Page 31

Installation/Wiring

DRIVE OPERATION WITHOUT A HUMAN INTERFACE MODULE (HIM) Bulletin 1305 drives are functional without the use of the Human Interface Module (HIM). All control functions can be performed from the control terminal block (TB2). See Table 2.F for control descriptions. Programming must be performed using a HIM or PLC Remote I/O function. If operating without a HIM, you must use an external Frequency Source on TB2. Frequency Source To control frequency from the control terminal block (TB2) an input is required to SW3 at TB2. The input to SW3 changes the frequency source from [Freq Select 1] to [Freq Select 2]. The factory default setting for [Freq Select 2] is the “Remote Pot”. If a 0 – 10 Volt or 4 – 20mA frequency source is required, then the [Freq Select 1] or [Freq Select 2] parameters must be programmed to select that source. These parameters can be programmed using the optional Human Interface Module or through serial communications when using an optional Bulletin 1203 Communication Module. See Appendix C for catalog numbers of these accessories. Refer to Chapter 5 for the factory default settings for all parameters. Special attention should be paid to Table 5.A on page 5-29 and Table 5.B on page 5-30. These tables demonstrate what frequency source and accel and decel parameters can be selected based on the inputs to SW1, SW2 and SW3 at TB2.

2-17

CONTROL WIRING Important: All common terminals are tied together within the drive and internally connected to chassis ground. Recommended practice is to run all signal wiring in separate steel conduit.

!

ATTENTION: Drive can be permanently damaged if any EXTERNAL control voltage is applied to terminals 5 – 8 and 11 – 18. DO NOT connect drive Common terminals (TB2) to ground. DO NOT switch these inputs using non-isolated TTL type circuits. Use dry relay contacts to switch signal inputs to Common. Only isolated 4-20mA sources are recommended. There must be no ground potential difference between source and drive.

The factory default control wire scheme is ‘‘3 Wire” control. The [Input Mode] parameter can be used to program the drive to operate using a two wire ‘‘Run Forward/Run Reverse” control wire scheme. Refer to Chapter 4, Step 10 for programming instructions. Figures 2.7 through 2.10 show the wiring diagrams for the different input modes. Important: If the [Input Mode] is changed, power must be cycled to the drive for the change to take effect. The Start and Reverse functions operate differently for the two different modes.

Page 32

2-18

Installation/Wiring

Three Wire Control

MOP Function

When using this control scheme, the factory default for the reverse function is controlled from TB2. To enable Reverse operation from the HIM or other serial communication adapters, Bit 0 of the [Direction Mask] parameter must be changed from “1” to a “0”. See page 5-47. See Chapter 5 for general programming instructions.

The MOP function is a digital solid-state circuit that produces the same effect as rotating a speed reference potentiometer with a small DC motor. This permits local (HIM) or remote (TB2) control of the command frequency.

Two Wire “Run Forward/Run Reverse” Control To use a two wire ‘‘Run Forward/Run Reverse” control scheme, Bit 0 of the [Direction Mask] must be set to a ‘‘1.” For proper operation of the “Run Forward/Run Reverse” mode, install a jumper across terminals 7 and 8 (Stop) and terminals 11 and 12 (Enable). 3W/2nd Acc and Run F/R 2nd A Control The HIM module is limited in the number of characters in the LCD display. Definitions of these functions are as follows. Refer to Chapter 5, Table 5.A for configuration of switches or inputs to TB2. 3w/2nd Acc = Three Wire, 2nd Acceleration Run F/R 2nd A = Run Forward/Reverse, 2nd Acceleration

Important: The drive can still be started from any adapter (HIM or a serial device) and will run at the last commanded direction unless the start, jog and reverse functions of that adapter have been disabled (See [Start Mask], [Direction Mask] and [Jog Mask]. See page 5-47 and 5-48. Important: A stop command can be issued from any adapter at all times. Important: If a Jog is initiated, the drive will Jog in the direction last traveled.

Page 33

Installation/Wiring

Figure 2.8 TB2 Designations – Two Wire Control Operation [Input Mode]=“Run Fwd/Rev” or [Input Mode]=“Run F/R 2nd A”

Figure 2.7 TB2 Designations [Input Mode] = “Three Wire” or [Input Mode]=“3 w/2nd Acc.”

Remote Pot

Remote Pot

➄ ➀

1

Source

1

Source

2

Wiper or 0-10V DC Input

2

Wiper or 0-10V DC Input

3

Common

3

Common

4

4-20mA Input

4

4-20mA Input

5

0-10V Output

5

0-10V Output

6

Start ➂

6

Start ➂

7

Common

7

Common

8

Stop ➂

8

Stop ➂

User Side

9

24VDC Source (User Supplied)

Momentary Input Maintained Input Wires must be shielded

11

Enable ➂

12

Common

13

Reverse ➂

14

Jog ➂

15

Common

16

SW1 ➂

17

SW2 ➂

18

SW3 ➂

19 20

Run Forward Jumper ➀➁

Output #1

10

➀➃

0-10V

User Side

0-10V

2-19

Jumper ➀➃ Run Reverse

9

Output #1

10 11

Enable ➂

12

Common

13

Reverse ➂

14 Jog ➂

(Sink) Output #2

Shield

15

Common

(connect to drive at TB2 Only)

See Table 2.F and Notes on page 2-21

24VDC Source (User Supplied)

Common

16

SW1 ➂

17

SW2 ➂

18

SW3 ➂

19 20

(Sink) Output #2

Page 34

Installation/Wiring

2-20

Figure 2.9 TB2 Designations [Input Mode] = “3 Wire/MOP”

Figure 2.10 TB2 Designations – Two Wire Control Operation [Input Mode] = “Run F/R MOP” Remote Pot

Remote Pot

➄ ➀

Source

1

Source

2

Wiper or 0-10V DC Input

2

Wiper or 0-10V DC Input

3

Common

3

Common

4

4-20mA Input

4

4-20mA Input

5

0-10V Output

5

0-10V Output

6

Start ➂

6

Start ➂

7

Common

7

Common

8

Stop ➂

8

Stop ➂

User Side

9

Momentary Input Maintained Input Wires must be shielded

11

Enable ➂

12

Common

13

Reverse ➂

Run Forward Jumper ➀➁

Output #1

10

➀➃

0-10V

User Side

0-10V

1

Jumper ➀➃ Run Reverse

11

Enable ➂

12

Common

13

Reverse ➂

15

Common

16

MOP Increment ➂➅

17

MOP Decrement ➂➅

Frequency Source ➂➅

18

Frequency Source ➂➅

(Sink) Output #2

19

(Sink) Output #2

15

Common

16

MOP Increment ➂➅

17

MOP Decrement ➂➅

18 19 20

Output #1

14 Jog ➂

14 Jog ➂

24VDC Source (User Supplied)

9 10

Shield

Common

(connect to drive at TB2 Only)

See Table 2.F and Notes on page 2-21

24VDC Source (User Supplied)

20

Page 35

Installation/Wiring

2-21

Figure Notes:

Table 2.F Control Terminal Block (TB2) Descriptions

➀ Required to operate drive. STOP also used to clear a fault. ➁ Use HIM Stop button to clear faults. ➂ Contact Closure Input. Internal 5V supply. DO NOT apply external voltage. ➃ When the ENABLE signal is lost, the drive output immediately shuts off and the motor will coast to a stop. ➄ A Start command will override any Jog command. ➅ See Table 5.C on Page 5-31 for more information.

Terminal

Signal

Specification

1, 2, 3 2,3 4,3 5, 3 6, 7 8, 7 9, 10

External Speed Pot 0-10V Analog Input 4-20mA Analog Input 0-10V Analog Output Start Stop Programmable Output 1

11, 12 13, 12 14, 15 16, 15 17, 15 18, 15 19, 20

Drive Enable Reverse Jog SW1 SW2 SW3 Programmable Output 2

10 kΩ Potentiometer, 2 Watts Drive Input Impedance = 100 kΩ Drive Input Impedance = 250 Ω Meter Impedance ≥ 4 kΩ Contact Closure Input ➂ Contact Closure Input ➂ Resistive Rating = 115 V AC/30 VDC, 5A Inductive Rating = 115 V AC/30 VDC, 2A Contact Closure Input ➂➃ Contact Closure Input ➂ Contact Closure Input ➂ Contact Closure Input ➂ Contact Closure Input ➂ Contact Closure Input ➂ 24V DC "20%, 50 mA Max. (Sink)

The recommended control signal wire is: D Belden 8760 (or equiv.) - 18 AWG (0.750 mm2), twisted pair, shielded. D Belden 8770 (or equiv.) - 18 AWG (0.750 mm2), 3 conductor, shielded. D

Belden 9460 (or equiv.) - 18 AWG (0.750 mm2), twisted pair, shielded.

Important: Control inputs to two or more drives must NOT be connected in parallel.

Recommended practice is to run all signal wiring in a separate steel conduit. The shield wire must only be connected at the drive.

!

ATTENTION: Signal common is internally connected to chassis ground. Do not use cable shields as signal current paths.

Page 36

2-22

Installation/Wiring

OUTPUT DEVICES Drive Output Disconnection

!

ATTENTION: Any disconnecting means wired to drive output terminals U, V and W must be capable of disabling the drive if opened during drive operation. If opened during drive operation, the drive will continue to produce output voltage between U, V, W. An auxiliary contact must be used to simultaneously disable the drive or output component damage may occur.

CABLE TERMINATION Optional Cable Terminator Voltage doubling at motor terminals, known as reflected wave phenomenon, standing wave or transmission line effect, can occur when using drives with long motor cables. Inverter duty motors with phase-to-phase insulation ratings of 1600 volts or higher should be used to minimize effects of reflected wave on motor insulation life. Applications with non-inverter duty motors or any motor with exceptionally long leads may require an output inductor or cable terminator. An inductor or terminator will help limit reflection to the motor, to levels which are less than the motor insulation value.

Table 2.D lists the maximum recommended cable length for unterminated cables, since the voltage doubling phenomenon occurs at different lengths for different drive ratings. If your installation requires longer motor cable lengths, a reactor or cable terminator is recommended. Optional Output Reactor The reactors listed in Catalog A111 can be used for the drive input and output. These reactors are specifically constructed to accommodate IGBT inverter applications with switching frequencies up to 20 kHz. They have a UL approved dielectric strength of 4000 volts, opposed to a normal rating of 2500 volts. The first two and last two turns of each coil are triple insulated to guard against insulation breakdown resulting from high dv/dt. When using output line reactors, it is recommended that the drive PWM frequency be set to its lowest value to minimize losses in the reactors. See Table 2.E. Important: By using an output reactor the effective motor voltage will be lower because of the voltage drop across the reactor – this may also mean a reduction of the motor torque. Output Contactor For application of an output contactor to a 1305 drive, please contact Allen-Bradley.

Page 37

Installation/Wiring

ADAPTERS An adapter is any device connected to the drive’s serial port. Typical devices include: D Human Interface Modules D Communication Modules D Future adapter devices Important: A maximum of five adapters can communicate to the drive. The total current draw of all adapters should not exceed 250mA. Refer to the data sheet or nameplate of each adapter for the amount of current needed for the adapter to operate. The Adapter address is determined as follows: D Port 1 equals Adapter 1. D Port 2 equals Adapter 2. However, if a splitter is used to expand the number of Adapters to 3, 4 or 5 the splitter will be marked with the appropriate Adapter numbers.

Adapter Mounting Distance The maximum mounting distance between any two adapters connected to the drive is 10 meters. Refer to Figure 2.11.

2-23

Page 38

2-24

Installation/Wiring

Figure 2.11 Adapter Mounting Distance and Cable Connections Pull back connector to disconnect cable from the adapter device or Port 2 connection.

Maximum Distance A + B + C ≤ 10 Meters (33 feet) A + B + D ≤ 10 Meters (33 feet) C + D ≤ 10 Meters (33 feet)

Maximum Distance A + B ≤ 10 Meters (33 feet)

Refer to Appendix C for Cable recommendations.

Port 2 Port 1

Port 2 Port 1

Male-Female Cable

Male-Male Cable

A

A

B

B Male-Female Cable ESC

ESC

HIM or Other Remote Device

SEL

ESC

JOG

SEL

C

Male-Male Cables

D

JOG

Adapter 2 Adapter 1

Port Expansion Option

SEL

JOG

Male-Male Cable

Adapter 1

Adapter 2 Communication Module

Adapter 3 Communication Module