Page 79
Programming
5-11
Setup Group (continued) [Maximum Freq] This parameter sets the highest frequency the drive will output. Important: All analog inputs to the drive (4-20mA, 0-10V, Remote Pot) are scaled for the range [Minimum Freq] to [Maximum Freq]. Max hertz may be set to less than base hertz.
[Stop Select] This parameter selects the stopping mode when the drive receives a valid stop command.
Parameter # 19 Parameter Type Read & Write Units 1 Hz
Factory Default 60 Hz Minimum 40 Hz Maximum 400 Hz
Parameter # 10 Parameter Type Read & Write Units Text
Factory Default ‘‘Ramp” Settings ‘‘Coast” ‘‘Ramp”
‘‘DC Brake”
‘‘S-Curve”
[Current Limit] This parameter sets the maximum drive output current that is allowed before current limiting occurs. Important: If a value is programmed into the [Sec Curr Limit] parameter then that value will be the active current limit value at speeds above 1.5 times [Base Frequency]. See Fig. 5.5. [Output 1 Config] and [Output 2 Config] can be set to ‘‘alarm” to indicate an overload condition exists.
Parameter # 36 Parameter Type Read & Write Units 1 %
Important: This parameter can not be programmed while the drive is running.
Causes the Drive to Turn Off Immediately Drive Decelerates to 0 Hz, Then Turns Off – Requires a Value In [Decel Time 1] or [Decel Time 2] Injects DC Braking Voltage Into the Motor – Requires a Value in Both [Decel Hold Time] & [Decel Hold Level]. Drive ramps to stop using ‘fixed S-Curve’ profile. Stop time is twice the selected decel time.
Factory Default 150 % of Drive Rated Current ➀ Minimum 20 % of Drive Rated Current ➀ Maximum 150% of Drive Rated Current ➀ Important: See [Cur Lim Trip En] on page 5-40.
➀ The Drive Rated Ouput Current is based on three phase input ratings. See page 5-13 for instructions for Single Phase Input Ratings.
Page 80
Programming
5-12
Setup Group (continued)
Figure 5.2 No Derating 100 80 60 40 20 0
25 50 75 100 125 150 175 200 % Base Speed
[Overload Current] This value should be set to the motor nameplate Full Load Amps (F.L.A.).
Factory Default “No Derating” Settings ‘‘No Derating”
Figure 5.3 Min Derating 100 80 60 40 20 0
25 50 75 100 125 150 175 200 % Base Speed
Parameter # 38 Parameter Type Read & Write Units 0.1 Amps
10:1 Speed Range – No Derating Refer to Figure 5.2
‘‘Min Derate”
4:1 Speed Range – Derate below 25% of Base Speed. Refer to Figure 5.3
‘‘Max Derate”
2:1 Speed Range – Derate below 50% of Base Speed. Refer to Figure 5.4
% of [Overload Current] Setting
% of [Overload Current] Setting
This parameter selects the derating factor for the I2t electronic overload function. Designed to meet NEC Article 430 and UL (file E59272) equivalent requirements. Additional overload devices do not need to be installed.
Parameter # 37 Parameter Type Read & Write Units Text
% of [Overload Current] Setting
[Overload Mode]
Figure 5.4 Max Derating 100 80 60 40 20 0
Factory Default 115% of Drive Rated Current Minimum 20% of Drive Rated Current Maximum 115% of Drive Rated Current
25 50 75 100 125 150 175 200 % Base Speed
Displayed in Amps Displayed in Amps Displayed in Amps
Page 81
Programming
5-13
Setup Group (continued)
When this parameter is set to zero, the [Current Limit] setting is used throughout the frequency range. When set to a value other than zero, the [Current Limit] value will be active up to the [Base Frequency] setting, then tapers down between [Base Frequency] and 1.5 times [Base Frequency]. At frequencies above 1.5 times [Base Frequency], the [Sec Curr Limit] setting is the active current limit value.
Figure 5.5 Current Limit Setting
Parameter # 141 Parameter Type Read & Write Units 1%
% of Drive Output Current
[Sec Curr Limit]
Factory Default 0% of Drive Rated Current ➀ Minimum 0% of Drive Rated Current ➀ Maximum 150% of Drive Rated Current ➀ a [Current Limit] (36) a [Sec Curr Limit] (141) [Base Frequency] (17) 1.5 Times [Base Frequency] (17)
[Maximum Frequency] (19)
Single Phase Input Ratings The [Current Limit], [Overload Current] and [Sec Curr Limit] parameters are set based on the drive rated output current for three phase input ratings. When setting these parameters for single phase input ratings, use the following formula to determine the proper parameter setting: ➀ The Drive Rated Ouput Current is based on three phase input ratings. See Single Phase Input Ratings instructions.
1-Phase Output Current ➁ x Percent (0 to 150%) Three-Phase Output Current ➁ ➁ See Table 1.A on page 1-6.
= Parameter Setting in Percent
Page 82
5-14
Programming
Setup Group (continued) [Adaptive I Lim] When ENABLED (default), this parameter allows tripless commanded accelerations into medium to high inertia conditions and delivers maximum performance when drive load conditions change with time. For most circumstances this is the correct selection. When DISABLED, this parameter allows quicker acceleration times from stopped to commanded speed with low system inertia.
Parameter # 149 Parameter Type Read & Write Units Text
Factory Default “Enabled” Settings “Enabled” “Disabled”
Page 83
Programming
Advanced Setup
[Minimum Freq] This parameter sets the lowest frequency the drive will output.
This group contains parameters that are required to setup advanced functions of the drive such as custom Volts per Hertz settings and dynamic braking.
Parameter # 16 Parameter Type Read & Write Units 1 Hz
This parameter sets the highest frequency the drive will output.
Parameter # 19 Parameter Type Read & Write Units 1 Hz
This value should be set to the motor nameplate Rated Frequency.
Factory Default 60 Hz Minimum 40 Hz Maximum 400 Hz Important: This parameter can not be programmed while the drive is running.
Important: All analog inputs to the drive (4-20mA, 0-10V, Remote Pot) are scaled for the range [Minimum Freq] to [Maximum Freq]
[Base Frequency]
Factory Default 0 Hz Minimum 0 Hz Maximum 120 Hz Important: This parameter can not be programmed while the drive is running.
Important: All analog inputs to the drive (4-20mA, 0-10V, Remote Pot) are scaled for the range [Minimum Freq] to [Maximum Freq].
[Maximum Freq]
5-15
Parameter # 17 Parameter Type Read & Write Units 1 Hz
Factory Default 60 Hz Minimum 40 Hz Maximum 400 Hz
Page 84
5-16
Programming
Advanced Setup Group (continued) [Base Voltage] This value should be set to the motor nameplate Rated Voltage.
Parameter # 18 Parameter Type Read & Write Units 1 Volt
Factory Default Max. Drive Rated Volts Minimum 25% of Max. Drive Rated Volts Maximum 100% of Max. Drive Rated Volts
[Base Voltage] [Base Frequency] b
Figure 5.6 Standard Volts-per-Hz Pattern Motor Rated ' a [Maximum Voltage] [Maximum Frequency]
Voltage
0– 0
[Break Frequency] This parameter sets a midpoint frequency on a custom Volts-per-Hz curve. Combined with [Break Voltage], this value determines the Volts-per-Hz ratio between 0 and [Break Frequency]. Important: [DC Boost Select] must be set to ‘‘Break Point” for this parameter to be active.
Frequency
Parameter # 49 Parameter Type Read & Write Units 1 Hz y Motor Rated
Factory Default 30 Hz Minimum 0 Hz Maximum 120 Hz
Page 85
Programming
Advanced Setup Group (continued) [Break Voltage] Sets the voltage the drive will output at [Break Frequency]. Combined with [Break Frequency], this value determines the Volts-per-Hz ratio between 0 and [Break Frequency].
Parameter # 50
Sets the highest voltage the drive will output.
Minimum 0 Volts
Parameter Type Read & Write Units 1 Volt
Important: [DC Boost Select] must be set to ‘‘Break Point” to activate this parameter.
[Maximum Voltage]
Factory Default 115V for 230V Drive 230V for 460V Drive
Maximum 50% of Max. Drive Rated Volts
Parameter # 20 Parameter Type Read & Write Units 1 Volt
Factory Default Max. Drive Rated Volts Minimum 25% of Max. Drive Rated Volts Maximum 110% of Max. Drive Rated Volts
Important: [Maximum Voltage] does not have to be set greater than [Base Voltage], but the maximum drive output is limited to [Maximum Voltage].
Figure 5.7 Custom Volts-per-Hz Pattern
[Base Voltage] [Base Frequency]
Maximum '
This pattern is active only when [DC Boost Select] is set to ‘‘Break Point.” The following guidelines should be followed when setting up a custom Volts-per-Hz curve: 1. [Base Voltage] must be greater than [Start Boost]. 2. If [DC Boost Select] is set to “Break Point” then: [Base Voltage] must be greater than [Break Voltage] and [Break Voltage] must be greater than [Start Boost].
b
Motor Rated ' a [Maximum Voltage] [Maximum Frequency] b
Voltage
[Break Voltage] [Break Frequency]
Start Boost ' 0 0
Frequency y Motor Rated y Maximum
5-17
Page 86
Programming
5-18
Advanced Setup Group (continued) [DC Boost Select] This parameter sets the level of DC boost at low frequencies. It also selects special Volts-per-Hz patterns.
Parameter # 9 Parameter Type Read & Write Units Text
Factory Default ‘‘Break Point” Settings ‘‘No Boost” ‘‘6 Volts” ‘‘12 Volts” ‘‘18 Volts’’ ‘‘24 Volts’’ ‘‘30 Volts’’ ‘‘36 Volts’’ ‘‘42 Volts’’ ‘‘48 Volts’’ ‘‘Break Point’’ ‘‘Run Boost’’ ‘‘Fan Sel #1’’ ‘‘Fan Sel #2”
See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.8 See Figure 5.7 See Figure 5.10 See Figure 5.9 See Figure 5.9
Figure 5.8 Standard Boost Volts-per-Hz Pattern
Figure 5.9 Fan/Pump Volts-per-Hz Pattern
Active when [DC Boost Select] is set to ‘‘No Boost” or ‘‘6 Volts” through ‘‘48 Volts.”
These patterns are active only when [DC Boost Select] is set to ‘‘Fan Sel #1” or ‘‘Fan Sel #2.”
[Base Voltage] [Base Frequency] b a [Maximum Voltage] [Maximum Frequency]
Motor Rated '
Voltage
[Base Voltage] [Base Frequency] b
[Maximum Frequency]
Voltage 48
Fan Sel #2 ' a Fan Select #1
45% Base Voltage 35% Base Voltage
6 No Boost 0 0
Frequency y Motor Rated a [Maximum Voltage]
0 0 b 1/2 Base Frequency
Page 87
Programming
5-19
Advanced Setup Group (continued) [Start Boost]
Parameter # 48 Parameter Type Read & Write
This parameter sets the DC boost level for acceleration when [DC Boost Select] is set to ‘‘Run Boost” or ‘‘Break Point.”
Minimum 0 Volts
230V
0.37 kW (0.5 HP) 3 Volts
Maximum 25% of Max. Drive Rated Volts
460V
12 Volts
Factory Default See Table
Units 1 Volt
Figure 5.10 Start/Run Boost Active when [DC Boost Select] is set to ‘‘Run Boost”
Voltage
This parameter sets the DC boost level for constant speed level when [DC Boost Select] is set to ‘‘Run Boost.” [Run Boost] must be set at a value less than [Start Boost].
1.5 kW (2 HP) 3 Volts
2.2 kW (3 HP) 3 Volts
4.0 kW (5 HP) N/A
12 Volts
12 Volts
9 Volts
6 Volts
6 Volts a 150% of Start Boost a 150% of Run Boost 0
Parameter # 83 Parameter Type Read & Write Units 1 Volt
0.75 kW (1 HP) 3 Volts
[Base Voltage] [Base Frequency] b
[Start Boost] ' [Run Boost] ' 0–
[Run Boost]
0.55 kW (0.75 HP) 3 Volts
Frequency
Factory Default 0 Volts Minimum 0 Volts Maximum 25% of Max. Drive Rated Volts
Page 88
5-20
Programming
Advanced Setup Group (continued) [PWM Frequency] This parameter sets the carrier frequency for the PWM output waveform.
Parameter # 45 Parameter Type Read & Write Units 0.1 kHz
Factory Default 4.0 kHz Minimum 2.0 kHz Maximum 8.0 kHz
Important: Output Current derating applies above 4kHz. See Fig. 5-11. Important: Changing PWM carrier frequency may result in changes in Start-up and Holding current if start boost and DC Holding voltages are in effect. These parameters should be checked if the carrier frequency is changed and reprogrammed if needed.
Important: Ignoring derating guidelines can cause reduced drive performance.
% Output Current (A)
Figure 5.11 PWM Frequency Derating
100 98 96 94 92 90 88 86 84 1
2
3 5 4 Carrier Frequency, kHz
6
7
8