The text of a manual · part 14 of 21

User Manual: 1305 Adjustable Frequency AC Drive (Series C): 5 - Programming, pages 109 to 118

Pages 109 to 118 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1305-BA03A

Page 109

Programming

5-41

Faults Group (continued) Line Loss Fault “F03 Enable” (Enabled)

Line Loss Fault “U Volt Run” (Disabled) 100% Nominal Bus Voltage

100% Nominal Bus Voltage

85% Nominal Bus Voltage ➀ Minimum Bus Voltage

T1 T2

No Fault

Output Power is on

No Fault

Output Power is on

Undervolt Fault

No Output Power

No Fault

85% Nominal Bus Voltage

Power Loss Fault

➀ Minimum Bus Voltage

T3

Output Power is on

Undervolt Fault T4 T5

No Output Power

T6

➀ Minimum bus voltage is approximately 70% of Line Voltage

Application Notes: If line loss is set to ‘‘U Volt Run” and [Run On Power Up] is enabled, the drive will run as long as the bus voltage is high enough to maintain logic. To obtain longer power ride-thru, choose “U Volt Run”. This allows the output power to be on from time T1 to T3. To obtain a longer control ride–thru, choose “F03 Enable”. The output power devices are turned off at time T5 but note that time T6 – T5 is greater than time T3 – T2. [Flt Clear Mode] This parameter controls the method for clearing faults.

Parameter # 39 Parameter Type Read & Write Units Text

Factory Default ‘‘Enabled” Setting ‘‘Enabled” ‘‘Disabled”

Faults Cleared By Issuing a Valid Stop Command or Cycling Input Power Faults Cleared Only By Cycling Input Power

Page 110

5-42

Programming

Diagnostics

This group of parameters contains values that can be helpful in explaining the operation of the drive. Drive status, direction, control and alarm conditions are included.

[Drive Command]

Parameter # 58 Parameter Type Read Only

This parameter displays the status of the drive commands in an 8-bit binary format.

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0 “Run” “Reverse” “Accel 2” “Decel 2” N/A N/A N/A N/A

Run Reverse Accel 2 Decel 2 Not Used Not Used Not Used Not Used

Page 111

Programming

5-43

“Enabled” “Running” “Command Fwd” “Rotating Fwd” “Accel” “Decel” “Alarm” “Faulted” “At Speed” “Local 0” “Local 1” “Local 2” “Freq Ref 0” “Freq Ref 1” “Freq Ref 2” “Freq Ref 3”

Enabled Running Command Forward Rotating Forward Accel Decel Alarm Faulted At Speed Local 0 Local 1 Local 2 Freq Ref 0 Freq Ref 1 Freq Ref 2 Freq Ref 3

Diagnostics Group (continued) [Drive Status] This parameter displays the actual operating condition in 16 bit binary format.

Parameter # 59 Parameter Type Read Only Bit 15

Bit 14 Bit 7

Bit 13 Bit 6

Bit 12 Bit 5

Bit 11 Bit 4

Bit 10 Bit 3

Bit 9 Bit 2

Bit 8 Bit 1

Bit 0

Page 112

5-44

Programming

Diagnostics Group (continued) [Drive Alarm] This parameter displays which alarm condition is present when bit 6 of [Drive Status] is high (set to 1)

Parameter # 60 Parameter Type Read Only Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0 “Hard Cur Lim” “Soft Cur Lim” “Bus Overvolt” “Line Loss” “4-20mA Loss “Bus Changing” N/A N/A

[Input Status] This parameter displays the open (0) and closed (1) status of inputs at TB2. Refer to Figure 2.7 through Figure 2.10 for description of terminal connections.

Hard Current Limit Software Currnt Limit Bus Overvoltage Line Loss 4-20mA Loss Bus Changing Not Used Not Used

Parameter # 55 Parameter Type Read Only Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0 “Start TB2-6” “Stop TB2-8” “Rev TB2-13” “Jog TB2-14” “SW1 TB2-16” “SW2 TB2-17” “SW3 TB2-18” N/A

TB2–6 Start/Run Forward TB2–8 Stop TB2–13 Reverse/Run Reverse TB2–14 JOG TB2–16 SW1 TB2–17 SW2 TB2–18 SW3 Not Used

Page 113

Programming

Diagnostics Group (continued) [Freq Source] This parameter displays the frequency source currently commanding the drive.

[Freq Command] This parameter displays the frequency that the drive is commanded to output. This command may come from any one of the frequency sources selected by [Freq Select 1], [Freq Select 2] or [Preset Freq 1-7] as determined by inputs to SW1, SW2 and SW3 at TB2.

[Drive Direction] This parameter displays the running direction of the drive.

[Motor Mode] This parameter is used for internal diagnostic purposes.

Parameter # 62 Parameter Type Read Units Text

Displays ‘‘Remote Pot” ‘‘0-10 Volt” ‘‘4–20 mA” ‘‘MOP” ‘‘Adapter 1” ‘‘Adapter 2” ‘‘Adapter 3” ‘‘Adapter 4” ‘‘Adapter 5” ‘‘Adapter 6”

Parameter # 65 Parameter Type Read Only Units 0.01 Hz

Factory Default 0.00 Hz Minimum 0.00 Hz Maximum 400.00 Hz

Parameter # 69 Parameter Type Read Only Units Text

Factory Default ‘‘Forward’’

Parameter # 43 Parameter Type Read Only

Displays ‘‘Forward” ‘‘Reverse”

‘‘Preset 1” ‘‘Preset 2” ‘‘Preset 3” ‘‘Preset 4” ‘‘Preset 5’’ ‘‘Preset 6” ‘‘Preset 7”

5-45

Page 114

5-46

Programming

Diagnostics Group (continued) [Power Mode]

Parameter # 44 Parameter Type Read Only

This parameter is used for internal diagnostic purposes.

[Drive Type]

Parameter # 61 Parameter Type Read Only

This parameter displays a decimal number that identifies the drive.

[Firmware Ver]

Parameter # 71 Parameter Type Read Only

Factory Default None Display 0.00

Parameter # 67 Parameter Type Read Only Units 1 Cycle

Factory Default None Minimum 0 Maximum 65535

Parameter # 70 Parameter Type Read Only Units 1 Degree C

Factory Default None Minimum 0 Degrees C Maximum 100 Degrees C

Parameter # 64 Parameter Type Read & Write Units Text

Factory Default ‘‘Ready”

This parameter displays the version number of the drive firmware.

[Output Pulses] This parameter displays the number of output cycles for the PWM waveform. The count rolls over at 65535.

[Drive Temp] This parameter displays the internal drive temperature.

[Set Defaults] Setting parameter to ‘‘Default Init” resets all parameters to their factory values. See also page 3-11 EEPROM Mode.

Settings ‘‘Ready” ‘‘Store to EE” Note: This parameter can not be programmed while ‘‘Recll frm EE” ‘‘Default Init” the drive is running.

Display After Function Complete Saves parameter Ram to EEPROM Restores parameter Ram from EEPROM Resets All Parameters to Their Factory Settings

Page 115

Programming

Masks

This group of parameters contains binary masks for all control functions except the stop command. The masks control which adapters can issue control commands.

Each mask contains a bit for each adapter. Individual bits can be set to ‘‘0” to lockout control by an adapter or set to ‘‘1” to permit an adapter to have control.

Mask

[Logic Mask]

Parameter # 92 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 94 Parameter Type Read & Write Units Byte

Factory Default 01111111

This parameter determines which adapters are allowed to control the drive logic commands. Setting a bit to ‘‘0” (deny control) disables all command functions except stop and frequency reference. Important: In order to remove an adapter from the drive without causing a drive communications fault, the corresponding bit for that adapter must be set to zero. Important: This parameter has no effect on the frequency value being sent from TB2 or any of the adapters.

[Direction Mask] This parameter determines which adapters can issue forward/reverse commands. Important: Terminal Block (TB2) will have control unless masked out.

5-47

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0 “TB2” TB2 “Adapter 1” Adapter 1 “Adapter 2” Adapter 2 “Adapter 3” Adapter 3 “Adapter 4” Adapter 4 “Adapter 5” Adapter 5 “Adapter 6” Adapter 6 Not Used N/A

Settings 1 0

Settings 1 0

Permit Control Deny Control

Permit Control Deny Control

Page 116

5-48

Programming

Masks Group (continued) [Start Mask] This parameter determines which adapters can issue start commands.

[Jog Mask] This parameter determines which adapters can issue jog commands.

[Reference Mask] This parameter determines which adapters can control the switching between the available freq. reference sources. Important: Terminal Block (TB2) will have control unless masked out.

[Accel Mask] This parameter determines which adapters can switch between [Accel Time 1] and [Accel Time 2]. Important: Terminal Block (TB2) will have control unless masked out.

[Decel Mask] This parameter determines which adapters can switch between [Decel Time 1] and [Decel Time 2]. Important: Terminal Block (TB2) will have control unless masked out.

Parameter # 95 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 96 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 97 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 98 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 99 Parameter Type Read & Write Units Byte

Factory Default 01111111

Settings 1 0

Settings 1 0

Settings 1 0

Settings 1 0

Settings 1 0

Permit Control Deny Control

Permit Control Deny Control

Permit Control Deny Control

Permit Control Deny Control

Permit Control Deny Control

Page 117

Programming

Masks Group (continued) [Fault Mask] This parameter determines which adapters can reset a fault using input control signals.

[MOP Mask] This parameter determines which adapters can issue MOP commands to the drive.

[Local Mask] This parameter determines which adapters can issue a Local command in order to obtain exclusive control of the drive. For safety reasons, local control can only be granted or removed while the drive is not running and is in a safe state. If any adapter is in local control of the drive, all other adapters are locked out and prohibited from controlling any logic function except stop. Important: The only way to obtain local control of Bulletin 1305 drives is through the serial port via a PLC command. Important: This parameter has no effect on the frequency value being sent from TB2 or any of the adapters..

Parameter # 100 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 101 Parameter Type Read & Write Units Byte

Factory Default 01111111

Parameter # 93 Parameter Type Read & Write Units Byte

Factory Default 01111111

Settings 1 0

Settings 1 0

Settings 1 0

Permit Control Deny Control

Permit Control Deny Control

Permit Control Deny Control

5-49

Page 118

5-50

Programming

Owners

This group of parameters contains binary status information to display which adapters are issuing control commands. Owners

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0 “TB2” TB2 “Adapter 1” Adapter 1 “Adapter 2” Adapter 2 “Adapter 3” Adapter 3 “Adapter 4” Adapter 4 “Adapter 5” Adapter 5 “Adapter 6” Adapter 6 Not Used N/A

[Stop Owner] This parameter displays which adapters are currently issuing a valid stop command.

[Direction Owner] This parameter displays which adapter currently has exclusive control of direction changes. When commanding the direction from an adapter, the corresponding bit is set to “1”. Important: Only one adapter is allowed to control direction at any instance.

Parameter # 102 Parameter Type Read Only Units Byte

Parameter # 103 Parameter Type Read Only Units Byte

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling