Page 99
Programming
5-31
Frequency Set Group (continued) Table 5.C Motor Operated Potentiometer (MOP) Frequency Source and Accel/Decel Selection Parameter Settings Preset/ 2nd Accel (26)
Upper Presets (72)
Preset or 2nd Accel
Disabled or Enabled
Frequency Source ➀ Freq Select 1 (5)
Freq Select 2 (6)
•
Accel/Decel Accel Time 1 (7)
Decel Time 1 (8)
•
•
•
Accel Time 2 (30)
Control Terminal Block Decel Time 2 (31)
•
•
SW3 TB2-18
SW2 TB2-17
SW1 TB2-16
0
MOP Decrement ➁
MOP Increment ➂
X
MOP Decrement ➁
MOP Increment ➂
➀ The parameter [Freq Source] indicates the active frequency source. See p. 5-45. ➁ MOP Decrement – When this switch is closed, [MOP Hz] is decreased at the rate programmed in [MOP Increment]. ➂ MOP Increment – When this switch is closed, [MOP Hz] is increased at the rate programmed in [MOP Increment]. • Indicates active function/parameter. X Indicates closed switch. 0 Indicates open switch. (26) Indicates parameter number.
[Analog Filter] Selects the amount of software filtering applied to the 0-10 volt analog input and potentiometer input in 25% increments. The lower the percentage, the less filtering applied – allowing faster response to analog signal changes. To obtain higher noise immunity, set the filter value higher. A value of 100% represents the same amount of filtering as all previous versions of released firmware. With this setting the frequency command rises to 95% of the signal input in 0.5 seconds.
Parameter # 144 Parameter Type Read & Write Units Text
Factory Default 100% Settings “0%” “25%” “50%” “75%” “100%”
Page 100
5-32
Programming
Feature Select
[Run On Power Up] This parameter enables the function that allows the drive to automatically restart on power up regardless of what the drive status was before power is lost. This applies only when there is a maintained input to the start and stop inputs. Refer to Chapter 2, Figure 2.7 through Figure 2.10.
[Reset/Run Tries] This value sets the maximum number of times the drive attempts to reset a fault and restart before the drive issues a ‘‘Max Retries Fault.” Not operative for faults 9, 10, 11, 24, 25, 26, 29, 30, 32, 33, 34, 35, 38, 39, 40, 41, 42, 43 and 48. Important: [Reset/Run Tries] is a cumulative count. This counter resets to zero if four (4) minutes elapses since the last fault.
This group contains the necessary parameters to activate and program advanced features of the drive.
Parameter # 14 Parameter Type Read & Write Units Text
!
Factory Default ‘‘Disabled” Settings ‘‘Enabled” ‘‘Disabled”
ATTENTION: This parameter may only be used as outlined in NFPA 79, paragraph 6-14 (exceptions 1-3) for specialized applications. Equipment damage and/or personal injury may result if this parameter is used in an inappropriate application.
Parameter # 85 Parameter Type Read & Write Units Numeric
Factory Default 0 Minimum 0 Maximum 9
Page 101
Programming
5-33
Feature Select Group (continued) [Reset/Run Time] This value sets the time between restart attempts when [Reset/Run Tries] is a value other than zero.
Parameter # 15 Parameter Type Read & Write Units 0.1 Second
Factory Default 1.0 Sec Minimum 0.5 Sec Maximum 30.0 Sec
Parameter # 57 Parameter Type Read & Write Units Text
Factory Default ‘‘Disabled”
Important: [Reset/Run Tries] is a cumulative count. This counter resets to zero if four (4) minutes elapses since the last fault.
[S Curve Enable] This parameter enables a fixed shape S-Curve.
Settings ‘‘Enabled” ‘‘Disabled”
Figure 5.16 S-Curve Accel/Decel times are double the active accel/decel time settings.
Enabled
Important: The setting for [S-Curve Time] must be 0. Important: If [Stop Select] is set to “S Curve” then the decel time will be double the active decel setting when a stop command is provided.
a 2X Accel Time 1 or 2 ' a 2X Decel Time 1 or 2 '
Disabled
'
Accel Time a 1 or 2
' Decel Time 1 or 2 a
Page 102
5-34
Programming
Feature Select Group (continued) [S Curve Time] This parameter enables an adjustable shape S-Curve accel/decel time. Important: [S-Curve Time] must be set to a value less than or equal to the Accel & Decel times.
Parameter # 56 Parameter Type Read & Write Units 0.1 Second
Factory Default 0.0 Sec Minimum 0.0 Sec Maximum 300.0 Sec
Figure 5.17 S-Curve Time [S-Curve Enable] must be ‘‘enabled” for this parameter to be active. The [S-Curve Time] setting is added to the active accel/decel times to form an adjustable S-Curve. Important: If [Stop Select] is set to “S Curve” then the decel time will be double the active decel setting when a stop command is provided.
'
1/2 S-Curve a Time
1/2 S-Curve a Time
' a Accel Time 1 or 2
'
'
1/2 S-Curve a Time
'
1/2 S-Curve a Time
Enabled a Decel Time ' 1 or 2
Disabled
[Language] This parameter selects between English and the alternate second language that can be displayed on the HIM.
Parameter # 47 Parameter Type Read & Write Units Text
Factory Default Alternate language in multilingual versions,English in English only versions. Settings ‘‘English” or “French” “Italian” “Spanish” “German”
Page 103
Programming
Feature Select Group (continued) [Cable Length] This parameter selects the length of cable that is connected to the motor.
Parameter # 143 Parameter Type Read & Write Units Text
Factory Default “Short”
Parameter # 146 Parameter Type Read & Write Units 0.1 Hz
Factory Default 2.0 Hz Minimum 0.0 Hz Maximum 5.0 Hz
Settings “Short” “Long”
Important: A setting of “Long” causes the PWM carrier frequency to be fixed at 2 kHz and Voltage Ring-Up Reduction software to be enabled. Important: If “Overload Fault” (F7) occurs – choose “Long” length.
[Rated Slip] This parameter compensates for the inherent slip in an induction motor. A frequency is added to the commanded output frequency based on torque current. The actual value added may be viewed in [Slip Comp Adder] (parameter 148). If motor shaft speed decreases significantly under heavy loads then this value should be increased. A setting of 0.0 Hz disables the function. This parameter can be set more accurately based on motor nameplate RPM at full load. Use the formula and table shown.
Rated Slip =
[(
Motor Sync Speed – Nameplate RPM Motor Sync Speed
Motor
Drive Rated Amps x( ) x ( Nameplate ) )] Motor FLA Hertz
Example Drive 1 HP, 460V 2.3 Amps Rated Motor Motor Sync Speed = 1800 RPM Nameplate RPM = 1725 RPM Nameplate Hertz = 60 Hz Motor FLA = 1.7 Amps Rated Slip =
[(
1800 – 1725
1800 Set [Rated Slip] to 3.4 Hz.
2.3
Motor Sync Speed Poles 60 Hz 50 Hz 2 3600 3000 4 1800 1500 6 1200 1000 8 900 750 12 600 500
) x ( 60 ) x ( 1.7 )] = 3.38 Hz
Note: Instability may occur if [Rated Slip] is set too high with operating frequencies below 10 Hz.
5-35
Page 104
5-36
Programming
Feature Select Group (continued) [Slip Comp Adder] Displays the frequency added to the drive output due to the slip compensation feature. See [Rated Slip] for additional information.
[IR Comp %] A voltage is added to the output based on torque current. An additional 31 volts (maximum) is added to 460 volt units to compensate for stator resistance. 15.5 volts is added for 230 volt units. If the drive trips on an Overload fault (F7), or has trouble accelerating to commanded speed, this value should be reduced. A setting of 0% disables this function.
Parameter # 148 Parameter Type Read Only Units 0.01 Hz
Factory Default None Minimum 0.00 Hz Maximum 5.00 Hz
Parameter # 147 Parameter Type Read & Write
Factory Default See Table Minimum 0%
Units 1%
Maximum 150%
0.37 kW (0.5 HP)
0.55 kW (0.75 HP)
0.75 kW (1 HP)
1.5 kW (2 HP)
2.2 kW (3 HP)
4.0 kW (5 HP)
230V
45%
45%
45%
45%
45%
N/A
460V
75%
75%
75%
60%
50%
50%
Page 105
Programming
Output Configuration [Output 1 Config] This parameter sets the condition that actuates the relay output at TB2, terminals 9 and 10.
This group of parameters contains the programming options for digital and analog drive outputs.
Parameter # 90 Parameter Type Read & Write Units Text
Factory Default “Faulted“ Settings ‘‘At Speed” ‘‘Above Freq” ‘‘Running” ‘‘Faulted” ‘‘Alarm” ‘‘Above Curr”
[Output 2 Config] This parameter sets the condition that actuates the open collector output at TB2, terminals 19 and 20.
5-37
Parameter # 91 Parameter Type Read & Write Units Text
Output closes when drive reaches [Freq Command]. Output closes when drive exceeds value set in [Above Freq Val]. Output closes when drive is running. Output closes when drive is faulted. Output closes when the drive reaches hardware current limit, software current limit, overvoltage, line loss or 4-20 mA loss. Output closes when current exceeds value set in [Above Curr Val].
Factory Default “Running” Settings ‘‘At Speed” ‘‘Above Freq” ‘‘Running” ‘‘Faulted” ‘‘Alarm” ‘‘Above Curr”
Output closes when drive reaches [Freq Command]. Output closes when drive exceeds value set in [Above Freq Val]. Output closes when drive is running. Output closes when drive is faulted. Output closes when the drive reaches hardware current limit, software current limit, overvoltage, line loss or 4-20 mA loss. Output closes when current exceeds value set in [Above Curr Val].
Application Note: During power up of the drive, the customer programmable Outputs 1 & 2 (TB2–9 & 10, TB2– 19 & 20) are in an indeterminate state for a period of time until the internal control of the drive has initialized (3 sec. max.). Any control system connected to the programmable outputs should take this into consideration. On power down, the programmable outputs may transition in a similar way.
Page 106
5-38
Programming
Output Configuration Group (continued) [Analog Out Sel] This parameter selects the value to which the 0-10V DC analog output at TB2-5 is proportional to.
Parameter # 25 Parameter Type Read & Write Units Text
Factory Default “Frequency” Setting ‘‘Frequency” ‘‘Current” ‘‘Bus Volts” ‘‘Power” “Output Volts”
[Above Freq Val] This parameter sets the level at which Output 1 or Output 2 will transition when [Output 1 Config] or [Output 2 Config] are set to ‘‘Above Freq”. This provides an indication that the drive is operating above the programmed frequency value.
[Above Curr Val] This parameter sets the level at which Output 1 or Output 2 will transition when [Output 1 Config] or [Output 2 Config] are set to ‘‘Above Curr”. This provides an indication that the drive output current exceeds the programmed value.
Parameter # 77 Parameter Type Read & Write Units 1 Hz
0 to [Maximum Freq] 0 to 200% of Rated Drive Output Current) 0 to Maximum Bus Voltage– 410V/230V Drives 815V/460V Drives 0 to 200% of Drive Rated OutputPower 0 to Drive Rated Voltage
Factory Default 0 Hz Minimum 0 Hz Maximum 400 Hz NOTE: This parameter can not be programmed while the drive is running.
Parameter # 142 Parameter Type Read & Write Units 1%
Factory Default 0 % of Drive Rated Current ➀ Minimum 0 % of Drive Rated Current ➀ Maximum 150% of Drive Rated Current ➀
➀ The drive rated output current is based on three phase input ratings. See page 5-13 for Single Phase Input Rating instructions.
Page 107
Programming
Faults
[Fault Buffer 0-3] These parameters store the last (4) faults that occur. If the same fault occurs multiple times in a row, it will only be stored once. [Fault Buffer 0] through [Fault Buffer 3] can only be cleared by ‘‘Reset Defaults” from EEPROM mode or [Set Defaults] parameter. This will leave a ‘‘F48” in [Fault Buffer 0] and reset all parameters to factory defaults.
[Clear Fault] This parameter is used to clear a fault and return the drive to ready status if the fault condition no longer exists. Important: [Clear Fault] will stop a running drive. Also [Clear Fault] does not clear [Fault Buffer 0] through [Fault Buffer 3].
5-39
This group of parameters provides information and programmed settings on commonly viewed drive faults.
Parameter # 86-89 Parameter Type Read Only Units Numeric
Factory Default None Buffer
0 1 2 3
Parameter # 51 Parameter Type Read & Write Units Text
Last Fault, stored in EEPROM Fault from Buffer 0, Stored in EEPROM Fault from Buffer 1, Stored in EEPROM Fault from Buffer 2, Stored in EEPROM
Factory Default ‘‘Ready” Displays ‘‘Ready” ‘‘Clear Fault”
Display after function has been attempted
Attempts to clear fault
Important:To clear a fault using parameter #51, press the SEL key once to select the bottom display line. Press the ▲ ▼ keys until “Clear Fault” appears on the bottom display line. Press the ↵ key. This action will attempt to clear the fault. “Ready” will be displayed. Press the ESC key several times to get back to the Status Display and check if the fault has been cleared. If the fault has not been cleared refer to the Troubleshooting section of this manual.
Page 108
5-40
Programming
Faults Group (continued) [Cur Lim Trip En] This setting determines whether or not exceeding the setting in [Current Limit] will cause a Diagnostic Current Limit Fault (Fault F36).
[Line Loss Fault] This setting determines whether a 15% drop in DC Bus voltage will have no effect on operation or cause a ‘‘Power Loss Fault” (fault F03). Important:The “Line Loss” alarm bit will be set when this condition exists regardless of the parameter setting.
Parameter # 82 Parameter Type Read & Write Units Text
Factory Default ‘‘Default Run” Setting ‘‘Trip @ I Lim” ‘‘Default Run”
Parameter # 40 Parameter Type Read & Write Units Text
A Diagnostic Current Limit Fault is generated No fault generated
Factory Default ‘‘F03 Enable” Setting ‘‘UVolt Run” ‘‘FO3 Enable”
‘‘Power Loss Fault” Disabled
Drive Trips at 85% of nominal bus voltage.