For the Allen-Bradley 1734-FPD

Page 7

POINT I/O Field Potential Distributor Module 7

About the Module The purpose of the module is to break the field power distribution. Use the module to change the field power distribution source for I/O modules to the right of the module. This facilitates logical or functional partitioning of low-channel count, high I/O-mix applications using the 1734-adapters, 1734-PDN, and 1734D Series communication interfaces. This module passes through all POINT I/O backplane signals except the internal field power bus for field devices. You can use the module with a range of voltage inputs to include the following. • 5 to 250V dc applications • 24 to 240V ac applications • I/O modules

DIN Rail Locking Screw (orange) RTB Removal Handle Module Label Removable Terminal Block (RTB) Interlocking Side Pieces 43974

Publication 1734-IN059C-EN-P - June 2005

Page 8

8 POINT I/O Field Potential Distributor Module

Install the Module ATTENTION

ATTENTION

POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail material (e.g., aluminum, plastic, etc.) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm. When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

To install the module on the DIN rail, proceed as follows. 1. Position the module vertically above the DIN rail. 2. Engage the interlocking pieces with the unit on the left. 3. Press down firmly to install the module on the DIN rail. The locking mechanism locks the module to the DIN rail.

Remove the Module To remove a 1734-FPD module, you must first remove any I/O module installed in the base to the right. To remove the 1734-FPD module from the DIN rail, proceed as follows. Publication 1734-IN059C-EN-P - June 2005

Page 9

POINT I/O Field Potential Distributor Module 9 1. Pull up on the RTB removal handle to remove the terminal block.

42511fpd

2. Use a small-bladed screwdriver to rotate the DIN rail locking screw to a vertical position. This releases the locking mechanism. 3. Lift straight up to remove.

Replace the Module To install a replacement module in an existing system, proceed as follows. WARNING

When you connect or disconnect the removable terminal block (RTB) with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

1. Position the module vertically above the DIN rail. 2. Slide the module down to engage the interlocking sides pieces to the adjacent modules on both left and right sides. Publication 1734-IN059C-EN-P - June 2005

Page 10

10 POINT I/O Field Potential Distributor Module 3. Press down firmly to install the module on the DIN rail. The module locking mechanism snaps into place.

Wire the Module

NC CHAS GND NC = No Connection C = Common CHAS GND = Chassis Ground V = Supply

ATTENTION

NC CHAS GND

C

C

V

V 41970

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1734-IN059C-EN-P - June 2005

Page 11

POINT I/O Field Potential Distributor Module 11

12/24V dc Wiring 0

1

NC

NC

2

3

CHAS CHAS GND GND 4

12/24V dc

5

C

C

V

V

This supply will be connected to the internal field power bus.

Vdc 6

7

V = 12/24V dc, C = Common CHAS GND = Chassis Ground

43995

Connect

Terminal

+V dc

6

-V dc

4

Chas Gnd

2

12/24V dc becomes the internal field power bus for modules to the right.

Publication 1734-IN059C-EN-P - June 2005

Page 12

12 POINT I/O Field Potential Distributor Module

120/240V ac Wiring 0

1

NC

NC

CHAS GND

CHAS GND

L2/N

L2/N

L1

L1

2

3

4

120/240V ac

Vac

5

This supply will be connected to the internal field power bus.

7

6

L2/N = Neutral, L1 = 120/240V ac CHAS GND = Chassis ground

43995

Connect

Terminal

L1

6

L2/N

4

Chas Gnd

2

120/240V ac becomes the internal power bus for modules to the right.