The text of a manual · part 10 of 21
User Manual: 1305 Adjustable Frequency AC Drive (Series C): 5 - Programming, pages 69 to 78
Pages 69 to 78 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)
The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1305-BA03A
Page 69
Programming
Chapter 5
CHAPTER OBJECTIVES
Function
Page #
Function
Page #
Chapter 5 describes the 1305 parameters which are divided into groups for ease of programming and operator access. Grouping replaces a sequentially numerical parameter list with functional parameter groups that increases operator efficiency and helps to reduce programming time. For most applications, this means simplicity at startup with minimum drive tuning.
Accel/Decel Time
5-9
Min/Max Freq.
5-10, 5-11, 5-15
Accel/Decel Selection
5-30
MOP
Analog Invert
5-21
5-6, 5-8, 5-28, 5-49, 5-53
Auto-Restart/ Run On Power Up
5-32
Output Configuration
5-37
Overload Protection
5-12
Current Limiting
5-11, 5-13
Preset Frequencies
5-25, 5-27, 5-29
Custom Volts/Hz
5-17
Process Display
5-55
DC Boost
5-17, 5-18, 5-19
PWM Freq. Derating
5-20
Ramp to Stop
5-22
DC Brake-to-Stop
5-22, 5-23
S-Curve Acceleration
5-33, 5-34
Fan/Pump Volts/Hz
5-18
Skip Frequencies
5-27, 5-28
Fault Buffer History
5-39
Standard Boost V/Hz
5-18
Frequency Select
5-25
Standard Volts/Hz
5-16
Freq. Source Select
5-29
Start/Run Boost
5-19
Line Loss Fault
5-40, 5-41
CHAPTER CONVENTIONS 1. All parameters required for any given drive function will be contained within a group, eliminating the need to change groups to complete a function. 2. To help differentiate parameter names and display text from other text in this manual, the following conventions will be used – Parameter Names will appear in [Brackets] – Display Text will appear in “Quotes.” 3. Parameter information in this chapter is presented for users who have a Human Interface Module (HIM) installed. For those users without a HIM installed, the drive can be operated using the factory default values for each parameter or parameter values can be changed through the serial port.
FUNCTION INDEX The Function Index shown provides a directory of various drive functions. The Page Number will direct you to the parameters associated with each function.
PARAMETER FLOW CHART The chart provided on pages 5-2 and 5-3 highlights each group of parameters and lists all parameters for each of the 13 groups. Parameters that appear in more than one group are shown in bold. Parameter numbers are shown in parenthesis immediately after the parameter name. An example of how to program a parameter is shown on page 5-4.
Page 70
Programming
5-2
Wrap to Linear List
Metering
Setup
Advanced Setup
Frequency Set
Feature Select
Output Configuration
Faults
Page 5-5
Page 5-8
Page 5-15
Page 5-25
Page 5-32
Page 5-37
Page 5-39
Output Current (54) Output Voltage (1) Output Power (23) DC Bus Voltage (53) Output Freq (66) Freq Command (65) MOP Hz (42) Drive Temp (70) Last Fault (4) % Output Power (3) % Output Curr (2)
Input Mode (21) Freq Select 1 (5) Accel Time 1 (7) Decel Time 1 (8) Base Frequency (17) Base Voltage (18) Maximum Voltage (20) Minimum Freq (16) Maximum Freq (19) Stop Select (10) Current Limit (36) Overload Mode (37) Overload Current (38) Sec Curr Limit (141) Adaptive I Lim (149)
Minimum Freq (16) Maximum Freq (19) Base Frequency (17) Base Voltage (18) Break Frequency (49) Break Voltage (50) Maximum Voltage (20) DC Boost Select (9) Start Boost (48) Run Boost (83) PWM Frequency (45) Analog Invert (84) 4-20 mA Loss Sel (81) Stop Select (10) DC Hold Time (12) DC Hold Volts (13) DB Enable (11) Motor Type (41) Compensation (52)
Freq Select 1 (5) Freq Select 2 (6) Jog Frequency (24) Prst/2nd Accel (26) Upper Presets (72) Accel Time 2 (30) Decel Time 2 (31) Preset Freq 1 (27) Preset Freq 2 (28) Preset Freq 3 (29) Preset Freq 4 (73) Preset Freq 5 (74) Preset Freq 6 (75) Preset Freq 7 (76) Skip Freq 1 (32) Skip Freq 2 (33) Skip Freq 3 (34) Skip Freq Band (35) MOP Increment (22) Analog Filter (144)
Run On Power Up (14) Reset/Run Tries (85) Reset/Run Time (15) S Curve Enable (57) S Curve Time (56) Language (47) Cable Length (143) Rated Slip (146) Slip Comp Adder (148) IR Comp % (147)
Output 1 Config (90) Output 2 Config (91) Analog Out Sel (25) Above Freq Val (77) Above Curr Val (142)
Fault Buffer 0 (86) Fault Buffer 1 (87) Fault Buffer 2 (88) Fault Buffer 3 (89) Clear Fault (51) Cur Lim Trip En (82) Line Loss Fault (40) Flt Clear Mode (39)
Bold indicates parameters located in more than one group.
Page 71
Programming
Wrap to Metering
Diagnostics
Masks
Owners
Adapter I/O
Process Display
Linear List
Page 5-42
Page 5-47
Page 5-50
Page 5-54
Page 5-55
Page 5-56
Drive Command (58) Drive Status (59) Drive Alarm (60) Input Status (55) Freq Source (62) Freq Command (65) Drive DIrection (69) Motor Mode (43) Power Mode (44) Drive Type (61) Firmware Ver (71) Output Pulses (67) Drive Temp (70) Set Defaults (64)
Logic Mask (92) Direction Mask (94) Start Mask (95) Jog Mask (96) Reference Mask (97) Accel Mask (98) Decel Mask (99) Fault Mask (100) MOP Mask (101) Local Mask (93)
Stop Owner (102) Direction Owner (103) Start Owner (104) Jog Owner (105) Reference Owner (106) Accel Owner (107) Decel Owner (108) Fault Owner (109) MOP Owner (110) Local Owner (137)
Data In A1 (111) Data In A2 (112) Data In B1 (113) Data In B2 (114) Data In C1 (115) Data In C2 (116) Data In D1 (117) Data In D2 (118) Data Out A1 (119) Data Out A2 (120) Data Out B1 (121) Data Out B2 (122) Data Out C1 (123) Data Out C2 (124) Data Out D1 (125) Data Out D2 (126)
Process Par (127) Process Scale (128) Process Txt 1 (129) Process Txt 2 (130) Process Txt 3 (131) Process Txt 4 (132) Process Txt 5 (133) Process Txt 6 (134) Process Txt 7 (135) Process Txt 8 (136)
This group contains all parameters listed in numerical order.
5-3
Page 72
Programming
5-4
PROGRAMMING EXAMPLE The following is an example of the programming steps required to change a parameter setting. In this example, the parameter [Freq Select 1] is being programmed from its’ factory default setting of “Adapter 1” to a new setting, “Adapter 2”. DESCRIPTION
ACTION ESC
❏ 1. Press any key to go from the Status Display to the ‘‘Choose Mode” menu.
SEL
To Select Mode or
To Select a Group
To Select a Parameter within a Group or SEL
To Change a Parameter Setting or Enter a Value or
Stopped +0.00 Hz
❏ 2. Press the Up/Down keys until ‘‘Program” appears on the display. ❏ 3. Press the Enter key to go to the ‘‘Program” menu.
or
HIM DISPLAY
Choose Mode Program
Choose Group Setup
❏ 4. Press the Up/Down keys until “Setup” appears on the display. ❏ 5. Press the Enter key to go to the “Setup” menu. ❏ 6. Press the Up/Down keys until [Freq Select 1] appears on the display.
Freq Select 1 Remote Pot
❏ 7. Press the SEL key. The first character of line 2 will flash indicating the parameter setting/value can be changed. ❏ 8. Press the Up/Down keys until ‘‘Adapter 2” appears on the display. ❏ 9. Press the Enter key to program [Freq Select 1] to ‘‘Adapter 2.”
Freq Select 1 Adapter 2
Freq Select 1 Adapter 2
Page 73
Programming
Metering
[Output Current] This parameter displays the output current present at TB1, terminals T1, T2 & T3 (U, V & W).
[Output Voltage] This parameter displays the output voltage present at TB1, terminals T1, T2 & T3 (U, V & W)
[Output Power] This parameter displays the output power present at TB1, terminals T1, T2, & T3 (U, V & W).
[DC Bus Voltage] This parameter displays the DC bus voltage level.
5-5
This group of parameters consists of commonly viewed drive operating conditions such as drive output frequency, output voltage, output current and command frequency. All parameters in this group are Read Only.
Parameter # 54 Parameter Type Read Only Units 0.01 Amps
Factory Default None Minimum 0.00 Maximum Two Times Drive Output Current
Parameter # 1 Parameter Type Read Only Units 1 Volt
Factory Default None Minimum 0 Maximum Maximum Voltage
Parameter # 23 Parameter Type Read Only Units 0.01 kW
Factory Default None Minimum 0 Maximum Two Times Rated Drive Output Power
Parameter # 53 Parameter Type Read Only Units 1 Volt
Factory Default None Minimum 0 Maximum 410 - 230V Drive 815 - 460V Drive
Page 74
5-6
Programming
Metering Group (continued) [Output Freq] This parameter displays the output frequency present at TB1, terminals T1, T2 & T3 (U, V & W).
[Freq Command] This parameter displays the frequency that the drive is commanded to output. This command may come from any one of the frequency sources selected by [Freq Select 1], [Freq Select 2] or [Preset Freq 1-7] the preset speeds 1-7 as determined by the inputs to SW1, SW2, and SW3 at TB2.
[MOP Hz] This parameter displays the frequency reference commanded by the Motor Operated Potentiometer (MOP) function. This MOP frequency command can be adjusted from TB2-16 and TB2-17 if the appropriate [Input Mode] is selected. This MOP frequency command can also be changed through serial communication. This value is displayed regardless of whether or not this is the active frequency command.
Parameter # 66 Parameter Type Read Only Units 0.01 Hz
Factory Default None Minimum – [Maximum Freq] Maximum + [Maximum Freq]
Parameter # 65 Parameter Type Read Only Units 0.01 Hz
Factory Default 0.00 Hz Minimum 0.00 Hz Maximum +400.00 Hz
Parameter # 42 Parameter Type Read Only Units 0.01 Hz
Factory Default None Minimum 0.00 Hz Maximum 400.00 Hz
Page 75
Programming
Metering Group (continued) [Drive Temp] This parameter displays the drive internal temperature.
[Last Fault] This parameter displays the fault code for the present drive fault. If there is no active fault, the value will be zero.
[% Output Power] This parameter displays the percent of drive rated output power.
[% Output Curr] This parameter displays the percent of drive rated output current.
Parameter # 70 Parameter Type Read Only Units 1_C
Factory Default None Minimum 0 Maximum 100_C
Parameter # 4 Parameter Type Read Only Units Numeric
Factory Default None Minimum 0 Maximum Max. Fault Number
Parameter # 3 Parameter Type Read Only Units 1 %
Factory Default None Minimum 0 % Maximum 200% Drive Rated Power
Parameter # 2 Parameter Type Read Only Units 1 %
Factory Default None Minimum 0 % Maximum 200% of Rated Drive Output Current
5-7
Page 76
Programming
5-8
Setup
[Input Mode] This parameter selects between Three Wire and Run Fwd/Rev control. Refer to Chapter 2, Figure 2.7 through Figure 2.10.
This group of parameters defines the basic operation of the drive and should be programmed before initial operation. For advanced programming and information on specific parameters, refer to the flow chart on page 5-2 & 5-3 Parameter # 21 Parameter Type Read & Write Units Text
Important: Power must be cycled to the drive for the change to take effect. Important:See Frequency Set Group for MOP explanation.
Factory Default “Three Wire” Setting “Three Wire” “Run Fwd/Rev” “3 W/2nd Acc” (2nd Accel) “Run F/R 2nd A” (2nd Accel) “3 Wire/MOP” “Run F/R MOP” Important:This parameter cannot be programmed while the drive is running.
[Freq Select 1] This parameter is the factory default parameter for selecting the frequency source that will supply the [Freq Command] to the drive. [Freq Select 2] or [Preset Freq 1–7] can be selected in place of this parameter with proper terminal block inputs. (See Chart on Page 5-29). Important: If an adapter that is not connected is selected as the active frequency source, the drive will fault on “Hz Sel Fault” (F30).
Parameter # 5 Parameter Type Read & Write Units Text
Factory Default “Adapter 1” Settings ‘‘Remote Pot” ‘‘0-10 Volt” ‘‘4–20 mA” ‘‘MOP” ‘‘Adapter 1” ‘‘Adapter 2” ‘‘Adapter 3” ‘‘Adapter 4” ‘‘Adapter 5” ‘‘Adapter 6”
‘‘Preset 1” ‘‘Preset 2” ‘‘Preset 3” ‘‘Preset 4” ‘‘Preset 5’’ ‘‘Preset 6” ‘‘Preset 7”
Page 77
Programming
Setup Group (continued) [Accel Time 1] This parameter is the factory default parameter for determining the time it will take the drive to ramp from 0 Hz to [Maximum Frequency]. The rate is linear unless [S Curve] is ‘‘Enabled.” It applies to any increase in command frequency. The [Accel Time 2] parameter can be selected in place of this parameter. (See Chart on Page 5-30).
[Decel Time 1] This parameter is the factory default parameter for determining the time it will take the drive to ramp from [Maximum Frequency] to 0 Hz. The rate is linear unless [S Curve] is ‘‘Enabled” or [Stop Select] is set to ‘‘S-Curve.” It applies to any decrease in command frequency. The [Decel Time 2] parameter can be selected in place of this parameter. (See Chart on Page 5-30).
Figure 5.1 Accel/Decel Time
Parameter # 7 Parameter Type Read & Write Units 0.1 Second
Factory Default 10.0 Sec Minimum 0.0 Sec Maximum 3600.0 Sec
Parameter # 8 Parameter Type Read & Write Units 0.1 Second
Factory Default 10.0 Sec Minimum 0.0 Sec Maximum 3600.0 Sec
Max. Frequency '
Speed
0 a Accel ' 0 Time
Time a Decel ' Time
5-9
Page 78
5-10
Programming
Setup Group (continued) [Base Frequency] This value should be set to the motor nameplate Rated Frequency.
[Base Voltage] This value should be set to the motor nameplate Rated Voltage.
[Maximum Voltage] This parameter sets the highest voltage the drive will output.
[Minimum Freq] This parameter sets the lowest frequency the drive will output. Important: All analog inputs to the drive (4-20mA, 0-10V, Remote Pot) are scaled for the range [Minimum Freq] to [Maximum Freq].
Parameter # 17 Parameter Type Read & Write Units 1 Hz
Factory Default 60 Hz Minimum 40 Hz Maximum 400 Hz
Parameter # 18 Parameter Type Read & Write Units 1 Volt
Factory Default Max. Drive Rated Volts Minimum 25% of Max. Drive Rated Volts Maximum 100% of Max. Drive Rated Volts
Parameter # 20 Parameter Type Read & Write Units 1 Volt
Factory Default Max. Drive Rated Volts Minimum 25% of Max. Drive Rated Voltage Maximum 110% of Max. Drive Rated Volts
Parameter # 16 Parameter Type Read & Write Units 1 Hz
Factory Default 0 Hz Minimum 0 Hz Maximum 120 Hz
Important: This parameter can not be programmed while the drive is running.