Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of POINT I/O Field Potential Distributor Module Installation Instructions

Manual · Allen-Bradley

POINT I/O Field Potential Distributor Module Installation Instructions

Manual16 pagesPDF 218 KB

Installation instructions for the Allen-Bradley 1734-FPD Series B POINT I/O field potential distributor module.

Download the PDF218 KB

Covers · 1 model

The models it covers

Summary

What is in it

Installation instructions for the Allen-Bradley POINT I/O field potential distributor module, catalog number 1734-FPD, Series B. The module breaks the field power bus so that I/O modules to its right can take field power from a different source. The instructions cover environment and enclosure requirements, electrostatic discharge, European and North American hazardous location approvals, installing, removing, replacing and wiring the module, and specifications.

Its parts

  1. Important User Information
  2. Environment and Enclosure
  3. Preventing Electrostatic Discharge
  4. European Hazardous Location Approval
  5. North American Hazardous Location Approval
  6. About the Module
  7. Install the Module
  8. Remove the Module
  9. Replace the Module
  10. Wire the Module
  11. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Rockwell Automation installation instructions, publication 1734-IN059C-EN-P (June 2005), for the Allen-Bradley POINT I/O Field Potential Distributor Module 1734-FPD, Series B. It explains what the module does, how to install, remove and replace it on a DIN rail, and how to wire 12/24V dc or 120/240V ac field power. It closes with the electrical, environmental and certification specifications.

Function
Breaks the POINT I/O field power bus so the I/O modules to its right get a new field power source; passes all other backplane signals p. 7
Used with
1734-adapters, 1734-PDN and 1734D Series communication interfaces p. 7
Input voltage
12V dc, 24V dc nominal (10 to 28.8V dc range); 120V ac, 240V ac nominal p. 13
Input current
10 A maximum p. 13
POINTBus current
Pass through p. 13
Indicators
None p. 13
DC wiring
+V dc to terminal 6, -V dc to terminal 4, chassis ground to terminal 2 p. 11
AC wiring
L1 to terminal 6, L2/N to terminal 4, chassis ground to terminal 2 p. 12
Dimensions (HxWxL)
76.2 x 25.4 x 133.4 mm (3.00 x 1.00 x 5.25 in) p. 13
Operating temperature
-20 to 55 oC (-4 to 131 oF) p. 14
Storage temperature
-40 to 85 °C (-40 to 185 °F) p. 14
Relative humidity
5 to 95% non-condensing p. 14
Wire size
#22 to #14 AWG (0.324 to 2.08 sq. mm) solid or stranded copper rated 75 oC or greater; 1.2 mm insulation max p. 15
Terminal screw torque
0.6 N-m (7 lb-in) p. 13

What this manual walks you through

  • Choosing a suitable enclosure and environment p. 3
  • Handling the module without electrostatic damage p. 4
  • Installing the module on the DIN rail p. 8
  • Removing the module p. 8, 9
  • Replacing a module in an existing system p. 9, 10
  • Wiring 12/24V dc field power p. 11
  • Wiring 120/240V ac field power p. 12

Good to know

  • Use zinc plated yellow-chromate steel DIN rail, secured about every 200 mm, since the module grounds through the rail. p. 8
  • Inserting or removing the module with backplane power on can cause an arc; remove power or make sure the area is nonhazardous. p. 8
  • To remove the 1734-FPD, first remove any I/O module installed in the base to its right. p. 8
  • Open-type equipment with no enclosure rating; it must be mounted in an enclosure that opens only with a tool. p. 3, 15
  • Intended for Pollution Degree 2 industrial environments at altitudes up to 2000 meters without derating. p. 3

Questions this manual answers

What voltages can the 1734-FPD distribute?

It is rated for 12V dc or 24V dc nominal (10 to 28.8V dc) and 120V ac or 240V ac nominal, at 10 A maximum. p. 13

Which terminals do I wire 24V dc to on the 1734-FPD?

+V dc goes to terminal 6, -V dc to terminal 4 and chassis ground to terminal 2. p. 11

Does the 1734-FPD have status LEDs?

No, its specifications list no indicators. p. 13

How do I remove a 1734-FPD from the DIN rail?

Remove any I/O module to its right, pull up the RTB removal handle, turn the orange DIN rail locking screw vertical and lift the module straight up. p. 7, 8, 9

What wire size does the 1734-FPD take?

#22 to #14 AWG solid or stranded copper wire rated at 75 oC or greater. p. 15

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Environment and Enclosure3
  2. About the Module7
  3. Install the Module8
  4. Remove the Module8
  5. Replace the Module9
  6. Specifications13

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Environment and Enclosure1-6
  2. Pages 7 to 127-12
  3. Specifications13-16

The file

Revision and size

RevisionPublication 1734-IN059C-EN-P, June 2005
PublisherRockwell Automation
Pages16
PDF218 KB
TextText from the PDF itself.

The first pages · 3 of 16

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 16
Page 2
Page 2of 16
Page 3
Page 3of 16