User Manual: 1305 Adjustable Frequency AC Drive (Series C): A - Block Diagram & Specifications

Pages 137 to 142 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1305-BA03A

Page 137

Block Diagram and Specifications

Appendix A

BLOCK DIAGRAM DC+

CB

U V

T

W

Fuses

GRD

Rectifier

Start TB2-6 Stop TB2-8

➀

BRK

R S IPM Control Power

TB2-7 Common Drive TB2-11 ➀ Enable Common TB2-12 Reverse

Jog

TB2-13 TB2-14

Bus Voltage Circuitry

Motor

Fault Feedback Opto Isolator

Port 1

CPU

Port 2

TB2-5

TB2-17

Analog Circuitry

SW2 TB2-18

0-10V 4-20ma

Option Module

Serial Port Frequency Meter

SW1

Freq ref pot

GRD

Current Circuitry

TB2-16

SW3

Human Interface Module

TB2-3 Common

Analog Output 0-10 Volts

TB2-15 TB2-1 TB2-2 TB2-3 TB2-4

Relay Circuitry

TB2-9 TB2-10 TB2-19 TB2-20

Customer Programmable Outputs

➀ Required to run drive

Page 138

A-2

Block Diagram and Specifications

Table A.1 Specifications Bulletin 1305 Drive Rated 200-230 V AC

Drive

Bulletin 1305 Drives Rated 380-460 V AC

-AA02A

-AA03A

-AA04A

-AA08A

-AA12A

-BA01A

-BA02A

-BA03A

-BA04A

-BA06A

-BA09A

Three-Phase Motor Rating kW (HP)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.5 (2)

2.2 (3)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.5 (2)

2.2 (3)

4.0 (5)

Output Current (A) ➀➁

2.3

3.0

4.5

8.0

12.0 ➂

1.3

1.6

2.3

4.0

6.0 ➃

9.0 ➄

OUTPUT RATINGS

Output Voltage

Adjustable from 0 V to Input Voltage

Output Frequency (Hz)

0.00 to 400.00 Hz Programmable

SCANport Load

250 mA maximum (all adapters combined)

INPUT RATINGS Input Voltage & Frequency

200/230V Three Phase, 50/60 Hz

380/460V Three Phase, 50/60 Hz

180-265V, 47-63 Hz

340V-500V, 47-63 Hz

Operational Range (V) Input kVA

0.9

1.3

1.7

3.1

4.6

0.9

Power Factor (Displacement)

0.8 (Lagging)

Efficiency (%)

97.5 % (Typical)

Power Dissipation (W)

27

34

46

76

108

21

1.3

1.7

3.1

4.6

7.0

27

34

52

73

107

In general: ➀ Motor Full Load Amps (FLA) should not exceed the drive output current rating. ➁ If the [PWM Frequency] is set above 4kHz, the output current must be derated per the chart on page 5-20. When operating the drive in an ambient temperature at or near the maximum operating temperature (50°C), the following derating guidelines are recommended to guard against overheating depending on application and operating conditions. ➂ Output current value listed for 200V input voltage. At 230V input voltage, output current is 9.6A for 3 phase and 6.8A for single phase. ➃ Output current value listed for 380V input voltage. At 415V input voltage, output current is 5.3A. At 460V input voltage, output current is 4.8A. ➄ Output current value listed for 380V input voltage. At 415V input voltage, output current is 8.4A. At 460V input voltage, output current is 7.6A. For derating guidelines at ambient temperatures between 40°C and 50°C, consult Allen-Bradley.

Page 139

Block Diagram and Specifications Table A.1 Specifications (continued) ENVIRONMENTAL SPECIFICATIONS Enclosure

NEMA 1 (IP30) standard

Ambient Temperature

0 to 50_C; Optional Enclosures: 0 to 40_C

Storage Temperature

-40_C to 70_C

Relative Humidity

0 to 95% (non condensing)

Vibration Cooling Method Altitude CONTROL INPUTS Control Input Type Start Stop Forward/Reverse

1.0 G Operational Natural Convection (no fans) Above 1,000 m (3,300 ft), derate at 6% of drive rated amps per 1000 m Contact closure (Internal 5V supply) DO NOT ground or apply external voltage Configurable Inputs for 2 or 3 wire control

Jog

Momentary (non-maintained) Input

SW1 SW2 SW3

Configurable Inputs for control of 7 Preset speeds and 2 Accel/Decel times

Enable

Interlock Input to enable drive operation

External Speed Potentiometer

10 K Ohms, 1 Watt

Analog Input (4 to 20mA)

Input lmpedance 250 Ohms (Non-Isolated), 10 bit resolution

Analog Input (0 to 10 V DC)

Input Impedance 100 K Ohms (Non-Isolated), 10 bit resolution

A-3

Page 140

Block Diagram and Specifications

A-4

Table A.1 Specifications (continued) CONTROL OUTPUTS Programmable Output 1

Form A Relay Contact: Resistive Rating 115V AC/ 30V DC, 5A; Inductive Rating 115V AC/ 30V DC, 2A

Programmable Output 2

Open Collector (Sink): 24V DC, -20%, 50 mA maximum (User supplied source voltage)

Analog Output (0 to 10V DC)

Load lmpedance - 4,000 Ohms, 8 bit resolution

PWM AIgorithm

Sine Weighted PWM Output

Switching Device 3-Phase Output

IGBT Intelligent Power Module

V/Hz Ratio

Programmable

Carrier Frequency

Adjustable in 100Hz Increments from 2 kHz to 8 kHz. Output Current Derating applies above 4 kHz.

DC Boost

Adjustable single point or full custom – Start and Run boost available

CONTROL FEATURES Bulletin 1305 Drive Rated 200-240 V AC

Drive

-AA02A

-AA03A

-AA04A

-AA08A

Bulletin 1305 Drives Rated 380-460 V AC -AA12A

-BA01A

-BA02A

-BA03A

-BA04A

-BA06A

-BA09A

AC Dynamic Braking Torque - Estimated - Actual value will depend on motor characteristics W/0 External Resistor

100%

100%

100%

With External Resistor

N/A

N/A

N/A

Current Limiting Overload

50%

50%

100%

100%

100%

50%

50%

20%

150%

100%

150%

150%

150%

150%

100%

100%

Trip Free Operation, Co-ordinated for Drive and Motor Protection Programmable from 20% to 150% of Drive Rated Current 200%, Fixed by hardware, based on drive rating 150% for 60 seconds

Page 141

Block Diagram and Specifications Table A.1 Specifications (continued) Motor Protection➀

Electronic Overload Protection. Adjustable from 20% to 115% (Motor FLA)

Overload Pattern #0

Flat response over speed range (no current derating)

Overload Pattern #1

Current derating below 25% of Base Speed

Overload Pattern #2 Accel/Decel Time(s) Preset Speeds

Current derating below 50% of Base Speed 0.1 to 3600 Seconds, independently set (2 Accel, 2 Decel) 0 to 400 Hz, 7 selections, independently set

Jog Input

0 to 400 Hz

Stopping Modes

4 modes programmable

Ramp to stop

0.1 to 3600 seconds

Coast DC Brake to stop S-Curve

Stops all PWM Output Applies DC Voltage to the Motor for 0 to 150 seconds Ramps to stop with S-Curve profile

PROTECTIVE FEATURES Excessive Temperature

Embedded temperature sensor trips if factory preset level is exceeded➁

Over/Under Voltage

DC Bus voltage is monitored

Power Ride Through

Minimum ride through 15mS under nominal conditions

Control Ride Through

Minimum ride through is 0.5 Seconds – typical value 2 seconds

Ground Short

Any output short to ground, detected prior to start

Line Voltage Transients

Inherent MOV (varistor) protection

Output Short Circuit

Inherent short circuit protection provided within IPM

➀ See Page 5-12 for NEC and UL information. ➁ Conditions such as ambient temperature, overload, duty cycle, etc. can affect tripping time.

A-5

Page 142

A-6

Block Diagram and Specifications

Table A.1 Specifications (continued) PROGRAMMING/COMMUNICATIONS Adapters

The maximum current draw of all adapters connected to the drive should not exceed 250 mA

Hand Held Programming

Optional Human Interface Module (HIM can be removed from the Drive)

Type of Annunciation

Parameters displayed in textual form, organized in Iogical groupings

Type of Display Language Capability Local Controls Communication Adapters

16 character, 2 line LCD supertwist with backlight Multiple Languages available 3 versions available ( Digital Pot., Analog Pot. and Blank) Optional adapters provide Remote I/0, or RS232/RS422/RS485/DF1/DH485, or DeviceNet capability

MONITORING Output Frequency (Hz)

Displayed over the entire range of operation with direction indication

Output Voltage (V)

Selectable as a displayed parameter

Output Current (A)

Selectable as a displayed parameter in % or actual value

Output Power (kW)

Selectable as a displayed parameter in % or actual value

DC Bus Voltage (V)

Selectable as a displayed parameter

Frequency Command (Hz)

Selectable as a displayed parameter

Process Parameter

Any drive variable can be scaled and definable text can be added up to 8 characters

Drive Temperature _C

Selectable as a displayed parameter

Last Fault

The previous 4 faults can be displayed for troubleshooting