The text of a spec sheet · part 3 of 3

Control Circuit and Load Protection, pages 17 to 22

Pages 17 to 22 of 22

The original document is the PDF (2.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1492-CB1F040, Allen-Bradley 1492-CB1G070, Allen-Bradley 1492-CB2H010 and Allen-Bradley 1492-SP1D250

Page 17

Bulletin_1492-SP.qxd

12/01/2004

22:18

Page 4-17

Bulletin 1492-SP

Supplementary Protector/Miniature Circuit Breaker Product Selection, Continued Additional Devices Description

Cat. No.

Auxiliary Contact Module Switches when protective device is operated manually or tripped electrically 1 N.O. – 1 N.C. Form C Contact Auxiliary Contact Module Switches when protective device is operated manually or tripped electrically 2 N.O. – 2 N.C. 2 Form C Contact Auxilliary/Signal Alarm Contact Module 1 Auxillary Contact Switches when protective device Is operated manually or tripped electrically 1 N.O. – 1 N.C. Form C Contact 1 Signal Contact Switches when protective device Is tripped electrically 1 N.O. – 1 N.C. Form C Contact

Auxiliary Contacts

Undervoltage Release Module Use the Undervoltage Release Module to trip the adjacent breaker poles when the applied voltage is less than the nominal voltage. Undervoltage trip is often used when loss of power and eventual restoration of power creates an unsafe or unknown set of condition. Shunt Trip Module Use the Shunt Trip Module to trip the adjacent breaker poles from a remote location. The module is actuated by applying a voltage (Pickup Voltage) to the trip terminals.

1492-ASPH3

1492-ASPHH3

1492-ASPHS3

50…115V AC 110…240V AC

1492-ASPU115 1492-ASPU230

110…415V AC (110…230V DC) 12…110V AC (12…60 VDC)

1492-ASPA1 1492-ASPA2

Shunt Trip Modules are often used in emergency shutdown circuits where multiple power circuits must be switched off from a single location. Pieces Per Package

Cat. No.

10

199-DR1 1492-EAHJ35 1492-ASPLOA

Mounting Rail End Anchor Lockout Attachment

5

The following bus bars (communing links have CE approval only) Type Pin Style Commoning Links (may be cut to length, not for use with accessories) One Pole Two Pole (1p + N) Three Pole End Cap for two and three pole

No. of 1492-SP

Rated Operational la

Pieces Per Package

Cat. No.

1 m (56 per m) 1 m (26 per m) 1 m (16 per m)

40 30 30

1 1 1 10

1492-ACBCL1 1492-ACBCL2 1492-ACBCL3 1492-ACBEC1

1 m (56 per m) 1 m (19 per m)

40 30

1 1 10 10 sets (5/set)

1492-ASPCL1 1492-ASPCL3 1492-ASPEC1 1492-ASPCLPS

Fork Style Commoning Links (may not be cut) Four Pole Four Pole

2 3

120 120

5 5

1492-ASPCL408 1492-ASPCL412

For 1492-SP with an Auxiliary contact One pole One pole One pole Two pole (1p+N) Two pole (1p+N) Two pole (1p+N) Three pole Three pole

2 6 9 2 3 5 2 4

85 85 85 120 120 120 120 120

1492-ASPCL1A02 1492-ASPCL1A06 1492-ASPCL1A09 1492-ASPCL2A04 1492-ASPCL2A06 1492-ASPCL2A10 1492-ASPCL3A06 1492-ASPCL3A12

Fork Style Commoning Links (may be cut to length, not for use with accessories) One Pole Three Pole End Cap for two and three pole Protective Covers for unused forks termination

Visit our website: www.ab.com/catalogs

Page 18

Bulletin_1492-SP.qxd

12/01/2004

22:18

Page 4-18

Bulletin 1492-SP

Supplementary Protector/Miniature Circuit Breaker Product Selection, Continued/Specifications Type For multiple single pole 1492-SP, each with one Auxiliary

No. of 1492-SP 2x3 (1p) 2x3 (1p)+2 (1p) 3x3 (1p)

Rated Operational la 120 120 120

Pieces Per Package

Cat. No. 1492-ASPCL3AP06 1492-ASPCL3AP08 1492-ASPCL3AP09

2 6 12 2 3 6 2 4

85 85 85 120 120 120 120 120

1492-ASPCL102 1492-ASPCL106 1492-ASPCL112 1492-ASPCL204 1492-ASPCL206 1492-ASPCL212 1492-ASPCL306 1492-ASPCL312

1492-ASPCLT25 1492-ASPCLT35

For 1492-SP without Auxiliary contact One pole One pole One pole Two pole (1p+N) Two pole (1p+N) Two pole (1p+N) Three pole Three pole Incoming Terminals for fork style (Not for use in North American Installations) For max 25mm2 wire For max 35 mm2 wire

Description Tripping Characteristics Dielectric Strength Shock Vibration

Operating Temperature Range Shipment and Short TermTemperature Limits Housing Material Wire Size Recommended Wire Strip Length Electromechanical Life Switched Neutral Rating

B Curve Resistive or Slightly Inductive Loads

C Curve Inductive Loads

D Curve Highly Inductive Loads

3…5 In

5…10 In

10…20 In

1960V AC 25 G Half Sine Wave for 11 ms (3 Axis) Frequency Range: 10…2000 Hz Max. Amplitude (p-p) = 0.030 in Max. Acceleration = 5 G 2 hours each of 3 axis 23…104 °F (–5…+40 °C) noncondensing –40…+185 °F (–40…+85 °C) Nylon #18…8 AWG (1.0…25 mm2) 0.51 in (13 mm) 6000 operations (1 operation = 2 switching events) ON/OFF 277V AC

Description

Certifications Current Range

B Curve D Curve Resistive or C Curve Highly Slightly Inductive Inductive Inductive Loads Loads Loads Supplementary Protector UL 1077, CSA 22.2 No. 235 UL File Number E65138 1…63 A 0.5…63 A 0.5…40 A

One-pole without 5 kA @ 277V AC UZ series fuse Multi-pole Withstand without 5 kA @ 480Y/277V AC UZ Rating series fuse All poles 1 pole, 5 kA @ 48V DC UZ without 2 pole in series, 5 kA @ 125V DC UZ series fuse Miniature Circuit Breaker IEC/EN 60898 (VDE) Certifications IEC/EN 60947-2 (GL) Current Range 1…63 A 0.5…63 A 0.5…40 A Interrupt Rating One-Pole 10 kA @ 240V AC Interrupt Rating Multi-Pole 10 kA @ 415V AC Rated Impulse Withstand 4000V Voltage Uimp Rated Insulation Voltage Ui 440V AC Overload Category/Pollution Degree Rated Operation Voltage Ue Approval Rated Ultimate Short Circuit Breaking Capacity Icu

Visit our website: www.ab.com/catalogs

III/3 240/415V AC IEC/EN 60947-2 (GL) 15 kA 0.5 cos @ 240/415V AC

Page 19

Bulletin_1492-SP.qxd

12/01/2004

22:18

Page 4-19

Bulletin 1492-SP

Supplementary Protector/Miniature Circuit Breaker Approximate Dimensions Auxiliary Specifications Auxiliary Contact Module Dual Auxiliary Contact Module Auxiliary/Signal Alarm Module Cat. Nos. 1492-ASPH3 1492-ASPHH3 1492-SASPHS3 Degree of Protection Dimensions Weight Mechanical Lifespan Minimum Impulse Duration Minimum Command Time

0.045 kg 6000 operations, - Undervoltage Release Module Cat. Nos. 1492-ASPU115 1492-ASPU230 IP20 (IP00) See page 4-20 0.155 kg 10 000 operations, - Shunt Trip Module Cat. Nos. 1492-ASPA1 1492-ASPA2

0.155 kg 4000 operations > 15 ms ≤ 200ms 1492-ASPA1: 110…415V AC, 110…230V AC, 1492-ASPU115: Un-115V AC, Umin-50V AC, 1492-ASPU230: Un-230/240V AC, Umin-110V AC

1492-ASPA2: 12…110V AC, 12…60V AC

Inrush Current, 3.6/44 mA (AC/DC)

25/12 mA (AC) 15/2 mA (DC)

Dropout, 0.7…0.35 x Us, Voltage Range, - 0.7…1.1 x Us

AC 13 @ 250V AC 3 A AC 15 @ 250V AC 0.5 A DC 12 @ 110V DC 0.5 A Umin-5V AC, - 0.5…2.5 mm2 2 x 0.5…2 x 2.5 mm2 0.8 N•m @ 230V AC 2 A @ 110V DC 0.5 A Umin-5V CDC

0.5…4.0 mm2 2 x 0.5…2 x 2.5 mm2 1.1 N•m

1.0…25 mm2 2 x 1.0…2 x 4.0 mm2 2.4 N•m, - #18…14 AWG 2 x #18…2 x #14 AWG 7 lb•in

#18…14 AWG 2 x #18…2 x #14 AWG 10 lb•in

#18…8 AWG 2 x 18…2 x #12 AWG 21 lb•in

Operating Voltage

Max. Operating Current IEC Terminal Capacity IEC Rigid, CU Tightening Torque

UL 1077 CSA 22.2 No. 235 Αππροξιµατε ∆ιµενσιονσ

Max. Operating Current Terminal Capacity CU Tightening Torque

Approximate Dimensions Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.

Bulletin 1492-SP Series C

Bulletin 1492-SP

Visit our website: www.ab.com/catalogs

Page 20

Bulletin_1492-SP.qxd

12/01/2004

22:18

Page 4-20

Bulletin 1492-SP

Supplementary Protector/Miniature Circuit Breaker Approximate Dimensions, Continued Approximate Dimensions

Cat. No. 1492-ASPU_ _ _

Cat. No. 1492-ASPHH3 1492-ASPHS3 1492-ASPH3

Cat. No. 1492-ASPA_

Visit our website: www.ab.com/catalogs

Page 21

Bulletin_1492-SPU.qxd

12/01/2004

22:21

Page 4-21

Bulletin 1492-SPU

Circuit Breaker with UL 489 Approval Product Overview Bulletin 1492-SPU, Circuit Breaker with UL 489 Approval y True IP2X finger safe design (front) y Ratings to 240V AC, 10 000 A Interrupt Rating y A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) y 3 trip curves: B, C, and D y Time delay (D characteristic) for high inrush currents during inductive start-ups such as transformers and power supplies y Superior shock and vibration resistance capabilities, helps to prevent nuisance tripping y Mounts on DIN Rail y Line and load connections may be reversed

Table of Contents Specifications . . . . . . . 4-22 Product Selection . . . 4-22 Approximate Dimensions . . . . . . . . . 4-22

Standards Compliance y UL 489 y CSA 22.2 No. 5.1

Bulletin 1492-SPU circuit breakers are thermal magnetic type overcurrent protective devices meeting UL 489/CSA 22.2 No. 5.1. These devices are designed for the protection of a wide variety of products including: y Solenoids y Branch Circuit y Solenoids y Test Equipment y Controller I/O Points y Relay and Contactor Coils y Computers y Transformers y Automotive Systems y Power Supplies y Medical Equipment y Control Instrumentation

Mounting Multiple single-pole circuit breakers may be mounted adjacent to each other if switching the same polarity. If multiple circuit breakers are switching different polarities, allow a minimum spacing of 0.62 in. between circuit breakers. Use of (2) Cat. No. 1492-EA35 or (2) Cat. No. 1492-ER35 meets the spacing requirement.

Visit our website: www.ab.com/catalogs

Page 22

Bulletin_1492-SPU.qxd

12/01/2004

22:21

Page 4-22

Bulletin 1492-SPU

Circuit Breaker with UL 489 Approval Specification/Product Selection/Approximate Dimensions Σπεχιφιχατιονσ

Specifications Specifications Tripping Characteristic Cerifications Maximum Voltage Rating Dielectric Strength Shock Operating Temperature Range Shipment and Short Term Temperature Limits Tripping Characteristic Reference Temperature Housing Material Wire Size Recommended Wire Strip Length Interrupt Rating Terminal Torque Pieces per Carton

B Trip Resistive or Slightly Inductive 3…5 /n

C Trip Inductive 5…10 /n UL 489, CSA 22.2 No. 5.1 240V AC 1960V AC 25 g Half Sine Wave for 11 ms (2 Axis) 23…104 °F (–5…+40 °C) non-condensing

D Trip Highly Inductive 10…20 /n

–40…+185 °F (–40…+85 °C) 25 °C Nylon #14…12 AWG 75 C Cu Only 0.51 in (13 mm) 1-pole 10 kA @ 240V AC 2.4 N•m (21 lb•in) 12

Product Selection Continuous Current Rating (In) Ampere 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20

Cat. No., 1492-SPU1B010 1492-SPU1B015 1492-SPU1B020 1492-SPU1B030 1492-SPU1B040 1492-SPU1B050 1492-SPU1B060 1492-SPU1B070 1492-SPU1B080 1492-SPU1B100 1492-SPU1B130 1492-SPU1B150 1492-SPU1B160 1492-SPU1B200

Cat. No. 1492-SPU1C005 1492-SPU1C010 1492-SPU1C015 1492-SPU1C020 1492-SPU1C030 1492-SPU1C040 1492-SPU1C050 1492-SPU1C060 1492-SPU1C070 1492-SPU1C080 1492-SPU1C100 1492-SPU1C130 1492-SPU1C150 1492-SPU1C160 1492-SPU1C200

Approximate Dimensions Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.

Visit our website: www.ab.com/catalogs

Cat. No. 1492-SPU1D005 1492-SPU1D010 1492-SPU1D015 1492-SPU1D020 1492-SPU1D030 1492-SPU1D040 1492-SPU1D050 1492-SPU1D060 1492-SPU1D070 1492-SPU1D080 1492-SPU1D100 1492-SPU1D130, -