User Manual: 1305 Adjustable Frequency AC Drive (Series C): 4 - Start-Up

Pages 59 to 68 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1305-BA03A

Page 59

Start-Up

Chapter 4

CHAPTER OBJECTIVES This chapter describes the steps needed to start-up the drive. Included in the procedure are typical adjustments and checks to assure proper operation. The information contained in previous chapters of this manual must be read and understood before proceeding. Important: The drive is designed so that start-up is simple and efficient. The programmable parameters are grouped logically so that most start-ups can be accomplished by adjusting parameters in only one group. Advanced features and adjustments are grouped separately. This eliminates having to step through unneeded parameters on initial start-up. This start-up procedure covers only those most commonly adjusted values, all of which appear in the Setup Group.

START-UP PROCEDURE The following start-up procedure is written for users who have a Human Interface Module (HIM) installed in the drive (Port 1). For users without a HIM, external commands and signals must be substituted. Important: The parameters in the Set Up Group (page 5-8) should be reviewed and reprogrammed as necessary for basic operation.

!

ATTENTION: Power must be applied to the drive to perform the following start-up procedure. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove Power by opening the branch circuit disconnect device and correct the malfunction before continuing.

Important: D Power must be applied to the drive when viewing or changing parameters. Previous programming may effect the drive status when power is applied. D Confirm that all circuits are in a de-energized state before applying power. User supplied voltages may exist at TB2 even when power is not applied to the drive. D Refer to Chapter 6 for fault code information.

Page 60

4-2

Start-Up

Initial Operation - Motor Disconnected ❏ 1.Verify that AC line power at the disconnect device is within the rated value of the drive. ❏ 2.Disconnect and lock-out all incoming power to the drive including incoming AC power to terminals L1, L2 and L3 (R, S and T) plus any separate control power for remote interface devices. Remove the drive cover and verify the motor leads are disconnected from the Power Terminal Block (TB1), terminals T1, T2 and T3 (U, V, W). Refer to Chapter 2 for terminal location.

!

ATTENTION: Proceed with caution. A DC bus voltage may be present at the Power Terminal Block (TB1) even when power is removed from the drive.

❏ 3.Verify that the Stop and Enable inputs are connected. ❏ 4.Confirm that all other optional inputs are connected to the correct terminals and are secure. ❏ 5.If the HIM has a Control Panel, use the local controls to complete the start-up procedure. If a Control Panel is not present, remote devices must be used to operate the drive. ❏ 6.Replace the drive cover.

ACTION

DESCRIPTION

Apply Power to Drive

❏ 7. When power is first applied to the drive, the following information will be momentarily displayed: a.) The HIM ID# (Adapter #) and firmware version number. b.) Communication status.

HIM DISPLAY

HIM ID # Version X.XX HIM ID # Connecting... HIM ID # Connected c.) Series letter of drive is displayed. d.) The LCD Display should light and display a drive status of ‘‘Stopped” and an output frequency of ‘‘+0.00 Hz.”

Bul. 1305 Drive Series X Stopped +0.00 Hz

Page 61

Start-Up

❏ 8. If the HIM and drive are not communicating properly, ‘‘Connection Fail” may be displayed on line 2. If this occurs remove the HIM from the drive and reinsert. See Page 3-4 for HIM Removal instructions. If this does not correct the problem or another fault message is displayed, record the information and remove all power. Determine and correct the fault source before proceeding. Refer to Chapter 6 for fault descriptions. Reset Factory Defaults

[Input Mode] Selection

❏ 9. Important: The remaining steps in this procedure are based on factory default parameter settings. If the drive has been previously operated, parameter settings may have been changed and may not be compatible with this start-up procedure or application. Refer to page 3-11 to reset to factory defaults. ❏ 10. The factory default [Input Mode] is “3 wire” control as described in Chapter 2. If the factory default setting is sufficient, then skip to Step 11. If another control scheme is desired, change the [Input Mode] parameter by performing the following procedure.

Bul. 1305 Drive Connection Fail

4-3

Page 62

Start-Up

4-4

❑ 10. INPUT MODE SELECTION (continued) a.) From the Status Display, press the Enter key (or any key). ‘‘Choose Mode” will be displayed. b.) Press the Increment (or Decrement) key until ‘‘Program” is displayed. c.) Press Enter. The parameter group ‘‘Metering” will be displayed. d.) Press the Increment key again until the ‘‘Set Up” Group is displayed.

Choose Mode Display Choose Mode Program Choose Group Metering Choose Group Set Up e.) Press Enter. or f.) Press the Increment or Decrement key until the [Input Mode] parameter is displayed.

Input Mode 3 Wire

SEL g.) Press SEL. The first character of line 2 will now flash.

Input Mode 3 Wire or h.) Press the Increment or Decrement key until the correct mode is displayed, then press enter. The first character of line 1 should now be flashing.

Input Mode Run Fwd/Rev

ESC i.) Press the ESC key (3 times) to return to the Status Display. Important: If the [Input Mode] is changed, power must be cycled for the change to take effect.

Stopped +0.00 Hz

Page 63

Start-Up

❏ 11. Setting Frequency Command to 0 Hz If the HIM has an analog potentiometer option, turn the potentiometer fully counter clockwise and skip to Step 12. If the HIM has Digital Up-Down keys for frequency control then perform the following:

or or or or ESC a.) From the Status Display, press the Enter key (or any key). “Choose Mode” will be displayed.

Choose Mode Program b.) Press the Increment or Decrement key until “Display” is shown.

Choose Mode Display c.) Press Enter.

Choose Group Set Up d.) Press the Increment or Decrement key again until “Metering” is displayed.

Choose Group Metering e.) Press Enter.

Output Current 0.00 Amps f.) Press the Increment or Decrement key until [Freq Command] is displayed.

Freq Command +0.00 Hz g.) If the frequency command is a value other than 0 Hz, use the speed source (digital up-down keys on Control Panel) to set the command to 0 Hz. h.) After the command has been set to 0 Hz, press the ESC key until the Status Display is shown.

Stopped +0.00 Hz

4-5

Page 64

Start-Up

4-6

❏ 12. Verifying Minimum and Maximum Frequency Settings. a.) Press the Start key. The drive should output 0 Hz. which is the factory default value for the [Minimum Freq] parameter. The Status Display should indicate “At Speed” and the actual frequency (+0.00 Hz.). or b.) With the drive still running, use the speed source to command maximum speed. The drive should ramp to 60 Hz. which is the factory default value for the [Maximum Freq] parameter.

At Speed +0.00 Hz

Accelerating +29.62 Hz At Speed +60.00 Hz

❏ 13. Enable interlock check.

Open Enable Signal Restore Enable Signal

The following steps check for correct drive operation when the Enable input is removed. Refer to Chapter 2 for terminal designations.

At Speed +60.00 Hz a.) With the drive still running, open the Enable signal. The drive should stop and indicate “Not Enabled” on the Display Panel. Restore the Enable signal.

Not Enabled +0.00 Hz b.) Restart the drive by pressing the Start key.

Accelerating +10.00 Hz c.) Stop the drive.

Stopped +0.00 Hz

Page 65

Start-Up

❏ 14. Jog Control Check. Press & Hold Jog Key JOG

Release Jog Key

Set to Maximum Frequency or a.) With the drive stopped, press and hold the JOG key on the Control Panel. The drive should accelerate to the frequency programmed by the [Jog Frequency] parameter and remain there until the JOG key is released. When released, the drive should “Ramp to Stop” which is the factory default stopping method for the [Stop Select] parameter.

At Speed +10.00 Hz Stopped +0.00 Hz

❏ 15. Checking Accel and Decel Times. a.) Start the drive and use the speed source to command maximum frequency. b.) Press the Stop key and estimate the amount of time the drive takes to decelerate from 60 Hz to 0 Hz. This time should equal the time set in the [Decel Time l] parameter (default is 10 seconds). If these times are not correct for your application, refer to Chapter 5 for instructions on programming changes. c.) Start the drive and estimate the amount of time the drive takes to accelerate to maximum frequency. This should equal l0 seconds, which is the factory default value for the [Accel Time 1] parameter. d.) Stop the drive.

Accelerating +10.00 Hz At Speed +60.00 Hz Decelerating +30.00 Hz Stopped +0.00 Hz Accelerating +10.00 Hz At Speed +60.00 Hz

4-7

Page 66

4-8

Start-Up

❏ 16. Reconnect the Motor. Remove ALL Power Reconnect Motor

!

ATTENTION: Proceed with caution. A DC Bus Voltage may be present at the Power Terminal Block (TB1) even when power is removed from the drive.

a.) Disconnect and lock-out all input and control power to the drive. When the HIM Display is no longer illuminated, remove the drive cover. b.) Verify that the DC Bus neon indicator is not illuminated (See Figure 2.3 for location) and wait 60 seconds. Reconnect the motor leads to the drive and replace the drive cover. Important: The parameters in the Set Up Group (page 5-8) should be reviewed and reprogrammed as necessary for basic operation.

!

ATTENTION: In the following steps, rotation of the motor in an un-desired direction can occur. To guard against possible equipment damage, it is recommended that the motor be disconnected from the load before proceeding.

Page 67

Start-Up Apply Power to Drive Verify Frequency Command = 0

❏ 17. Check for Correct Motor Rotation. a.) Reapply power to the drive.

At At Speed Speed +5.00 +5.00 Hz Hz b.) Verify that the frequency command is at zero Hz. Refer to step 11 for further information. c.) Start the drive.

Slowly Increase Speed or d.) Slowly increase the speed until the motor begins to turn. Check the direction of motor rotation.

Verify Direction of Rotation e.) Stop the drive. If the direction of rotation is as desired, proceed to step 18. If the direction of rotation is incorrect - disconnect and lock-out all input and control power to the drive. When the HIM Display is no longer illuminated, remove the drive cover. Verify that the DC Bus neon indicator is not illuminated (see Figure 2.3 for location) and wait 60 seconds. Interchange any two of the three motor leads at TB1 terminals, T1, T2 or T3. Replace the drive cover and repeat steps a – e to verify correct motor rotation.

Stopped Stopped +0.00 Hz 0.00 Hz

4-9

Page 68

Start-Up

4-10

❏ 18. Check for proper operation. a.) Start the drive.

At Speed +5.00 Hz

Slowly Increase Speed or b.) Slowly increase the speed. Check for proper motor operation throughout the speed range.

c.) Press the Stop key. ❏ 19. This completes the basic start-up procedure. Depending on your application, further parameter programming may be required. Refer to Chapter 5 for information. Important: The parameters in the Set Up Group (page 5-8) should be reviewed and reprogrammed as necessary for basic operation.

At Speed +60.00 Hz

Stopped +0.00 Hz