Page 23

Installation/Wiring

GROUNDING Refer to the grounding diagram on the following page. The drive must be connected to system ground at the power ground (GRD) terminal provided on the power terminal block (TB1). Ground impedance must conform to the requirements of national and local industrial safety regulations (NEC, VDE 0160, BSI, etc.) and should be inspected and tested at appropriate and regular intervals. In any cabinet, a single, low–impedance ground point or ground bus bar should be used. All circuits should be grounded independently and directly. The AC supply ground conductor should also be connected directly to this ground point or bus bar. Sensitive Currents It is essential to define the paths through which the high frequency ground currents flow. This will assure that sensitive circuits do not share a path with such current, and to minimize the area enclosed by these paths. Current carrying ground conductors must be separated. Control and signal ground conductors should not run near or parallel to a power ground conductor. Motor Cable The ground conductor of the motor cable (drive end) must be connected directly to the ground terminal, not to the enclosure bus bar. Grounding directly to the drive (and filter, if installed) provides a direct route for high frequency current returning from the motor frame and ground conductor. At the motor end,

2-9 the ground conductor should also be connected to the motor case ground. If shielded or armored cables are used, the same grounding methods should be used for the shield/armor as well. Discrete Control and Signal Wiring DO NOT connect drive Common terminals (TB2) to ground. DO NOT switch these inputs using non-isolated TTL type circuits. Use dry relay contacts to switch signal inputs to Common. Only isolated 4-20mA sources are recommended. There must be no ground potential difference between source and drive. Safety Ground This is the safety ground required by code. The ground bus can be connected to adjacent building steel (girder, joist) or a floor ground loop, provided grounding points comply with NEC regulations. RFI Filter Important: Using an optional RFI filter may result in relatively high ground leakage currents. The filter must be permanently installed and solidly grounded. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. The integrity of this connection should be periodically checked.

Page 24

2-10

Installation/Wiring

Figure 2.5 Recommended 1305 Grounding for Installation Without EMI Filter (Non–CE) Common Mode Core*

Conduit/4-Wire Cable R(L1)

S(L2)

Shield* U(T1) V(T2) W(T3) GRD

T(L3) GRD

Shield Motor Terminator*

Ground Rod

Standard unit has plastic conduit entry. For installation with EMI filter (CE), see Appendix D.

Motor Frame

* These are options that can be installed as needed.

Ground Per Local Codes

Page 25

Installation/Wiring

2-11

POWER WIRING

Table 2.B Power Block Terminal (TB1)

Input and output power connections are performed through a ten position terminal block, TB1 (see page 2-3 for location).

Terminals

Description

GRD

Earth Ground

Figure 2.6 Power Terminal Block Designations (TB1)

R, S, T (L1, L2, L3)

AC Input Line Terminals

+DC, BRK (or –DC)

Dynamic Brake Option - Refer to instructions included with option

U, V, W (T1, T2, T3)

Motor Connection

GRD

GRD

L1 R

L2 S

L3 T

BRK ➀ (–DC)

T1 U

T2 V

T3 W

Dynamic Brake Option

To Motor ➃ Required Input Fusing

+DC

To Motor ➂ Required Branch Circuit Disconnect AC Input Line ➁

➀ Connection for Dynamic Brake Resistors for all models except the 200-230 Volt, 0.37 to 0.75 kW (0.5 to 1 HP) drive. Important: The [DB Enable] parameter must be enabled for proper operation. ➁ For single phase applications, the AC input line can be connected to any two of the three input terminals R, S, T (L1, L2, L3). ➂ 1305 drives are UL and cUL listed, and CSA certified as a motor overload protective device. An external overload relay is not required for single motor applications. Important: This drive is not intended for use with single phase motors. ➃ Ground from drive to motor frame must be an independent continuous insulated wire run.

Table 2.C Screw Size, Wire Size and Torque Specifications Terminal

Screw Size

Max./Min. Wire Size mm 2 (AWG )

Maximum Torque N-m ( lb-ins. )

TB1 (0.37-0.75 kW/0.5-1 HP)

M4

3.5/0.75 (12/18)

0.90 (8)

TB1 (All except above)

M4

4/0.75 (10/18)

1.81 (16)

TB2 (All)

M3.5

1.5/0.20 (14/24)

0.90 (8)

Page 26

2-12

Installation/Wiring

Motor Cables A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 1 meter (3.3 feet) for every 10 meters (33 feet) of length. In all cases, long parallel runs must be avoided. The cable should be 4-conductor with the ground lead being connected directly to the drive ground terminal (GRD) and the motor frame ground terminal. Shielded Cable Shielded cable is recommended if sensitive circuits or devices are connected or mounted to the machinery driven by the motor. The shield must be connected to the drive ground and motor frame ground. The connection must be made at both ends to minimize the external magnetic field. If cable trays or large conduits are to be used to distribute the motor leads for multiple drives, shielded cable is recommended to reduce or capture the noise from the motor leads and minimize “cross coupling” of noise between leads of different drives. The shield should be connected to the ground connections at both the motor and drive end.

Armored cable also provides effective shielding. Ideally, it should be grounded only at the drive (GRD) and motor frame. Some armored cable has a PVC coating over the armor to prevent incidental contact with grounded structure. If, due to the type of connector, the armor must be grounded at the cabinet entrance, shielded cable should be used within the cabinet to continue as far as possible to the coaxial arrangement of power cable and ground. In some hazardous environments it is not permissible to ground both ends of the cable armor. This is because of the possibility of high current circulating at the input frequency if the ground loop is cut by a strong magnetic field. This only applies in the proximity of powerful electrical machines. In such case, the ground connection at one end may be made through a capacitance, which will block the frequency current but present a low impedance to RF. Because of the highly pulsed nature of the circulating current, the capacitor type used must be rated for AC-to-ground voltage. Consult factory for specific guidelines.

Page 27

Installation/Wiring

2-13

Conduit

Motor Lead Lengths

If metal conduit is preferred for cable distribution, the following guidelines must be followed.

Installations with long cable lengths between the 1305 drive and motor may require the use of an output reactor or Terminator. The following guidelines allow for selection of the appropriate drive HP rating (and output reactor or Terminator, if required) to work with an existing motor, and provide motor-lead length solutions for new installations.

1. Drives are normally mounted in cabinets and ground connections are made at a common ground point in the cabinet. If the conduit is connected to the motor junction box and at the drive end, no further conduit connections are necessary. 2. No more than three sets of motor leads can be routed through a single conduit. This will minimize “cross talk” that could reduce the effectiveness of the noise reduction methods described. If more than three drive/motor connections per conduit are required, shielded cable as described above must be used. If practical, each conduit should contain only one set of motor leads.

!

ATTENTION: To avoid a possible shock hazard caused by induced voltages, unused wires in the conduit must be grounded at both ends. For the same reason, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will eliminate the possible shock hazard from “cross coupled” drive motor leads.

Voltage doubling at motor terminals, known as reflected wave phenomenon, standing wave or transmission line effect, can occur when using long motor cables with drives. Long motor cables can cause capacitive charging current in excess of the rating of a smaller drive. To ensure proper installation, follow the guidelines provided. All cabling and distances are based on using 14 AWG, 4-conductor type cabling. In general, motors designed and built without phase separating insulation paper between motor windings should be classified as 1000VP-P insulation design. Section A: No Output Reactor or Terminator Table 2.D lists the maximum cable lengths permitted when applying a 460V, 1305 drive to a 460V motor for motor insulation ratings of 1000V, 1200V, and 1600V without an output reactor or Terminator. Shielded and unshielded maximum cable lengths also are listed. Tables are based on operation at nominal line condition (480V).

Page 28

2-14

Installation/Wiring

1000V and 1200V Motor Insulation Ratings: Cable lengths listed in Table 2.D are for operating the 1305 drive at a maximum carrier frequency of 4 kHz on motor insulation ratings of 1000V and 1200V. Consult the factory regarding operation above 4 kHz carrier frequency. Multiply listed distances by 0.85 for operation at high line conditions (above 480V). If the maximum cable length used exceeds the distances indicated, refer to Section B. 1600V Motor Insulation Ratings: Cable lengths listed in Table 2.D are based on operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor insulation ratings of 1600V. Consult the factory regarding operation above 2 kHz carrier frequency. Multiply listed distances by 0.55 for operation at high line conditions (above 480V). If the maximum cable length used exceeds the distances indicated, refer to Section B. The Allen-Bradley 1329-HR is representative of 1600VP-P insulation rating designs and is recommended in applications where long cable lengths are required.

Table 2.D Maximum Motor Cable Length Restrictions No External Devices or Reactor at the Motor Using a Motor with Insulation VP-P Drive Motor HP HP (460V) (460V) Maximum Carrier Frequency High-Line Derate Multiplier 5 5

3

2

1 0.5

1000 Volt

1200 Volt

1600 Volt 1329 HR

Any Cable

Any Cable

Shielded Cable Unshielded Cable

4 kHz

4 kHz

2 kHz

2 kHz

0.85

0.85

0.55

0.55

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

3

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

2

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

3

9m (30ft)

30m (100ft)

91m (300ft)

121m (400ft)

2

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

1

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

2

9m (30ft)

30m (100ft)

76m (250ft)

121m (400ft)

1

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

0.5

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

1

9m (30ft)

30m (100ft)

68m (225ft)

121m (400ft)

0.5

9m (30ft)

30m (100ft)

121m (400ft)

121m (400ft)

0.5

9m (30ft)

30m (100ft)

45m (150ft)

106m (350ft)

Page 29

Installation/Wiring

Section B: Use of Output Reactor or Terminator For longer motor-lead length applications, an output reactor or Terminator is required to ensure proper drive operation, and for the motor to operate within its specified insulation rating. The guidelines in Table 2.E are required for proper drive and motor operation, or motor designs without phase-separating insulation paper between motor windings. Applications with non-inverter duty rated motors, with long lead lengths, require an output reactor or Terminator. An output reactor or Terminator helps reduce voltage reflection to the motor to levels which are less than the motor insulation rating. Table 2.E lists maximum cable lengths that can be run when using an output reactor, or one of two available Terminators, for motor insulation ratings of 1000V, 1200V, and 1600V. Shielded and unshielded maximum cable lengths also are listed. When an output reactor is required, locate the reactor at the drive if possible. Consult the factory for applications which require mounting the reactor at the motor. 1000V and 1200V Motor Insulation Ratings: Cable lengths listed in Table 2.E are for operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor insulation ratings of 1000V and 1200V when used with an output reactor or Terminator. Consult the factory regarding operation above 2 kHz carrier frequency. Multiply listed distances by 0.85 for operation at high line conditions (above 480V).

2-15

1600V Motor Insulation Ratings: Cable lengths listed in Table 2.E are based on operating the 1305 drive at a maximum carrier frequency of 2 kHz on motor insulation ratings of 1600V. Consult the factory regarding operation above 2 kHz carrier frequency. The Allen-Bradley 1329-HR is representative of 1600VP-P insulation rating designs and is recommended in applications where long cable lengths are required. Example: An existing installation includes a 2 HP, 1200V motor with a 84-meter (275-foot) cable-length requirement between the 1305 drive and the motor. What are the possible solutions to this installation? 1. Table 2.D indicates that either an output reactor or a Terminator is required for this installation example. Consult Table 2.E for output reactor, Terminator, and cable types. 2. Table 2.E suggests these possible solutions: – Install a 1305 2-HP drive with an output reactor installed at the drive, and use unshielded cable.

– Install a 1305 3-HP drive with an output reactor installed at the drive, and use shielded or unshielded cable.

– Install a 1305 2-HP drive with a 1204-TFA1 Terminator, and use shielded or unshielded cable.

Contact Allen-Bradley for further assistance if required.

Page 30

Installation/Wiring

2-16

Table 2.E Maximum Motor Cable Length Reactor➀ at the Drive

With 1204-TFB2 Terminator

With 1204-TFA1 Terminator

Using a Motor with Insulation VP-P 1200 Volt or 1600 Volt

Using a Motor with Insulation VP-P 1000 Volt or 1200 Volt

Using a Motor with Insulation VP-P

1000 Volt Any Cable

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Maximum Carrier Frequency

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

High-Line Derating Multiplier

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

5

5

15m (50ft)

182m (600ft)

182m (600ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

3

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

2

15m (50ft)

182m (600ft)

182m (600ft)

121m (400ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

3

15m (50ft)

91m (300ft)

182m (600ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

2

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

1

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

182m (600ft)

99m (325ft)

61m (200ft)

182m (600ft)

121m (400ft)

2

15m (50ft)

76m (250ft)

167m (550ft)

NR

NR

91m (300ft)

61m (200ft)

91m (300ft)

121m (400ft)

1

15m (50ft)

182m (600ft)

182m (600ft)

61m (200ft)

61m (200ft)

99m (325ft)

61m (200ft)

121m (400ft)

121m (400ft)

0.5

15m (50ft)

182m (600ft)

182m (600ft)

91m (300ft)

121m (400ft)

99m (325ft)

61m (200ft)

152m (500ft)

121m (400ft)

1

15m (50ft)

68m (225ft)

152m (500ft)

NR

NR

45m (150ft)

61m (200ft)

45m (150ft)

76m (250ft)

0.5

15m (50ft)

121m (400ft)

182m (600ft)

NR

NR

76m (250ft)

61m (200ft)

76m (250ft)

121m (400ft)

0.5

15m (50ft)

45m (150ft)

106m (350ft)

NR

NR

NR

NR

NR

NR

Drive HP (460V)

3

2

1 0.5

Motor HP (460V)

1000 Volt

1200 Volt

NR = Not Recommended. ➀ Important: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100 volts or higher. Reactors are not recommended for lightly loaded applications because overvoltage trips may result at low output frequencies.