For the Allen-Bradley 1305-BA03A

Page 143

Serial Communications

Appendix B

COMMUNICATIONS USING BULLETIN 1203 COMMUNICATION MODULES

Table B.1 Remote I/O Data Transfer

Bulletin 1305 drive parameter data can be programmed and displayed using PLC’s, SLC’s or other logic controllers using an optional Bulletin 1203 Communication Module. The amount of information that can be transferred between the drive and controller is determined by the DIP switch settings on the Communication Module.

SW3 Settings

Type of Data Transferred

No. 1

Block transfer of data

1

➀

No. 2

Logic commands and Drive Status information

1

See Table B.2 & Table B.3

No. 3

Analog frequency reference

1

➁

Table B.1 illustrates the dip switch settings for Bulletin 1203-GD1 (Remote I/O) communication modules. Dip switch settings for other communication modules will be similar. Refer to the appropriate communication module user manual for details.

No. 4

Parameter data via Datalink A

2

See Page 5-54

No. 5

Parameter data via Datalink B

2

See Page 5-54

No. 6

Parameter data via Datalink C

2

See Page 5-54

No. 7

To transfer data via Datalink D

2

See Page 5-54

Important: 1305 drives with firmware revisions FRN1.01 and FRN1.02 are not compatible with Bulletin 1203 Communication Modules. If connected, an error message will be indicated. The red fault status and amber SCANportT status LED’s on the front of the module will flash simultaneously.

No. 8

Unused

––

SCANport is a trademark of Allen-Bradley Company.

Rack Space in Words

Reference Information

––

➀ Refer to the Bulletin 1203 Communication Module Block Transfer User Manual. ➁ To enable the PLC to provide the frequency reference, Logic Bits 12 through 15 must be set to select [Freq Select 1] or [Freq Select 2] as the frequency reference (refer to Table B.2 ). The [Freq Select 1] or [Freq Select 2] parameters must then be set to the adapter number that the communication module is connected to. See Pages 2-24 and 5-25 for additional information on determining the Adapter number and [Freq Select 1] and [Freq Select 2] selections.

Page 144

B-2

Serial Communications

LOGIC CONTROL DATA

SCALE FACTOR CONVERSION

The information in Table B.2 provides the Logic Control information that is sent to the drive through the logic controllers output image table. When using the Bulletin 1203-GD1 communication module, this information is sent to the drive when dip switch No. 2 of SW3 is enabled.

When Reading parameter data in the controller’s input image table, divide this value by the “Drive Units Scale Factor” to determine the ‘‘Display Units.”

DRIVE STATUS DATA The information in Table B.3 provides the Drive Status information that will be sent to the logic controllers input image table from the drive. When using the Bulletin 1203-GD1 communication module this information will be sent to the PLC from the drive when switch No. 2 of SW3 is enabled.

PARAMETER GROUPS/USER SETTINGS The information in Table B.4 provides a listing of all drive parameters. The column entitled ‘‘Display Units” are the units that will appear on the Human Interface Module. Since certain parameters have different resolution than others, a scale factor is required to convert the “Display Units” value to a decimal value that will be displayed in the controller’s I/O image tables. The column marked “Drive Units Scale Factor” is provided to perform this conversion.

When Writing parameter data from the controller’s output image table to the drive, the value entered into the output image table should be the required “Display Units” value multiplied by the “Drive Units Scale Factor”. “Display Unit” equivalent to Parameter Text Descriptions. Some parameters use a text description in the place of numerical “Display Units”. The information in Table B.5 provides the decimal equivalent to the text descriptions.

Page 145

Serial Communications

B-3

Table B.2 Logic Control Data

This information will be displayed in the controller’s output image table and will be sent to the drive when the appropriate dip switch setting on the Communication Module is enabled. 15

14

13

12

11

10

9

Logic Bits 8 7 6

5

4

3

2

1

0 X

X X X X X X X X X

X

X

X

X

X

X

Status Stop

Text 1 = Stop, 0 = Not Stop

Start

1 = Start, 0 = Not Start

Jog

1 = Jog, 0 = Not Jog

Clear Faults

1 = Clear Faults 0 = Not Clear Faults

Direction

00 = No Command 10 = Reverse Command 01 = Forward Command 11 = Hold Direction Control

Local

1 = Local Lockout, 0 = Not Local

MOP Increment

1 = Increment, 0 = Not

Accel Time

00 = No Commd 10 = Accel Time 2 Commd 01 = Accel Time 1 Commd 11 = Hold Accel Time Ctrl

Decel Time

00 = No Commd Time 10 = Decel Time 2 Commd 01 = Decel Time 1 Commd 11 = Hold Time Ctrl

Reference Select

000 = No Command Select 001 = [Freq Select 1] (Selectable) 010 = [Freq Select 2] (Selectable) 011 = [Preset Freq 3] 100 = [Preset Freq 4] 101 = [Preset Freq 5] 110 = [Preset Freq 6] 111 = [Preset Freq 7]

MOP Dec

1 = Decrement, 0 = Not

Page 146

Serial Communications

B-4

Table B.3 Drive Status Data

This information will be displayed in the controller’s input image table when the appropriate dip switch setting on the Communication Module is enabled. 15

14

13

12

11

10

9

Logic Bits 8 7 6

5

4

3

2

1 X

X X X X X X X X

X

X

X

X

X

X

0 X

Status Enabled

Text 1 = Enabled, 0 = Not Enabled

Running

1 = Running, 0 = Not Running

Command Direction 1 = Forward, 0 = Reverse Rotating Direction

1 = Forward, 0 = Reverse

Accel

1 = Accelerating, 0 = Not

Decel

1 = Decelerating, 0 = Not

Alarm

1 = Alarm, 0 = No Alarm

Fault

1 = Faulted, 0 = Not Faulted

At Speed

1 = At Speed, 0 = NOT at Speed

Local

000 = TB2 Local 001 = Adapter 1 Local 010 = Adapter 2 Local 011 = Adapter 3 Local

100 = Adapter 4 Local 101 = Adapter 5 Local 110 = Adapter 6 Local 111 = No Local Control

Frequency Reference

0000 = Freq Select 1 0001 = Preset Freq 1 0010 = Preset Freq 2 0011 = Preset Freq 3 0100 = Preset Freq 4 0101 = Preset Freq 5 0110 = Preset Freq 6 0111 = Preset Freq 7

1000 = Freq Select 2 1001 = Port 1 Adapter 1 1010 = Port 2 Adapter 2 1011 = Port 3 Adapter 3 1100 = Port 4 Adapter 4 1101 = Port 5 Adapter 5 1110 = Port 6 Adapter 6 1111 = Jog Frequency

Page 147

Serial Communications

B-5

Table B.4 Parameter Grouping/User Settings

Metering

Group Parameter Name Output Current Output Voltage Output Power DC Bus Voltage Output Freq Freq Command MOP Hz Drive Temp Last Fault % Output Power % Output Curr

Parameter Number

Display Units

Drive Units Scale Factor ➁

54 1 23 53

Amps Volts kW Volts

66 65 42 70 4 3 2

Hz Hz Hz Degrees C Numeric % %

100 100 100 1

Minimum 0.00 0 0.00 0

Maximum Two times drive output current Maximum Voltage Two times rated drive output power 410 - 230V Drive 815 - 460V Drive

Factory Setting –– –– –– ––

32767 = Max. Freq 100 100 1 1 1 1

Max. Frequency 0.00 0.00 0 0 0 0

Maximum Frequency +400.00 400.00 100 Max. Fault Number 200% Drive Rated Power 200% of Rated Drive Output Current

–– 0.00 –– –– –– –– ––

➀ Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions ➁ Refer to page B-2.

User‘s Setting

Page 148

B-6

Serial Communications

Table B.4 Parameter Grouping/User Settings (continued)

Set Up

Group Parameter Name Input Mode Freq Select 1 Accel Time 1 Decel Time 1 Base Frequency Base Voltage Maximum Voltage Minimum Freq Maximum Freq Stop Select Current Limit Overload Mode Overload Current Sec Curr Limit Adaptive I Lim

Parameter Number

Display Units

Drive Units Scale Factor ➁

21 5 7 8 17 18 20 16 19 10 36 37 38 141 149

Text ➀ Text ➀ Seconds Seconds Hz Volts Volts Hz Hz Text ➀ % Text ➀ Amps % Text ➀

1 1 10 10 1 1 1 1 1 1 1 1 100 = DRC 1 1

Minimum –– –– 0.0 0.0 40 25% of DRV 25% of DRV

0 40 –– 20% of DRC

–– 20% of DRC

0% of DRC ––

➀ Refer to Table B.6 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions ➁ Refer to page B-2.

Maximum –– –– 3600.0 3600.0 400 100% of Drive Rated Volts 110% of Drive Rated Volts 120 400 –– 150% of Drive Rated Current (DRC) –– 115% of Drive Rated Current (DRC) 150% of Drive Rated Current (DRC) ––

Factory Setting Three Wire Adapter 1 10.0 10.0 60 Drive Rated Volts Drive Rated Volts 0 60 Ramp 150% of DRC No Derating 115% of DRC 0% of DRC Enabled

User‘s Setting

Page 149

Serial Communications

B-7

Table B.4 Parameter Grouping/User Settings (continued) Parameter Number

Display Units

Drive Units Scale Factor ➁

16 19 17 18 49 50

Hz Hz Hz Volts Hz Volts

Maximum Voltage DC Boost Select Start Boost

20 9 48

Run Boost PWM Frequency Analog Invert 4–20 mA Loss Sel Stop Select DC Hold Time DC HoId Volts DB Enable Motor Type Compensation

83 45 84 81 10 12 13 11 41 52

Advanced Set Up

Group Parameter Name Minimum Freq Maximum Freq Base Frequency Base Voltage Break Frequency Break Voltage

1 1 1 1 1 1

Minimum 0 40 40 25% of DRV 0 0

Maximum 120 400 400 100% of Max. Drive Rated Volts 120 50% of Max Drive Rated Volts

Factory Setting 0 60 60 Maximum DRV 30 Drive Size Dependent

Volts Text ➀ Volts

1 1 1

25% of DRV –– 0

110% of Max. Drive Rated Volts –– 25% of Max. Drive Rated Volts

Maximum DRV Break Point Drive Size Dependent

Volts kHz Text ➀ Text ➀ Text ➀ Seconds Volts Text ➀ Text ➀ Text ➀

1 10 1 1 1 100 1 1 1 1

0 2.0 –– –– –– 0.0 0 –– –– ––

25% of Max. Drive Rated Volt 8.0 –– –– –– 150.0 25% of Max. Drive Rated Volts –– –– ––

0 4.0 Disabled Stop/Fault Ramp 0.0 0 Disabled Induc/Reluc Comp

➀ Refer to Table B.1 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.

User‘s Setting

Page 150

B-8

Serial Communications

Table B.4 Parameter Grouping/User Settings (continued)

Frequency Set

Group Parameter Name Freq Select 1 Freq Select 2 Jog Frequency Prst/2nd Accel Upper Presets Accel Time 2 Decel Time 2 Preset Freq 1 Preset Freq 2 Preset Freq 3 Preset Freq 4 Preset Freq 5 Preset Freq 6 Preset Freq 7 Skip Freq 1 Skip Freq 2 Skip Freq 3 Skip Freq Band MOP Increment Analog Filter

Parameter Number

Display Units

Drive Units Scale Factor ➁

5 6 24 26 72 30 31 27 28 29 73 74 75 76 32 33 34 35 22 144

Text ➀ Text ➀ Hz Text ➀ Text ➀ Seconds Seconds Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz/Second Text ➀

1 1 100 1 1 10 10 100 100 100 100 100 100 100 1 1 1 1 1 1

Minimum –– –– 0.0 –– –– 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0 0 0 0 0.00 ––

➀ Refer to Table B.7 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.

Maximum –– ––– 400.0 –– –– 3600.0 3600.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400 400 400 15 255.00 ––

Factory Setting Adapter 1 Remote Pot 10.0 Preset Disabled 5.0 5.0 10.0 20.0 30.0 40.0 50.0 60.0 0.0 400 400 400 0 1.00 100%

User’s Setting