The text of a manual · part 4 of 21

User Manual: 1305 Adjustable Frequency AC Drive (Series C): 2 - Installation/Wiring, pages 15 to 22

Pages 15 to 22 of 170, from User Manual: 1305 Adjustable Frequency AC Drive (Series C)

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1305-BA03A

Page 15

Installation/Wiring Figure 2.1 Mounting Requirements

Chapter 2 provides the information needed to properly mount and wire the drive. Since most start-up difficulties are the result of incorrect wiring, every precaution must be taken to assure that the wiring is done as instructed. All items must be read and understood before the actual installation begins.

SEL ESC

!

ATTENTION: The following information is merely a guide for proper installation. The National Electrical Code and any other governing regional or local code will overrule this information. The Allen-Bradley Company cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

50.8 mm (2.0 in.)

JOG

CHAPTER OBJECTIVES

Chapter 2

76.2 mm (3.0 in.) ESC

SEL

JOG

50.8 mm (2.0 in.)

Important: The drive must be mounted to a metallic surface.

Page 16

Installation/Wiring

2-2

Figure 2.2 Bulletin 1305 Approximate Dimensions Dimensions shown are in millimeters (inches). Shipping weights are in kilograms (pounds). C’ C

A

O 5.5 (7/32)

H D J O 22.5 (7/8)

B

E

G 200/230 V Cat. No. 1305- . . .

380/460 V Cat. No. 1305- . . .

F

A Width

B Height

C Depth w/o Pot.

C’ Depth w/ Pot.

D

E

F

G

H

J

Approx. Shipping Weight

AA02A AA03A

120 (4-23/32)

195 (7-11/16)

122 (4-13/16)

127.1 (5)

110 (4-11/32)

180 (7-1/16)

9 (11/32)

113 (4-7/16)

5 (7/32)

7.5 (5/16)

1.6 (3.5)

AA04A

120 (4-23/32)

195 (7-11/16)

140 (5-1/2)

145.1 (5-23/32)

110 (4-11/32)

180 (7-1/16)

27 (1-1/16)

113 (4-7/16)

5 (7/32)

7.5 (5/16)

1.9 (4.2)

AA08A

BA01A BA02A BA03A BA04A BA06A

170 (6-11/16)

195 (7-11/16)

179 (7-1/16)

184.1 (7-1/4)

160 (6-5/16)

180 (7-1/16)

66 (2-19/32)

113 (4-7/16)

5 (7/32)

7.5 (5/16)

3.6 (8.0)

AA12A

BA09A

210 (8-1/4)

195 (7-11/16)

179 (7-1/16)

184.1 (7-1/4)

200 (7-7/8)

180 (7-1/16)

66 (2-19/32)

113 (4-7/16)

5 (7/32)

7.5 (5/16)

4.2 (9.2)

Page 17

Installation/Wiring Figure 2.3 Terminal Block Access

TERMINAL BLOCK ACCESS To access the power and control terminal blocks, perform the following procedure:

LED Fault Indicator

1. Remove power from the drive.

3. For drives equipped with a blank front panel, slide the panel downward and remove it from the drive. Skip to Step 5.

5. Remove the drive front cover by grasping the upper corners of the cover and pulling at a 90-degree angle to the drive. Lift the cover off.

Drive with HIM Removed

TB2 Control Terminal Block

2. Lower the hinged panel located below the HIM or blank front panel.

4. For drives equipped with a HIM, press the retaining lever directly beneath the HIM and slide the HIM downward to remove it from drive.

2-3

ES

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

Serial Number

C SE

Firmware Revision Level

L

JO

G

HIM – See back for Series Letter and Firmware Revision Level Hinged Cover

!

DC Bus Charge Indicator

Retaining Lever

ATTENTION: Proceed with caution. A DC Bus Voltage may be present at the Power Terminal Block (TB1) even when power is removed from the drive.

TB1 Power Terminal Block

Page 18

2-4

Installation/Wiring

Figure 2.4 Installation Guidelines GRD

Input Devices

Input Power Conditioning

Input Filters

Input Fusing

Page 2-5

GRD R S T GRD (L1) (L2) (L3)

Page 2-6

Page 2-8

Page 2-6

GRD (T1) (T2) (T3) GRD U V W

Electrical Interference

Page 2-7

Grounding

Page 2-9

Power Wiring

Page 2-11

Control Wiring

Page 2-17

Output Filters

Page 2-8

Output Devices

Page 2-22

Cable Termination

Page 2-22

Motor

Page 19

Installation/Wiring

INPUT DEVICES Starting and Stopping the Motor ATTENTION: The drive start/stop control circuitry

!

includes solid-state components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop circuit is required to remove AC line power to the drive. When AC input power is removed, there will be a loss of inherent regenerative braking effect and the motor will coast to a stop. An auxiliary braking method may be required.

Repeated Application/Removal of Input Power ATTENTION: The drive is intended to be controlled

!

by control input signals that will start and stop the motor. A device that routinely disconnects then reapplies line power to the drive (input contactor, etc.) for the purpose of starting and stopping the motor should not be used. If it is necessary to use this method for starting and stopping or if frequent cycling of power is unavoidable, make sure that it does not occur more than once a minute.

Input Contactor ATTENTION: An incorrectly applied or installed

!

system can result in component damage or reduction in product life. Follow these recommendations for application of an input contactor to a 1305 drive.

2-5

Normal Operation: After the input contactor is closed, the enable, start, and stop signals may be applied. These control signals must be removed before opening the input contactor. The input contactor must not be opened and closed more than once a minute. Bypass Contactors

!

ATTENTION: An incorrectly applied or installed system can result in component damage or reduction in product life. The most common causes are: D Wiring AC line to drive output or control terminals. D Improper voltage placed on control terminals. D Improper bypass or output circuits not approved by Allen-Bradley.

D Output circuits which do not connect directly to the motor.

D Incorrect or inadequate AC supply. D Excessive ambient temperature. Contact Allen-Bradley for assistance with application or wiring.

Page 20

2-6

Installation/Wiring

INPUT POWER CONDITIONING The drive is suitable for direct connection to a correct voltage, single phase or three-phase, AC power line. However, there are certain power line conditions which may introduce the possibility of drive input power component malfunction. To reduce the possibility of these malfunctions, a line reactor or isolation type transformer with an input impedance of 3% of the drive input VA rating may be required. The basic rules for determining if a line reactor or isolation type transformer is required are as follows: 1. If the AC line supplying the drive has power factor correction capacitors that are switched in and out, installing an AC line reactor or isolation type transformer between the capacitor bank and the drive input may be required. Damage to drives can occur from the extreme current spikes caused by capacitor switching. 2. If the AC line frequently experiences transient power interruptions or significant voltage spikes, an AC line reactor or isolation type transformer may be required. Damage to drives can occur from extreme current spikes.

INPUT FUSING

!

ATTENTION: The drive does not provide branch circuit protection. Specifications for the recommended fuse size and type which provide branch circuit protection against short circuits are provided in Table 2.A. Branch circuit breakers or disconnect switches cannot provide this level of protection for drive components.

Table 2.A Maximum Recommended AC Input Line Fuse UL Class J, T, CC, or BS88 (or equivalent) Three-Phase Rating – kW (HP)

Single-Phase Rating – kW (HP)

Fuse 200-230V Rating

Fuse 380-460V Rating

0.37 (0.25)

0.19 (0.25)

6A

3A ➀

0.55 (0.75)

0.37 (0.5)

6A

3A ➀

0.75 (1)

0.55 (0.75)

10A

6A ➁

1.5 (2)

0.75 (1)

15A

10A ➁

2.2 (3)

1.5 (2)

25A

15A ➁

4.0 (5) –– –– 20A ➁ ➀ Must be dual element time delay, Bussmann LPJ or equivalent. ➁ If fuse blowing is a problem, use dual element type fuses.

Page 21

Installation/Wiring

ELECTRICAL INTERFERENCE – EMI/RFI Immunity The 1305 drive is designed for immunity to most externally generated interference. Usually, no special precautions are required beyond the installation practices provided in this publication. It is recommended that the coils of DC energized contactors associated with drives be suppressed with a diode or similar device, since they can generate severe electrical transients. In areas subject to frequent lightening strikes, additional surge suppression is advisable. Emission Careful attention must be given to the arrangement of power and ground connections to the drive to avoid interference with nearby sensitive equipment. The cable to the motor carries switched voltages and should be routed well away from sensitive equipment.

2-7

The ground conductor of the motor cable should be connected to the drive ground (GRD) terminal directly. Connecting this ground conductor to a cabinet ground point or ground bus bar may cause high frequency current to circulate in the ground system of the enclosure. The motor end of this ground conductor must be solidly connected to the motor case ground. Shielded or armored cable may be used to guard against radiated emissions from the motor cable. The shield or armor should be connected to the drive ground terminal and the motor ground as outlined in the Grounding section of this Installation chapter. Common mode chokes are recommended at the drive output to reduce the common mode noise. An RFI filter can be used and in most situations provides an effective reduction of RFI emissions that may be conducted into the main supply lines. If the installation combines a drive with sensitive devices or circuits, it is recommended that the lowest possible drive PWM frequency be programmed.

Page 22

2-8

Installation/Wiring

RFI FILTERING

RFI Filter Leakage Current

1305 drives can be installed with an RFI filter, which controls radio–frequency conducted emissions into the main supply lines and ground wiring.

The optional RFI filter may cause ground leakage currents. Therefore a solid ground connection must be provided.

If the cabling and installation recommendation precautions described in this manual are adhered to, it is unlikely that interference problems will occur when the drive is used with conventional industrial electronic circuits and systems. However, a filter is recommended if there is a likelihood of sensitive devices or circuits being installed on the same AC supply or if the motor cable exceeds 75 meters (250 feet). Beyond this length, capacitance to ground will increase the supply emissions. Where it is essential that very low emission levels must be achieved or if conformity with standards is required the optional RFI filter should be used. Refer to Appendix D and instructions included with the filter for installation and grounding information.

!

ATTENTION: To guard against possible equipment damage, RFI filters can only be used with AC supplies that are nominally balanced with respect to ground. In some installations, three–phase supplies are occasionally connected in a 3-wire configuration with one phase grounded (Grounded Delta). The filter must not be used in Grounded Delta supplies.

CE Conformity Refer to Appendix D.