs [Minimum Freq] and sets an Alarm bit

Page 90

5-22

Programming

Advanced Setup Group (continued) [Stop Select] This parameter selects the stopping mode when the drive receives a valid stop command.

Parameter # 10 Parameter Type Read & Write Units Text

Factory Default ‘‘Ramp” Settings ‘‘Coast” ‘‘Ramp” ‘‘DC Brake” ‘‘S-Curve”

[DC Hold Time] This value sets the amount of time that the [DC Hold Level] voltage will be applied to the motor when the stop mode is set to either ‘‘DC Brake” or ‘‘Ramp.” When in ‘‘Coast ” mode and the drive is stopped and restarted within the [DC Hold Time] setting, the speed will resume at the output frequency prior to the stop command.

Parameter # 12 Parameter Type Read & Write Units 0.1 Seconds

Figure 5.13 Ramp

Causes the Drive to Turn Off Immediately Drive Decelerates to 0 Hz, Then Turns Off – Requires a Value In [Decel Time 1] or [Decel Time 2] Injects DC Braking Voltage Into the Motor – Requires a Value in Both [Decel Hold Time] & [Decel Hold Level]. Drive ramps to stop using a fixed ‘‘S-Curve” profile. Stop time is twice the selected decel time.

Factory Default 0.0 Sec Minimum 0.0 Sec Maximum 150 Sec

Figure 5.14 DC Brake Voltage

Volts and Speed

Voltage Speed

[DC Hold Time] [DC Hold Time]

Volts and Speed

Speed

[DC Hold Level]

[DC Hold Level] y Stop Command

Time y Stop Command

Time

Page 91

Programming

5-23

Advanced Setup Group (continued) [DC Hold Volts] This parameter value sets the DC voltage applied to the motor during braking when the [Stop Select] is set to either ‘‘DC Brake” or ‘‘Ramp”.

Parameter # 13 Parameter Type Read & Write Units 1 Volt

Factory Default 0 Volts Minimum 0 Volts Maximum 25% of Max. Drive Rated Volts

Parameter # 11 Parameter Type Read & Write Units Text

Factory Default ‘‘Disabled”

Important: When setting this parameter, begin at a low voltage and continue increasing until sufficient holding torque is achieved and the drive output current rating is not exceeded.

[DB Enable] This parameter enables the use of external dynamic brake resisters by disabling the internal ramp regulation.

Settings ‘‘Enabled” ‘‘Disabled”

Permits dynamic brake operation Permits Ramp Regulation

Important: Dynamic braking is not available for 0.37 - 0.75 kW (0.5 - 1HP) units rated 230 Volt.

[Motor Type] Factory default for this parameter is an induction motor. Changing this parameter to “Sync PM” causes [Compensation] and [Rated Slip] to be internally disabled.

Parameter # 41 Parameter Type Read & Write Units Text

Factory Default ‘‘Induc/Reluc” Settings ‘‘Induc/Reluc” ‘‘Sync PM”

Requires No Additional Setting for use with induction/reluctance rated motors Requires [Stop Select] to be set to a selection other than ‘‘DC Brake” when used with Synchronous Permanent Magnet Motors

Page 92

5-24

Programming

Advanced Setup Group (continued) [Compensation] Some drive/motor combinations have inherent instabilities which are exhibited as nonsinusoidal current feedback. The compensation when enabled will correct this condition. This compensation is active from 1.1 Hz up to a maximum of 120 Hz. This compensation is turned off when [Motor Type] = “Sync PM.”

Parameter # 52 Parameter Type Read & Write Units Text

Factory Default ‘‘Comp” Settings ‘‘No Comp” ‘‘Comp”

Compensation Disabled Compensation Enabled

Page 93

Programming

Frequency Set

[Freq Select 1] This parameter is the factory default parameter for selecting the frequency source that will supply the [Freq Command] to the drive. [Freq Select 2] or [Preset Freq 1-7] can be selected in place of this parameter with proper terminal block inputs. Refer to charts on Pages 5-29 and 5-30.

This group of parameters allows the user to program the frequency source, frequency settings, accel/decel times and skip frequencies of the drive.

Parameter # 5 Parameter Type Read & Write Units Text

Factory Default “Adapter 1”

Parameter # 6 Parameter Type Read & Write Units Text

Factory Default ‘‘Remote Pot”

Important: If an adapter that is not connected is selected as the active frequency source, the drive will fault on “Hz Sel Fault” (F30).

[Freq Select 2] This parameter controls which of the frequency sources is currently supplying the [Freq Command] to the drive unless [Freq Select 1] or [Preset Freq 1-7] are selected with proper terminal block inputs. Refer to charts on Pages 5-29 and 5-30. Important: If an adapter that is not connected is selected as the active frequency source, the drive will fault on “Hz Sel Fault” (F30).

5-25

Settings ‘‘Remote Pot” ‘‘0-10 Volt” ‘‘4-20 mA” ‘‘MOP” ‘‘Adapter 1” ‘‘Adapter 2” ‘‘Adapter 3” ‘‘Adapter 4” ‘‘Adapter 5” ‘‘Adapter 6”

Settings ‘‘Remote Pot” ‘‘0-10 Volt” ‘‘4-20 mA” ‘‘MOP” ‘‘Adapter 1” ‘‘Adapter 2” ‘‘Adapter 3” ‘‘Adapter 4” ‘‘Adapter 5” ‘‘Adapter 6”

‘‘Preset 1” ‘‘Preset 2” ‘‘Preset 3” ‘‘Preset 4” ‘‘Preset 5’’ ‘‘Preset 6” ‘‘Preset 7”

‘‘Preset 1” ‘‘Preset 2” ‘‘Preset 3” ‘‘Preset 4” ‘‘Preset 5’’ ‘‘Preset 6” ‘‘Preset 7”

Page 94

5-26

Programming

Frequency Set Group (continued) [Jog Frequency] This parameter sets the frequency the drive will output when it receives a jog command.

[Prst/2nd Accel] This parameter, along with the [Upper Presets] parameter, determines which frequency source and Accel/Decel parameters will be selected using the optional inputs SW1, SW2 and SW3. Refer to charts on Pages 5-29 and 5-30.

[Upper Presets] This parameter along with the [Prst/2nd Accel] parameter determines which frequency source and Accel/Decel parameters will be selected using the optional inputs SW1, SW2 and SW3. Refer to charts on Pages 5-29 and 5-30.

[Accel Time 2] This value determines the time it will take the drive to ramp from 0 Hz to [Maximum Frequency]. The rate is linear unless [S Curve] is ‘‘Enabled.” It applies to any increase in command frequency unless [Accel Time 1] is selected. Refer to charts on Pages 5-29 and 5-30.

Parameter # 24 Parameter Type Read & Write Units 0.1 Hz

Factory Default 10.0 Hz Minimum 0.0 Hz Maximum 400.0 Hz

Parameter # 26 Parameter Type Read & Write Units Text

Factory Default “Preset”

Parameter # 72 Parameter Type Read & Write Units Text

Factory Default “Disabled”

Parameter # 30 Parameter Type Read & Write Units 0.1 Second

Factory Default 5.0 Sec Minimum 0.0 Sec Maximum 3600.0 Sec

Settings “Preset” “2nd Accel”

Settings “Enabled” “Disabled”

Page 95

Programming

5-27

Frequency Set Group (continued) [Decel Time 2] This value determines the time it will take the drive to ramp from [Maximum Freq] to 0 Hz. The rate is linear unless [S Curve] is ‘‘Enabled” or [Stop Select] is set to ‘‘S-Curve.” It applies to any decrease in command frequency unless [Decel Time 1] is selected. Refer to charts on Pages 5-29 and 5-30.

[Preset Freq 1-7] These values set the frequencies that the drive will output when selected. Refer to charts on Pages 5-29 and 5-30.

[Skip Freq 1-3] These values, in conjunction with [Skip Freq Band], create a range of frequencies at which the drive will not operate continuously.

Parameter # 31 Parameter Type Read & Write Units 0.1 Second

Factory Default 5.0 Sec Minimum 0.0 Sec Maximum 3600.0 Sec

Parameter # See Table Parameter Type Read & Write

Factory Default See Table Minimum 0.0 Hz

Units 0.1 Hz

Parameter # 32-34 Parameter Type Read & Write Units 1 Hz

Maximum 400.0 Hz

Parameter [Preset Freq 1] [Preset Freq 2] [Preset Freq 3] [Preset Freq 4] [Preset Freq 5] [Preset Freq 6] [Preset Freq 7]

No. 27 28 29 73 74 75 76

Default 10.0 Hz 20.0 Hz 30.0 Hz 40.0 Hz 50.0 Hz 60.0 Hz 0.0 Hz

Factory Default 400 Hz Minimum 0 Hz Maximum 400 Hz

Programming the drive for Frequency Source and Accel/Decel Control Use Table 5.A through Table 5.C to determine which frequency source and Accel/Decel Time are suitable to your application. Switch or contact inputs at terminal TB2 are used to select functionality based on how you program parameters (26), (72), and (21).

Page 96

5-28

Programming

Frequency Set Group (continued) [Skip Freq Band] This parameter determines the band width around a [Skip Frequency]. The band width is 2 [Skip Freq Band] – 1/2 the band above and 1/2 the band below the [Skip Frequency] setting. “0” Disables All Skip Frequencies.

Figure 5.15 Skip Frequency Band

Parameter # 35 Parameter Type Read & Write Units 1 Hz

Factory Default 0 Hz Minimum 0 Hz Maximum 15 Hz

Frequency Command Frequency

'

Drive Output a Frequency y Skip Frequency Setting

Two times [Skip Freq Band] Setting b

'

Time

[MOP Increment] The MOP function is a digital solid-state circuit that produces the same effect as rotating a speed reference potentiometer with a small DC motor. This permits local (HIM) or remote (TB2) control of the command frequency. This parameter sets the rate of increase or decrease to the [MOP Hertz] command frequency for each input to the MOP Increment or MOP Decrement terminals of TB2. (Requires the proper [Input Mode] selection or serial communications.)

Parameter # 22 Parameter Type Read & Write Units 1 Hz/Sec

Factory Default 1.00 Hz/Sec Minimum 0.00 Hz/Sec Maximum 255 Hz/Sec y INC

DEC

Hz (Speed)

Time

'

Page 97

Programming

5-29

Frequency Set Group (continued) Table 5.A Frequency Source Selection

• • •

Disabled ➁

• • • •

Preset ➁

• • •

Enabled

• • • • •

➀ The parameter [Freq Source] indicates the active frequency source. See p. 5-45. ➂ Not valid for [Input Mode] = “3 W/2nd Acc” or [Input Mode] = “Run F/R 2nd A”. ■

•

Valid for [Input Mode] = “3 W/2nd Acc” or [Input Mode] = “Run F/R 2nd A”. Indicates active function/parameter. X Indicates closed switch. 0

•

0

0

0

•

•

0

0

X

•

•

0

X

0

•

•

0

X

X

•➂

•➂

■

■

X

0

0

•➂

•➂

■

■

X

0

X

•➂

•➂

■

■

X

X

0

•➂

•➂

■

■

X

X

X

•

•

0

0

0

•

•

0

0

X

•

•

0

X

0

•

•

0

X

X

•

•

X

0

0

•

•

X

0

X

•

•

X

X

0

•

•

X

X

X

Decel Time 2 (31)

•

Accel Time 2 (30)

Decel Time 1 (8)

•

Control Terminal Block

Accel Time 1 (7)

Preset Freq 7 (76)

Preset Freq 6 (75)

Accel/Decel Preset Freq 5 (74)

Preset Freq 4 (73)

Preset Freq 3 (29)

Preset Freq 1 (27)

Freq Select 2 (6)

Upper Presets (72)

Freq Select 1 (5)

Preset/ 2nd Accel(26)

Preset Freq 2 (28)

Frequency Source ➀

Parameter Settings

➁ Factory default settings.

Indicates open switch.

(26) Indicates parameter number.

SW3 TB2-18

SW2 TB2-17

SW1 TB2-16

Page 98

5-30

Programming

Frequency Set Group (continued) Table 5.B Accel/Decel Selection

• •

•

Disabled ➁

• •

•

•

•

•

•

•

Enabled

• •

• • •

➀ The parameter [Freq Source] indicates the active frequency source. See p. 5-45. ➁ Factory default settings. • Indicates active function/parameter. X Indicates closed switch. 0 Indicates open switch.

0

0

X

•

0

X

0

•

0

X

X

X

0

0

X

0

X

•

X

X

0

•

X

X

X

0

0

0

0

0

X

•

0

X

0

•

0

X

X

X

0

0

X

0

X

•

X

X

0

•

X

X

X

•

•

• •

0

0

• •

•

0

•

•

•

2nd Accel

SW2 TB2-17

• •

•

SW3 TB2-18

•

•

•

Control Terminal Block Decel Time 2 (31)

•

•

Accel Time 2 (30)

Decel Time 1 (8)

•

Accel Time 1 (7)

Preset Freq 7 (76)

Preset Freq 6 (75)

Accel/Decel Preset Freq 5 (74)

Preset Freq 4 (73)

Preset Freq 3 (29)

Preset Freq 1 (27)

Freq Select 2 (6)

Upper Presets (72)

Freq Select 1 (5)

Preset/ 2nd Accel(26)

Preset Freq 2 (28)

Frequency Source ➀

Parameter Settings

• •

•

• •

(26) Indicates parameter number.

SW1 TB2-16