Page 13

POINT I/O Field Potential Distributor Module 13

Specifications 1734-FPD Field Potential Distributor Module Specification

Value

Input Voltage Rating

12V dc, 24V dc nominal 10…28.8V dc range 120V ac, 240V ac nominal

Input Current

10 A maximum

Indicators

None

Module Location

Between I/O modules in 1734 system Breaks power bus

POINTBus Current

Pass through

Field Power Bus Supply Voltage

Supply Current

264V ac maximum, 12V dc, 24V dc, 10…28.8V dc range 120V ac, 240V ac, 50/60 Hz 10 A maximum

Terminal Base Screw Torque

0.6 N-m (7 lb-in)

Weight

0.12 kg (0.26 lb)

Dimensions Metric Imperial

HxWxL 76.2 x 25.4 x 133.4 mm 3.00 x 1.00 x 5.25 in

Weight

0.12 kg (0.27 lb)

Publication 1734-IN059C-EN-P - June 2005

Page 14

14 POINT I/O Field Potential Distributor Module Environmental Specifications Specification

Value

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -20...55 oC (-4...131 oF)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged Non-operating Cold) IEC60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat) IEC60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock) -40...85 °C (-40...185 °F)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged Non-operating Damp Heat) 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating) 5 g @ 10…500 Hz

Shock Operating

IEC60068-2-27 (Test Ea, Unpackaged Shock) 30 g

Shock Non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock) 50 g

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC6100-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3 10 V/m with 1 kHz sine-wave 80%AM at 30…2000 MHz 10 V/m with 200Hz 50% Pulse 100%AM at 900 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

EFT/B Immunity

IEC 61000-4-4 +4 kV at 2.5 kHz on power ports

Surge Transient Immunity

IEC 61000-4-5 +1 kV line-line (DM) and +2 kV line-earth (CM) on power ports

Publication 1734-IN059C-EN-P - June 2005

Page 15

POINT I/O Field Potential Distributor Module 15 Environmental Specifications Conducted RF Immunity

IEC61000-4-6 10V rms with 1 kHz sine-wave 80%AM 150 kHz…80 MHz

Enclosure Type Rating

None (open-style)

Power Consumption

None

Power Dissipation

None

Thermal Dissipation

None

Isolation Voltage (continuous-voltage withstand rating)

50 V continuous Tested to withstand 2600V dc for 60 s

Wire Size

#22…#14 AWG (0.324…2.08 sq. mm) solid or stranded copper wire rated @ 75 oC or greater 3/64 in (1.2 mm) insulation maximum

Wire Category1

1 - on power ports

1

Use this Conductor Category information for planning conductor routing. Refer to publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

Publication 1734-IN059C-EN-P - June 2005

Page 16

Certifications Certification

Value

Certification1 c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada c-UL-us UL Listed for Class I, Division 2, Group A,B,C,D Hazardous Locations, certified for U.S. and Canada CE European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions European Union 72/23/EEC LVD Directive, compliant with: EN 61131-2; Programmable Controllers C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial Emissions EEX European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2) when used at or below 60V ac or 75V dc

(when product is marked)

1See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details. POINT I/O and POINTBus are trademarks of Rockwell Automation.

Publication 1734-IN059C-EN-P - June 2005 Supersedes Publication 1734-IN059B-EN-P - August 2000