Block Diagram and Specifications
Appendix A
BLOCK DIAGRAM DC+
CB
U V
T
W
Fuses
GRD
Rectifier
Start TB2-6 Stop TB2-8
➀
BRK
R S IPM Control Power
TB2-7 Common Drive TB2-11 ➀ Enable Common TB2-12 Reverse
Jog
TB2-13 TB2-14
Bus Voltage Circuitry
Motor
Fault Feedback Opto Isolator
Port 1
CPU
Port 2
TB2-5
TB2-17
Analog Circuitry
SW2 TB2-18
0-10V 4-20ma
Option Module
Serial Port Frequency Meter
SW1
Freq ref pot
GRD
Current Circuitry
TB2-16
SW3
Human Interface Module
TB2-3 Common
Analog Output 0-10 Volts
TB2-15 TB2-1 TB2-2 TB2-3 TB2-4
Relay Circuitry
TB2-9 TB2-10 TB2-19 TB2-20
Customer Programmable Outputs
➀ Required to run drive
Page 138
A-2
Block Diagram and Specifications
Table A.1 Specifications Bulletin 1305 Drive Rated 200-230 V AC
Drive
Bulletin 1305 Drives Rated 380-460 V AC
-AA02A
-AA03A
-AA04A
-AA08A
-AA12A
-BA01A
-BA02A
-BA03A
-BA04A
-BA06A
-BA09A
Three-Phase Motor Rating kW (HP)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.5 (2)
2.2 (3)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.5 (2)
2.2 (3)
4.0 (5)
Output Current (A) ➀➁
2.3
3.0
4.5
8.0
12.0 ➂
1.3
1.6
2.3
4.0
6.0 ➃
9.0 ➄
OUTPUT RATINGS
Output Voltage
Adjustable from 0 V to Input Voltage
Output Frequency (Hz)
0.00 to 400.00 Hz Programmable
SCANport Load
250 mA maximum (all adapters combined)
INPUT RATINGS Input Voltage & Frequency
200/230V Three Phase, 50/60 Hz
380/460V Three Phase, 50/60 Hz
180-265V, 47-63 Hz
340V-500V, 47-63 Hz
Operational Range (V) Input kVA
0.9
1.3
1.7
3.1
4.6
0.9
Power Factor (Displacement)
0.8 (Lagging)
Efficiency (%)
97.5 % (Typical)
Power Dissipation (W)
27
34
46
76
108
21
1.3
1.7
3.1
4.6
7.0
27
34
52
73
107
In general: ➀ Motor Full Load Amps (FLA) should not exceed the drive output current rating. ➁ If the [PWM Frequency] is set above 4kHz, the output current must be derated per the chart on page 5-20. When operating the drive in an ambient temperature at or near the maximum operating temperature (50°C), the following derating guidelines are recommended to guard against overheating depending on application and operating conditions. ➂ Output current value listed for 200V input voltage. At 230V input voltage, output current is 9.6A for 3 phase and 6.8A for single phase. ➃ Output current value listed for 380V input voltage. At 415V input voltage, output current is 5.3A. At 460V input voltage, output current is 4.8A. ➄ Output current value listed for 380V input voltage. At 415V input voltage, output current is 8.4A. At 460V input voltage, output current is 7.6A. For derating guidelines at ambient temperatures between 40°C and 50°C, consult Allen-Bradley.
Page 139
Block Diagram and Specifications Table A.1 Specifications (continued) ENVIRONMENTAL SPECIFICATIONS Enclosure
NEMA 1 (IP30) standard
Ambient Temperature
0 to 50_C; Optional Enclosures: 0 to 40_C
Storage Temperature
-40_C to 70_C
Relative Humidity
0 to 95% (non condensing)
Vibration Cooling Method Altitude CONTROL INPUTS Control Input Type Start Stop Forward/Reverse
1.0 G Operational Natural Convection (no fans) Above 1,000 m (3,300 ft), derate at 6% of drive rated amps per 1000 m Contact closure (Internal 5V supply) DO NOT ground or apply external voltage Configurable Inputs for 2 or 3 wire control
Jog
Momentary (non-maintained) Input
SW1 SW2 SW3
Configurable Inputs for control of 7 Preset speeds and 2 Accel/Decel times
Enable
Interlock Input to enable drive operation
External Speed Potentiometer
10 K Ohms, 1 Watt
Analog Input (4 to 20mA)
Input lmpedance 250 Ohms (Non-Isolated), 10 bit resolution
Analog Input (0 to 10 V DC)
Input Impedance 100 K Ohms (Non-Isolated), 10 bit resolution
A-3
Page 140
Block Diagram and Specifications
A-4
Table A.1 Specifications (continued) CONTROL OUTPUTS Programmable Output 1
Form A Relay Contact: Resistive Rating 115V AC/ 30V DC, 5A; Inductive Rating 115V AC/ 30V DC, 2A
Programmable Output 2
Open Collector (Sink): 24V DC, -20%, 50 mA maximum (User supplied source voltage)
Analog Output (0 to 10V DC)
Load lmpedance - 4,000 Ohms, 8 bit resolution
PWM AIgorithm
Sine Weighted PWM Output
Switching Device 3-Phase Output
IGBT Intelligent Power Module
V/Hz Ratio
Programmable
Carrier Frequency
Adjustable in 100Hz Increments from 2 kHz to 8 kHz. Output Current Derating applies above 4 kHz.
DC Boost
Adjustable single point or full custom – Start and Run boost available
CONTROL FEATURES Bulletin 1305 Drive Rated 200-240 V AC
Drive
-AA02A
-AA03A
-AA04A
-AA08A
Bulletin 1305 Drives Rated 380-460 V AC -AA12A
-BA01A
-BA02A
-BA03A
-BA04A
-BA06A
-BA09A
AC Dynamic Braking Torque - Estimated - Actual value will depend on motor characteristics W/0 External Resistor
100%
100%
100%
With External Resistor
N/A
N/A
N/A
Current Limiting Overload
50%
50%
100%
100%
100%
50%
50%
20%
150%
100%
150%
150%
150%
150%
100%
100%
Trip Free Operation, Co-ordinated for Drive and Motor Protection Programmable from 20% to 150% of Drive Rated Current 200%, Fixed by hardware, based on drive rating 150% for 60 seconds
Page 141
Block Diagram and Specifications Table A.1 Specifications (continued) Motor Protection➀
Electronic Overload Protection. Adjustable from 20% to 115% (Motor FLA)
Overload Pattern #0
Flat response over speed range (no current derating)
Overload Pattern #1
Current derating below 25% of Base Speed
Overload Pattern #2 Accel/Decel Time(s) Preset Speeds
Current derating below 50% of Base Speed 0.1 to 3600 Seconds, independently set (2 Accel, 2 Decel) 0 to 400 Hz, 7 selections, independently set
Jog Input
0 to 400 Hz
Stopping Modes
4 modes programmable
Ramp to stop
0.1 to 3600 seconds
Coast DC Brake to stop S-Curve
Stops all PWM Output Applies DC Voltage to the Motor for 0 to 150 seconds Ramps to stop with S-Curve profile
PROTECTIVE FEATURES Excessive Temperature
Embedded temperature sensor trips if factory preset level is exceeded➁
Over/Under Voltage
DC Bus voltage is monitored
Power Ride Through
Minimum ride through 15mS under nominal conditions
Control Ride Through
Minimum ride through is 0.5 Seconds – typical value 2 seconds
Ground Short
Any output short to ground, detected prior to start
Line Voltage Transients
Inherent MOV (varistor) protection
Output Short Circuit
Inherent short circuit protection provided within IPM
➀ See Page 5-12 for NEC and UL information. ➁ Conditions such as ambient temperature, overload, duty cycle, etc. can affect tripping time.
A-5
Page 142
A-6
Block Diagram and Specifications
Table A.1 Specifications (continued) PROGRAMMING/COMMUNICATIONS Adapters
The maximum current draw of all adapters connected to the drive should not exceed 250 mA
Hand Held Programming
Optional Human Interface Module (HIM can be removed from the Drive)
Type of Annunciation
Parameters displayed in textual form, organized in Iogical groupings
Type of Display Language Capability Local Controls Communication Adapters
16 character, 2 line LCD supertwist with backlight Multiple Languages available 3 versions available ( Digital Pot., Analog Pot. and Blank) Optional adapters provide Remote I/0, or RS232/RS422/RS485/DF1/DH485, or DeviceNet capability
MONITORING Output Frequency (Hz)
Displayed over the entire range of operation with direction indication
Output Voltage (V)
Selectable as a displayed parameter
Output Current (A)
Selectable as a displayed parameter in % or actual value
Output Power (kW)
Selectable as a displayed parameter in % or actual value
DC Bus Voltage (V)
Selectable as a displayed parameter
Frequency Command (Hz)
Selectable as a displayed parameter
Process Parameter
Any drive variable can be scaled and definable text can be added up to 8 characters
Drive Temperature _C
Selectable as a displayed parameter
Last Fault
The previous 4 faults can be displayed for troubleshooting