Spec sheet · Allen-Bradley
Control Circuit and Load Protection
Spec sheet22 pagesPDF 2.7 MB
Catalog section for Allen-Bradley Bulletin 1492 fuse holders, 1492-CB, -GH, -GS, -SP and -SPU circuit breakers and their accessories.
Names · 4 models
The models it names
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
An Allen-Bradley catalog section on control circuit and load protection devices in the Bulletin 1492 line. It gives overviews, product selection tables, specifications and approximate dimensions for 1492-FB DIN rail fuse holders, 1492-CB manual motor controllers and miniature circuit breakers (such as the 1492-CB1F040, -CB1G070 and -CB2H010) with accessories like the 1492-ACBH1 auxiliary contact, 1492-GH and -GS supplementary protectors, 1492-SP supplementary protectors and 1492-SPU circuit breakers with UL 489 approval.
Its parts
- Bulletin 1492 Line: Control Circuit and Load Protection Devices
- Bulletin 1492-FB: DIN Rail Mounting Fuse Holders
- Bulletin 1492-CB: Manual Motor Controller/Supplementary Protector/Miniature Circuit Breaker
- Bulletin 1492-GH & 1492-GS: Supplementary Protectors (Miniature Circuit Breakers)
- Bulletin 1492-SP: Supplementary Protector/Miniature Circuit Breaker
- Bulletin 1492-SPU: Circuit Breaker with UL 489 Approval
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
An Allen-Bradley catalog section on Bulletin 1492 control circuit and load protection devices: 1492-FB fuse holders, 1492-CB, 1492-GH/GS and 1492-SP supplementary protectors, and 1492-SPU circuit breakers. It lists catalog numbers by poles, trip curve and current, the add-on modules, and the ratings, so a reader can choose and order a breaker.
- Document
- Catalog section on Bulletin 1492 breakers, supplementary protectors and fuse holders p. 1
- 1492-CB type
- 1492-CB: manual motor controller and supplementary protector in one device (Series C) p. 6
- 1492-CB trip curves
- 1492-CB: F (3…5 In), G (6…10 In), H (12…20 In) p. 2, 6
- 1492-CB current
- 1492-CB: continuous current ratings from 0.5 to 52 A p. 7
- 1492-CB poles
- 1492-CB: 1-pole, 1-pole plus neutral, 2-pole, 3-pole, 3-pole plus neutral p. 6
- 1492-CB wire
- 1492-CB: line and load terminals take #16…4 AWG copper wire p. 6
- 1492-SP type
- 1492-SP: energy limiting, thermal magnetic supplementary protector (series C) p. 14
- 1492-SP trip curves
- 1492-SP: B (3…5 In), C (5…10 In), D (10…20 In) p. 15
- 1492-SP poles
- 1492-SP: 1-pole, 1-pole plus neutral, 2-pole, 3-pole, 3-pole plus neutral p. 14
- 1492-SP IEC interrupt
- 1492-SP: 10 kA @ 240V AC one-pole; 10 kA @ 415V AC multi-pole p. 18
- 1492-SP undervoltage
- 1492-SP: undervoltage release 1492-ASPU115 (115V AC) or 1492-ASPU230 (230/240V AC) p. 19
- 1492-SP shunt trip
- 1492-SP: shunt trip module 1492-ASPA1 or 1492-ASPA2 p. 19
- 1492-CB DC versions
- 1492-CB: DF, DG and DH trip curves, 1- and 2-pole, supplementary protectors only p. 6, 8
- 1492-CB shunt trip
- 1492-CB: shunt trip modules for 5…12, 10…24, 20…48, 40…110 or 90…240V AC/DC p. 9
What this sheet walks you through
- Comparing the 1492 product lines by certification, poles, voltage and trip curve p. 2
- Why energy limiting breakers reduce let-through energy p. 3
- Choosing a 1492-CB by poles, trip curve and current rating p. 7, 8
- Choosing a DC-rated 1492-CB (DF, DG, DH) p. 8, 9
- Auxiliary, signal alarm and shunt trip modules for the 1492-CB p. 9
- 1492-CB specifications and approximate widths p. 10
- Choosing a 1492-SP by poles, trip curve and current rating p. 15, 16
- 1492-SP add-on modules and commoning links p. 17, 18
- 1492-SP and module specifications p. 18, 19
Good to know
- Supplementary protectors are meant for use where branch circuit protection is already provided or not required. p. 2
- 1492-CB devices with neutral are rated as supplementary protectors only. p. 7
- Fork style incoming terminals for the 1492-SP are not for North American installations. p. 18
- Pin style commoning links may be cut to length but are not for use with accessories. p. 17
- The printed dimensions are not intended for manufacturing purposes. p. 10
Questions this sheet answers
What trip curves does the Allen-Bradley 1492-CB come in?
F for resistive or slightly inductive loads, G for inductive loads and H for highly inductive loads; DC-rated versions use DF, DG and DH. p. 7, 8
Can a 1492-CB be used as a motor disconnect?
Yes. Series C 1492-CB devices are described as suitable for use as a motor disconnect from 0.5 to 30 A. p. 6
What wire size fits 1492-CB terminals?
Both the line and load side terminals accept #16…4 AWG copper wire. p. 6
Which undervoltage release module fits the 1492-SP?
The 1492-ASPU115 (115V AC) or the 1492-ASPU230 (230/240V AC). p. 19
Contents
Chapters and sections
Each line opens the PDF at its page.
- Control Circuit and Load Protection1
- Bulletin 1492 Line–Control Circuit and Load Protection Devices2
- Bulletin 1492-FB–DIN Rail Mounting Fuse Holders4
- Bulletin 1492-CB–Manual Motor Controller/Supplementary Protector/Miniature Circuit Breaker6
- Bulletin 1492-GH & 1492-GS–Supplementary Protectors (Miniature Circuit Breakers)11
- Bulletin 1492-SP–Supplementary Protector/Miniature Circuit Breaker14
- Bulletin 1492-SPU–Circuit Breaker with UL 489 Approval21