Manual · Allen-Bradley
POINT I/O Field Potential Distributor Module Installation Instructions
Manual16 pagesPDF 218 KB
Installation instructions for the Allen-Bradley 1734-FPD Series B POINT I/O field potential distributor module.
Covers · 1 model
The models it covers
Summary
What is in it
Installation instructions for the Allen-Bradley POINT I/O field potential distributor module, catalog number 1734-FPD, Series B. The module breaks the field power bus so that I/O modules to its right can take field power from a different source. The instructions cover environment and enclosure requirements, electrostatic discharge, European and North American hazardous location approvals, installing, removing, replacing and wiring the module, and specifications.
Its parts
- Important User Information
- Environment and Enclosure
- Preventing Electrostatic Discharge
- European Hazardous Location Approval
- North American Hazardous Location Approval
- About the Module
- Install the Module
- Remove the Module
- Replace the Module
- Wire the Module
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Rockwell Automation installation instructions, publication 1734-IN059C-EN-P (June 2005), for the Allen-Bradley POINT I/O Field Potential Distributor Module 1734-FPD, Series B. It explains what the module does, how to install, remove and replace it on a DIN rail, and how to wire 12/24V dc or 120/240V ac field power. It closes with the electrical, environmental and certification specifications.
- Function
- Breaks the POINT I/O field power bus so the I/O modules to its right get a new field power source; passes all other backplane signals p. 7
- Used with
- 1734-adapters, 1734-PDN and 1734D Series communication interfaces p. 7
- Input voltage
- 12V dc, 24V dc nominal (10 to 28.8V dc range); 120V ac, 240V ac nominal p. 13
- Input current
- 10 A maximum p. 13
- POINTBus current
- Pass through p. 13
- Indicators
- None p. 13
- DC wiring
- +V dc to terminal 6, -V dc to terminal 4, chassis ground to terminal 2 p. 11
- AC wiring
- L1 to terminal 6, L2/N to terminal 4, chassis ground to terminal 2 p. 12
- Dimensions (HxWxL)
- 76.2 x 25.4 x 133.4 mm (3.00 x 1.00 x 5.25 in) p. 13
- Operating temperature
- -20 to 55 oC (-4 to 131 oF) p. 14
- Storage temperature
- -40 to 85 °C (-40 to 185 °F) p. 14
- Relative humidity
- 5 to 95% non-condensing p. 14
- Wire size
- #22 to #14 AWG (0.324 to 2.08 sq. mm) solid or stranded copper rated 75 oC or greater; 1.2 mm insulation max p. 15
- Terminal screw torque
- 0.6 N-m (7 lb-in) p. 13
What this manual walks you through
- Choosing a suitable enclosure and environment p. 3
- Handling the module without electrostatic damage p. 4
- Installing the module on the DIN rail p. 8
- Removing the module p. 8, 9
- Replacing a module in an existing system p. 9, 10
- Wiring 12/24V dc field power p. 11
- Wiring 120/240V ac field power p. 12
Good to know
- Use zinc plated yellow-chromate steel DIN rail, secured about every 200 mm, since the module grounds through the rail. p. 8
- Inserting or removing the module with backplane power on can cause an arc; remove power or make sure the area is nonhazardous. p. 8
- To remove the 1734-FPD, first remove any I/O module installed in the base to its right. p. 8
- Open-type equipment with no enclosure rating; it must be mounted in an enclosure that opens only with a tool. p. 3, 15
- Intended for Pollution Degree 2 industrial environments at altitudes up to 2000 meters without derating. p. 3
Questions this manual answers
What voltages can the 1734-FPD distribute?
It is rated for 12V dc or 24V dc nominal (10 to 28.8V dc) and 120V ac or 240V ac nominal, at 10 A maximum. p. 13
Which terminals do I wire 24V dc to on the 1734-FPD?
+V dc goes to terminal 6, -V dc to terminal 4 and chassis ground to terminal 2. p. 11
Does the 1734-FPD have status LEDs?
No, its specifications list no indicators. p. 13
How do I remove a 1734-FPD from the DIN rail?
Remove any I/O module to its right, pull up the RTB removal handle, turn the orange DIN rail locking screw vertical and lift the module straight up. p. 7, 8, 9
What wire size does the 1734-FPD take?
#22 to #14 AWG solid or stranded copper wire rated at 75 oC or greater. p. 15
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 3 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.