The text of a manual · part 16 of 21
User Manual: 1305 Adjustable Frequency AC Drive (Series C): 6 - Troubleshooting
Pages 125 to 136 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)
The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1305-BA03A
Page 125
Troubleshooting and Fault Information
Chapter 6
CHAPTER OBJECTIVES
Fault LED
Chapter 6 provides information to guide the user in understanding drive fault conditions and general troubleshooting procedures for 1305 drives. Included is a listing and description of the various drive faults with possible solutions, when applicable. General troubleshooting is presented in Table 6.C.
All drives come equipped with a fault LED. When the fault LED is illuminated it is an indication a fault condition exists. Refer to page 2-3 for the location of the fault LED. Once the fault is properly cleared the LED will return to an off state.
FAULT INFORMATION
As can be seen in Figure 2.3, there are two indicators provided to display the drive’s status condition. The DC Bus Charge Indicator is a neon bulb that will be illuminated when power is applied to the drive. The Fault Indicator is an LED that will be illuminated if a drive fault condition exists. Refer to details on How To Clear a Fault, below.
Figure 6.1 Fault Display
Diagnostics
How To Clear a Fault Drives equipped with a Human Interface Module will display a brief fault message on Line 1 of the LCD display when a fault occurs. Line 2 of the display indicates the corresponding fault number. Important: For Series A HIM software version 3.00 and Above or Series B HIM software version 1.01 and Above, faults are displayed as soon as they occur. Earlier HIM versions only display faults when the HIM is in the Status Display Mode. [Fault Buffer 0] through [Fault Buffer 3] display previous faults. Table 6.A lists all faults numerically with a cross reference to the page number where information can be found relating to that fault. Table 6.B provides an alphabetized listing of the faults with a description and possible corrective action to take.
Important: Resetting a fault will not correct the cause of the fault condition. Corrective action must be taken prior to resetting the fault. To clear a fault perform one of the following: 1. Cycle power to the drive. 2. Cycle the stop signal to the drive. 3. Cycle the [Clear Fault] parameter. See page 5-39. Important:The stop signal will not clear a fault if the [Logic Mask] or [Fault Mask] bit of that adapter has been disabled or the [Fault Clear Mode] parameter is disabled.
Page 126
6-2
Troubleshooting and Fault Information
Table 6.A Fault Code Cross Reference Fault Number
Fault Name
Page
Fault Number
Fault Name
Page
F3 F4 F5 F6 F7
Power Loss Fault Undervolt Fault Overvolt Fault Motor Stall Fault Overload Fault
6-7 6-8 6-6 6-5 6-6
F36 F38 F39 F40 F41
Diag C Lim Flt Phase U Fault Phase V Fault Phase W Fault UV Short Fault
6-3 6-6 6-6 6-6 6-8
F8 F9 F10 F11 F12
Overtemp Fault Open Pot Fault Serial Fault Op Error Fault Overcurrent Flt
6-6 6-5 6-7 6-5 6-6
F22 F24 F25 F26 F29
Drive Reset Flt Motor Mode Flt Overspeed Flt Power Mode Fault Hz Err Fault
6-3 6-5 6-6 6-7 6-3
F42 F43 F44 F45 F46 F48
UW Short Fault VW Short Fault IPM Current Fault IPM Overtemp Fault Power Test Fault Reprogram Fault
6-8 6-8 6-4 6-4 6-6 6-7
– – – –
Drive → HIM➀ HIM → Drive➀ Network Error ✳ ➀ Pin ID Error➀
6-3 6-4 6-5 6-7
F30 F32 F33 F34 F35
Hz Sel Fault EEprom Fault Max Retries Fault Run Boost Fault Neg Slope Fault
6-3 6-3 6-4 6-7 6-5
➀ These faults are generated in the HIM and not stored in the drive EEPROM.
Page 127
Troubleshooting and Fault Information Table 6.B 1305 Fault Descriptions Name & Fault Number
Description
Action to Take
Diag C Lim FauIt F36
The drive output current has exceeded the software [Current Limit] and the [Cur Lim Trip En] parameter was enabled.
Check programming of [Curr Lim Trip En] parameter. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess current.
Drive → HIM
The checksum read from the HIM’s EEPROM does not match the Repeat operation. Replace HIM. checksum calculated from the EEPROM data.
Drive Reset FauIt F22
Occurs on power-up. Caused by having the Start Input (or Run Check stop connection at TB2, terminal 8. Input) closed, with the Stop Input open and [Run On Power Up] = Disabled.
EEprom Fault F32
EEPROM has invalid data or can not be programmed to valid data.
Hz Err Fault F29
This fault indicates that there is not a valid operating frequency. 1. Check [Minimum Freq] and [Maximum Freq] parameters. It can be caused by any of the following: 2. Check [Skip Freq 1], [Skip Freq 2], [Skip Freq 3] and [Skip Freq Band] parameters. 1. [Maximum Frequency] is less than [Minimum Freq]. 2. Skip frequencies and skip bandwidth eliminate all operating 3. Check for broken wires, loose connections or transducer loss at 4-20mA input, TB2. frequencies. 3. 4-20mA input signal speed reference has been lost or is out of range and [4-20mA Loss Sel] is set for ‘‘Stop-Fault.”
Hz Sel Fault F30
An adapter that is not connected has been chosen as the active Connect proper adapter or change active frequency source. frequency source.
Check cable connection from main control board to power board. Reset to Default Parameters and Cycle power.
6-3
Page 128
6-4
Troubleshooting and Fault Information
Table 6.B 1305 Fault Descriptions (continued) Fault Name & Number
Fault Description
Action to Take
HIM → Drive
Error 1 – The checksum read from the HIM’s EEPROM does not Repeat operation. Old profile corrupt. Save new profile. Repeat match the checksum calculated from the EEPROM data. operation. Error 2 – The number of parameters in saved profile does not equal master.
The last parameter programmed will be displayed on the top line. Verify that all parameters have been programmed. If not, manually program any remaining parameters.
Error 3 – Download was attempted to a different type drive (i.e. 1336->1305).
Download can only take place with the same type of drive.
Error 4 – Saved data for parameter not correct for new drive.
Capabilities of drive are different than the master drive. Press Enter to continue download. When download is complete, manually program the parameter where the error occurred.
Error 5 – Drive is running while attempting download.
Stop drive, then perform download.
IPM Current Fault F44
The internal power module overcurrent limit had been exceeded. Check for short circuit at the drive output or excessive load conditions at the motor, specifically cable capacitance to ground.
IPM Overtemp Fault F45
The internal power module thermal limit has been exceeded.
Check for blocked or dirty heat sink fins. Check for proper mounting and spacing (See page 2-1). Check if the ambient temperature limit has been exceeded.
Max Retries Fault F33
Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Reset/Run Tries].
Check fault buffer for fault code requiring reset. Correct the cause of the fault and manually clear by cycling the stop command or cycling power.
Page 129
Troubleshooting and Fault Information Table 6.B 1305 Fault Descriptions (continued) Fault Name & Number Motor Mode FIt F24
Fault Description Internal error.
Action to Take Reset drive to factory defaults.
Motor Stall Fault F6
The motor is stalled.
If the motor is drawing excessive current, the motor load is excessive and will not allow the drive to accelerate to set speed. A longer accel time or a reduced load may be required.
Neg Slope Fault F35
Drive software detected a portion of the volts/Hz curve with a negative slope.
Check drive programming. 1. [Base Voltage] parameter must be greater than 1.5 X [Start Boost]. 2. If the [DC Boost Select] parameter is set to ‘‘Break Point,’’ [Base Voltage] must be greater than [Break Voltage] and [Break Voltage] must be greater than [Start Boost].
Network Error ✳
Network Error 0 – Error 6 Network Error 7 – Error 9
Op Error Fault F11 Open Pot Fault F9
ScanPort Error Communications Error
1. Press the “UP” or “DOWN” arrow to clear the message from the HIM display. 2. Unplug the HIM from the cable or drive and re-connect. 3. Check for external noise sources. [Motor Type] is set to “Sync PM” and [Stop Mode] is set to “DC Change one of these parameters. DC Braking cannot be used Brake”. with a synchronous motor. An external pot is connected and the ground lead of the pot is Check the external potentiometer circuit at TB2, terminals 1, 2 disconnected creating a potential drive overspeed hazard. and 3 for an open circuit.
6-5
Page 130
6-6
Troubleshooting and Fault Information
Table 6.B 1305 Fault Descriptions (continued) Fault Name & Number Fault Description
Action to Take
Overcurrent FauIt F12
Overcurrent is detected in overcurrent hardware trip circuit.
Check for a short circuit at the drive output or excessive load conditions at the motor.
Overload Fault F7
Internal electronic overload trip.
An excessive motor load exists. It must be reduced such that drive output current does not exceed the % of current set by the [Overload Current] parameter. Reduce [Start Boost] if applicable. Change [Cable Length] to “Long” if applicable.
Overspeed Fault F25 Overtemp Fault F8
Internal error.
Reset drive to factory defaults.
Temperature sensor detects excessive heat.
Check for blocked or dirty heat sink fins. Check for proper mounting and spacing (See page 2-1). Check if the ambient temperature limit has been exceeded.
Overvolt Fault F5
DC bus voltage exceeded maximum value.
Monitor the AC line for high line voltage or transient conditions.
Phase U Fault F38
A phase to ground fault has been detected between the drive and motor in this phase.
Check the wiring between the drive and motor. Check motor for grounded phase.
Phase V Fault F39
A phase to ground fault has been detected between the drive and motor in this phase.
Check the wiring between the drive and motor. Check motor for grounded phase.
Phase W Fault F40
A phase to ground fault has been detected between the drive and motor in this phase.
Check the wiring between the drive and motor. Check motor for grounded phase.
Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.
Page 131
Troubleshooting and Fault Information Table 6.B 1305 Fault Descriptions (continued) Fault Name & Number
Fault Description
Action to Take
Pin ID Error
Communication Hardware problem.
1. Unplug the HIM from the cable or drive and re-connect. 2. Replace Communication Cable.
Power Loss Fault F3
DC bus voltage remained below 85% of nominal for longer than Monitor the incoming AC line for low voltage or line power 0.500 sec. [Line Loss Fault] parameter is programmed to “F03 interruption. Enable”.
Power Mode Fault F26
Internal error.
Reset drive to factory defaults.
Power Test Fault F46
Fault detected during initial start-up sequence.
Check drive wiring. Check motor wiring. Reset drive to factory defaults.
Reprogram Fault F48
Occurs when drive parameters are reset to defaults.
Clear fault.
Run Boost Fault F34
An attempt has been made to set the [Run Boost] parameter to Verify that parameter has been programmed correctly. a value greater than the [Start Boost] parameter.
Serial Fault F10
An active local bus adapter is disconnected while it possesses control of a local bus function.
Check for break in communications line.
6-7
Page 132
6-8
Troubleshooting and Fault Information
Table 6.B 1305 Fault Descriptions (continued) Fault Name & Number Undervolt Fault F4
Fault Description DC Bus voltage fell below the minimum value. [Line Loss Fault] parameter is programmed to “U Volt Run”.
Action to Take Monitor the incoming AC line for low voltage or line power interruption.
UV Short Fault F41
Excessive current has been detected between these two drive output terminals.
Check the motor and external wiring to the drive output terminals for a shorted condition.
UW Short Fault F42
Excessive current has been detected between these two drive output terminals.
Check the motor and external wiring to the drive output terminals for a shorted condition.
VW Short Fault F43
Excessive current has been detected between these two drive output terminals.
Check the motor and external wiring to the drive output terminals for a shorted condition.
Page 133
Troubleshooting and Fault Information Table 6.C Troubleshooting General Problem
Action to Take
Motor does not start (No output voltage to motor) (“Stopped” is displayed on the HIM).
(1) Check power circuit - Check supply voltage. - Check all fuses and disconnects. (2) Check motor - Verify that motor is connected properly. (3) Check control input signals. - Verify that Enable signal is present. (“Not Enabled” is displayed on the HIM) - Verify that Start signal is present. - Verify that Stop signal is present. - Verify that Run Forward and Run Reverse signals are NOT both active. (4) Check parameter mask settings - Verify that [Start Mask] is set properly. - Verify that [Logic Mask] is set properly. - Verify that [Local Mask] is set properly.
Drive Started but motor NOT rotating. (1) Check motor - Verify that motor is connected properly. (“At Speed 0.00 Hz” is displayed on HIM). (2) Check Frequency Source - Verify that frequency signal is present at terminal block TB2. - 4-20mA signal - 0-10V signal -Remote Potentiometer - Verify that Adapter or Preset Frequencies are set properly. (3) Check control input signals. - Verify that SW1, SW2 and SW3 are in the proper state. (Refer to Table 5.A on page 5-29) (4) Check parameter settings and charts on Pages 5-29 and 5-30. - Verify that [Freq Source] is showing the desired frequency source. - Verify that [Freq Command] is the desired value. - Verify that [Reference Mask] is set properly.
6-9
Page 134
6-10
Troubleshooting and Fault Information
Table 6.C Troubleshooting (continued) General Problem
Action to Take
Motor not accelerating properly.
(1) Check motor - Verify that motor is connected properly. - Verify that no mechanical problems exist. 2) Check control input signals - Verify that SW1, SW2, and SW3 are in the proper state to select desired Accel/Decel rates. (Refer to Table 5.A on page 5-29) (4) Check parameter settings and charts on Pages 5-29 and 5-30. - Verify that [Accel Time 1] and [Accel Time 2] are set properly. - Verify that [Current Limit] is set properly. - Verify that [DC Boost Select] is set correctly. - Verify that [Start Boost] and [Run Boost] are set properly.
Specific Problem
Action to Take
Can not Jog from Adapter.
(1) Verify that [Jog Mask] is set properly to allow jogging from that adapter. (2) Verify that [Logic Mask] is set properly to allow jogging from that adapter. (3) Is drive already running? (4) Examine [Stop Owner] to verify that a maintained Stop does not exist.
Can not change direction from Adapter.
(1) Verify that [Direction Mask] is set to allow direction changes from that adapter. (2) Verify that [Logic Mask] is set to allow direction changes from that adapter.
Can not Start from Adapter.
(1) Verify that [Start Mask] is set properly to allow starting from that adapter. (2) Verify that [Logic Mask] is set properly to allow starting from that adapter. (3) Is drive already running? (4) Examine [Stop Owner] to verify that a maintained Stop does not exist.
Display indicates “Not Enabled”.
(1) Check enable signal at TB2, terminals 11 & 12.
Page 135
Troubleshooting and Fault Information
Table 6.C Troubleshooting (continued) Specific Problem
Action to Take
Can not operate in “Run Fwd/Run Rev” mode.
(1) Verify that [Input Mode] is set correctly. (2) Has power been cycled for above change to take effect? (3) Are both Run Forward and Run Reverse switches active?
Can not change speed from Adapter.
(1) Verify that the speed source is the adapter in question. (examine [Freq Source] parameter).
Can not operate drive without HIM.
(1) Verify that SW1, SW2, and SW3 are in the proper state to select the desired speed source. (Refer to charts on Pages 5-29 and 5-30) (2) Verify that [Freq Source] and [Freq Command] are desired values.
Drive faults when Adapter is unplugged.
(1) Verify that [Logic Mask] is set properly to allow removal of a particular Adapter while drive is powered up. (2) Verify that the adapter being unplugged is not the active frequency source.
Pin ID Error is displayed on HIM.
(1) Unplug the HIM from the cable or drive and re-connect.
“Network Error ✳” is displayed on the HIM.
(1) Press the “Up” or “Down” arrow to clear the message from the HIM display. (2) Unplug the HIM from the cable or drive and re-connect.
Can not clear fault from Adapter or Terminal Block with stop command.
(1) Verify that [Fault Clear Mode] is set to “Enabled” (2) Verify that [Fault Mask] is set to allow clearing of faults from chosen device. (3) Verify that [Logic Mask] is set properly.
6-11
Page 136
6-12
Troubleshooting and Fault Information
This Page Intentionally Left Blank.