Page 119

Programming

Owners Group (continued) [Start Owner] This parameter displays which adapters are currently issuing Start commands. Since Start commands are edge triggered, multiple adapters can issue the Start command simultaneously and as such are displayed. However, it is the first low to high transition of the Start (once all Stops and/or Faults are removed) that initiates the actual Start command.

[Jog Owner] This parameter displays which adapters are currently issuing Jog commands. Since the Jog function is momentary, multiple adapters can issue Jog commands simultaneously. This means that all adapters issuing the Jog must stop commanding the Jog before the function ceases. Important: Stop commands will terminate Jog control and Start commands will override any Jog command.

Parameter # 104 Parameter Type Read Only Units Byte

Parameter # 105 Parameter Type Read Only Units Byte

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling

5-51

Page 120

5-52

Programming

Owners Group (continued) [Reference Owner] This parameter displays which adapter has exclusive control of selecting the [Freq Source].

[Accel Owner] This parameter displays which adapter currently is exclusively controlling the selection between [Accel Time 1] and [Accel Time 2].

[Decel Owner] This parameter displays which adapter currently is exclusively controlling the selection between [Decel Time 1] and [Decel Time 2].

[Fault Owner] This parameter displays which adapters are currently issuing a [Clear Faults] Command. Multiple adapters can issue simultaneous [Clear Faults] Commands.

Parameter # 106 Parameter Type Read Only Units Byte

Parameter # 107 Parameter Type Read Only Units Byte

Parameter # 108 Parameter Type Read Only Units Byte

Parameter # 109 Parameter Type Read Only Units Byte

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling

Page 121

Programming

Owners Group (continued) [MOP Owner] This parameter displays which adapters are currently issuing increases or decreases in MOP Command Frequency. Multiple adapters can issue changes simultaneously to the MOP value.

[Local Owner] This parameter displays which adapter currently has exclusive control of all drive logic functions by requesting a LOCAL command. If an adapter is the [Local Owner], all other functions (except stop) on all other adapters are locked out and non-functional. Important: Local control can only be granted when the drive is in a safe state or stopped.

Parameter # 110 Parameter Type Read Only Units Byte

Parameter # 137 Parameter Type Read Only Units Byte

Settings 1 0

Controlling Not Controlling

Settings 1 0

Controlling Not Controlling

5-53

Page 122

5-54

Programming

Adapter I/O

This group contains the parameters needed for an optional communications adapter to communicate with the drive.

[Data In A1 through D2]

Parameter # 111 - 118 Parameter Type Read & Write

These parameters are used to write real time data values from a source controller (PLC, SLC, etc.) to the drive. This is accomplished by programming a parameter number into the [Data In] parameters. The value programmed into the source controller’s output image table will be written to the drive parameter identified in the corresponding [Data In] parameter.

Parameter 111 Data In A1 112 Data In A2 113 Data In B1 114 Data In B2 115 Data In C1 116 Data In C2 117 Data In D1 118 Data In D2

Bulletin 1305 drive

Controller Output Image Table (i.e. PLC, SLC, etc.) Important: addressing information that defines which controller I/O address corresponds to a [Data In] parameter is determined by the dip switch settings on the external communication module. Refer to the appropriate Bulletin 1203 Communication Module User Manual for details. Refer to Appendix B for additional information.

Important: The drive parameter that is accessed indirectly using Data In will not be stored permanently and automatically to EEPROM (due to the high potential update rate from a PLC). A manual operation is necessary for permanent storage. The HIM EEPROM command, Save Values, or using parameter (64) [Set Defaults] will perform this task. Similarly, to restore the values to the ones the drive had before Data In was configured, the HIM Recall Values Function can be used. [Data Out A1 through D2]

Parameter # 119 - 126 Parameter Type Read & Write

These parameters are used to write real time data values from the drive to a destination controller. This is accomplished by programming a parameter number into the [Data Out] parameters. The real time value of that parameter will be written to the input image table of the destination controller.

Parameter Bulletin 1305 drive 119 Data Out A1 120 Data Out A2 121 Data Out B1 122 Data Out B2 123 Data Out C1 124 Data Out C2 125 Data Out D1 126 Data Out D2

Controller Input Image Table (i.e. PLC, SLC, etc.) Important: addressing information that defines which controller I/O address corresponds to a [Data Out] parameter is determined by the dip switch settings on the external communication module. Refer to the appropriate Bulletin 1203 Communication Module User Manual for details. Refer to Appendix B for additional information.

Page 123

Programming

Process Display

[Process Par] This parameter should be set to the number of the parameter whose scaled value will be displayed on Line 1 of the HIM Display Panel when in process mode.

[Process Scale] This value sets the scaling multiplier for [Process Par]. The displayed value will be: [Process Par] actual value [Process Scale] value Displayed Value ➀

[Process Txt 1-8] These parameters set the ‘‘User Units” description for the value determined by [Process Par] and [Process Scale]. This text is displayed on Line 1 of the HIM.

This group contains parameters that can be used to display a drive parameter in ‘‘User Units.”

Parameter # 127 Parameter Type Read & Write Units Numeric

Factory Default 1 Minimum 1 Maximum Max. Parameter Number

Parameter # 128 Parameter Type Read & Write Units Numeric

Factory Default +1.00 Minimum –327.68 Maximum +327.67

Parameter #(s) 129-136 Parameter Type Read & Write Units ASCII Text Character

Factory Default ‘‘?’’

➀ The maximum value that can be displayed is 99,999.99. If this value is exceeded a character string of asterisks (******* ) will appear on the display.

5-55

Page 124

Programming

5-56

This group lists all parameters in numerical order.

Linear List 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Output Voltage % Output Curr % Output Power Last Fault Freq Select 1 Freq Select 2 Accel Time 1 Decel Time 1 DC Boost Select Stop Select DB Enable DC Hold Time DC Hold Volts Run On Power Up Reset/Run Time Minimum Freq Base Frequency Base Voltage Maximum Freq Maximum Voltage Input Mode MOP Increment Output Power Jog Frequency Analog Out Sel Prst/2nd Accel

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52

Preset Freq 1 Preset Freq 2 Preset Freq 3 Accel Time 2 Decel Time 2 Skip Freq 1 Skip Freq 2 Skip Freq 3 Skip Freq Band Current Limit Overload Mode Overload Current Flt Clear Mode Line Loss Fault Motor Type MOP Hertz Motor Mode Power Mode PWM Frequency Current Angle Language Start Boost Break Frequency Break Voltage Clear Fault Compensation

53 54 55 56 57 58 59 60 61 62 64 65 66 67 69 70 71 72 73 74 75 76 77 81 82 83

DC Bus Voltage Output Current Input Status S Curve Time S Curve Enable Drive Command Drive Status Drive Alarm Drive Type Freq Source Set Defaults Freq Command Output Freq Output Pulses Drive Direction Drive Temp Firmware Ver Upper Presets Preset Freq 4 Preset Freq 5 Preset Freq 6 Preset Freq 7 Above Freq Val 4–20mA Loss Sel Cur Lim Trip En Run Boost

84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109

Analog Invert Reset/Run Tries Fault Buffer 0 Fault Buffer 1 Fault Buffer 2 Fault Buffer 3 Output 1 Config Output 2 Config Logic Mask Local Mask Direction Mask Start Mask Jog Mask Reference Mask Accel Mask Decel Mask Fault Mask MOP Mask Stop Owner Direction Owner Start Owner Jog Owner Reference Owner Accel Owner Decel Owner Fault Owner

110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135

MOP Owner Data in A1 Data In A2 Data In B1 Data In B2 Data In C1 Data In C2 Data In D1 Data In D2 Data Out A1 Data Out A2 Data Out B1 Data Out B2 Data Out C1 Data Out C2 Data Out D1 Data Out D2 Process Par Process Scale Process Text 1 Process Text 2 Process Text 3 Process Text 4 Process Text 5 Process Text 6 Process Text 7

136 137 141 142 143 144 146 147 148 149

Process Text 8 Local Owner Sec Curr Limit Above Curr Val Cable Length Analog Filter Rated Slip IR Comp % Slip Comp Adder Adaptive I Lim