Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Installation Instructions: SLC 500 Modular Chassis (Catalog Numbers 1746-A4, -A7, -A10, and -A13 Series B)

Manual · Allen-Bradley

Installation Instructions: SLC 500 Modular Chassis (Catalog Numbers 1746-A4, -A7, -A10, and -A13 Series B)

Manual80 pagesPDF 3.7 MB

Installation instructions for the Allen-Bradley SLC 500 modular chassis 1746-A4, -A7, -A10 and -A13 Series B, in six languages.

What this file really is

The old site listed this file as a manual for the Allen-Bradley 1746-A2, 1746-A4 and 3 more models. The file is named for the 1746-A2, but the document covers only the 1746-A4, -A7, -A10 and -A13 Series B chassis.

Download the PDF3.7 MB

Names · 4 models

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley installation instructions for the SLC 500 modular chassis, catalog numbers 1746-A4, -A7, -A10 and -A13 Series B. The English section explains how to prepare, allow mounting space, mount and ground the chassis, fit the optional chassis interconnect cable, install I/O modules and attach the power supply, with specifications and hazardous location notes. The same content follows in French, German, Italian, Spanish and Portuguese, and the document ends with mounting dimensions.

Its parts

  1. English Section
  2. Section française
  3. Deutscher Abschnitt
  4. Sezione in Italiano
  5. Sección en español
  6. Seção em Português
  7. Mounting Dimensions

From the manual

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1746-IN016C-MU-P, December 2003) for the Allen-Bradley SLC 500 modular chassis, catalog numbers 1746-A4, -A7, -A10 and -A13 Series B; the 1746-A2 is not covered. It shows how to space, mount and ground the chassis, connect up to three chassis, and fit modules and a power supply, with specifications. The same text repeats in six languages; the English section was read.

Read for this summary: pages 1 to 14 and 80 of 80.

What it is
SLC 500 modular chassis, Series B, panel mount p. 1
Backplane current
5.1V dc at 10A; 24V dc at 2.88A (max.) p. 13
Expansion
Up to three chassis (30 I/O slots max) joined by a 1746-C7 or 1746-C9 interconnect cable p. 6, 12
Operating temperature
0 to +60 C (+32 to +140 F) p. 13
Mounting hardware
M4 or M5 (#10 or #12) phillips screws with star washers, or SEM screws p. 5
Logic ground
1M ohm resistor between logic ground and chassis ground (Series B) p. 12
Module slots
4, 7, 10 or 13, by model p. 13
Mounting tabs
1746-A4 and -A7: 4; 1746-A10: 6; 1746-A13: 8 p. 5
Dimensions
17.1 cm high, 14.5 cm deep; 17.7 cm (1746-A4) to 50.2 cm (1746-A13) wide with tabs p. 13
Weight
0.75 kg (1746-A4) to 1.9 kg (1746-A13), without modules p. 13
Storage temperature
-40 to +85 C (-40 to +185 F) p. 13
Relative humidity
5 to 95%, without condensation p. 13
Ground wiring
5.2 mm2 (10 AWG) from each chassis to the ground bus; 8.3 mm2 (8 AWG) minimum to the grounding-electrode system p. 11

What this manual walks you through

  • Gathering hardware and documents before installing p. 5
  • Allowing enough mounting space p. 6
  • Mounting the chassis on the enclosure back panel p. 7, 8
  • Grounding the chassis p. 9, 11
  • Installing a central ground bus p. 10
  • Installing the chassis interconnect cable p. 12
  • Installing I/O modules and attaching the power supply p. 12
  • Grounding with a 1746-P3 power supply p. 12, 13

Good to know

  • Two 1746-A13 chassis stacked vertically with a 1746-C9 cable must be no more than 15.3 cm (6.0 in) apart. p. 6
  • Do not drill above a chassis that already holds a processor and I/O modules. p. 7
  • Shim mounting tabs that do not lie flat; a warped chassis can damage the backplane. p. 8
  • Leave the connector plug on the left side connector when chassis are not joined. p. 12
  • Do not stack one ground lug directly on another. p. 11

Questions this manual answers

How many SLC 500 chassis can be connected together?

Up to three, for a maximum of 30 I/O slots. p. 12

What is the backplane current of a 1746-A7 chassis?

All four chassis list 5.1V dc at 10A and 24V dc at 2.88A maximum. p. 13

How many mounting tabs does a 1746-A13 have?

Eight. p. 5

What wire size grounds an SLC 500 chassis?

A ground lug with 5.2 mm2 (10 AWG) wire on a chassis mounting tab, run to the ground bus. p. 10

What is the operating temperature of the 1746 chassis?

0 to +60 C (+32 to +140 F). p. 13

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1746-IN016C-MU-P SLC 500™ Modular Chassis Installation Instructions1
    1. English Section3
    2. Section française15
    3. Deutscher Abschnitt27
    4. Sezione in Italiano39
    5. Sección en español51
    6. Seção em Português63
  2. Back Cover80

From the PDF’s own bookmarks.

The whole text · 8 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80

The file

Revision and size

Part no.1746-IN016C-MU-P
RevisionDecember 2003
PublisherRockwell Automation
Pages80
PDF3.7 MB
TextText from the PDF itself.
1746-IN016C-MU-P

The first pages · 3 of 80

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 80
Page 2
Page 2of 80
Page 3
Page 3of 80