Page 11

SLC 500™ Modular Chassis

11

Connect Equipment Grounding Conductor to Ground Bus Connect an equipment grounding conductor directly from each chassis to an individual bolt on the ground bus.

ground bus mounting ground bus equipment grounding conductors bolt ground lug tapped hole star washer

Grounding-electrode conductor to grounding-electrode system

• use 2.54 cm (1in) copper braid or 5.2 mm2 (10 AWG) copper wire to connect each chassis, the enclosure, and a central ground bus mounted on the back-panel • use a steel enclosure to guard against electromagnetic interference (EMI) • make sure the enclosure door viewing window is a laminated screen or a conductive optical substrate (to block EMI) • install a bonding wire for electrical contact between the door and the enclosure; do not rely on the hinge

IMPORTANT

Do not lay one ground lug directly on top of the other; this type of connection can become loose due to compression of the metal lugs. Place the first lug between a star washer and a nut with a captive star washer. After tightening the nut, place the second lug between the first nut and a second nut with a captive star washer.

Connect Ground Bus to Grounding-Electrode System The grounding-electrode system is at earth-ground potential and is the central ground for all electrical equipment and ac power within any facility. Use a grounding-electrode conductor to connect the ground bus to the grounding-electrode system. Use at minimum 8.3 mm2 (8 AWG) copper wire for the grounding-electrode conductor to guard against EMI. The National Electrical Code specifies safety requirements for the grounding-electrode conductor.

Publication 1746-IN016C-MU-P - December 2003

Page 12

12

SLC 500™ Modular Chassis

Install the Chassis Interconnect Cable (optional) To connect up to three chassis together (for a maximum of 30 I/O slots), install the chassis interconnect cable before attaching your power supply.

SLC chassis where processor will be installed

Install Your I/O Modules and Attach Your Power Supply Use the installation instructions/user manuals for your modules to install them into the chassis. Use the installation instructions for your power supply to attach it to your chassis.

ATTENTION

! IMPORTANT

• Keep the connector plug on the left side-connector of the chassis if you are not connecting chassis together. • Remove the protective label from the top of the power supply before applying power.

Series B chassis have a 1M Ω resistor between logic ground and chassis ground. When using a 1746-P3 power supply, follow the grounding instructions provided with the power supply to avoid unwanted potentials across the logic ground of the SLC processor.

Publication 1746-IN016C-MU-P - December 2003

Page 13

SLC 500™ Modular Chassis

13

1746-P3

Not used Not used +24V dc DC Neut Chassis Ground

Controller Logic Ground

Safety Ground

Functional Ground

SLC Chassis, Series B

Functional Ground

Specifications SLC Chassis, Series B 1746-A4

1746-A7

1746-A10

1746-A13

39.7 x 17.1 x 14.5 cm (15.9 x 6.8 x 5.8 in)

50.2 x 17.1 x 14.5 cm (20.1 x 6.8 x 5.8 in)

1.45 kg (3.2 lbs)

1.9 kg (4.2 lbs)

5.1V dc @ 10A; 24V dc @ 2.88A

5.1V dc @ 10A; 24V dc @ 2.88A

5.1V dc @ 10A; 24V dc @ 2.88A

7

10

13 panel mount panel mount panel mount dimensions (with tabs) -W x H x D 17.7 x 17.1 x 14.5 cm (7.1 x 6.8 x 5.8 in)

28.2 x 17.1 x 14.5 cm (11.3 x 6.8 x 5.8 in)

approximate weight (without modules) 0.75 kg (1.7 lbs)

1.1 kg (2.4 lbs)

maximum backplane current 5.1V dc @ 10A; 24V dc @ 2.88A module slots 4 type of mount panel mount operating conditions operating temperature: 0°C to +60°C (+32°F to +140°F) storage temperature: -40°C to +85°C (-40°F to +185°F) relative humidity: 5 to 95% (without condensation)

Publication 1746-IN016C-MU-P - December 2003

Page 14

14

SLC 500™ Modular Chassis

Specifications (continued) certification

C

R

UL Listed Industrial Control Equipment, certified for US and Canada UL Listed for Class 1 Division 2, Group A, B, C, D Hazardous Locations, certified for US US and Canada European Union 89/336/EEC EMC Directive, compliant with EN 50082-2 Industrial Immunity EN 61326, Meas./Control/Lab., Industrial Requirements EN 61000-6-2, Industrial Immunity EN61000-6-4, Industrial Emissions

Australian Rediocommunications Act, compliant with : AS/NZS 2064, Industrial Emissions N223

Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. WARNING

!

EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. • Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous. • All wiring must comply with N.E.C. article 501-4(b).

Publication 1746-IN016C-MU-P - December 2003

Page 15

Notice d'installation

Châssis modulaire SLC 500™

(Références 1746-A4, -A7, -A10 et -A13 série B) Section française

Contenu de cette publication Utilisez cette publication comme guide pour l’installation d’un châssis modulaire SLC 500.

Installation A propos de............................................................................. Voir page Préparation de l’installation ...................................................................17 Dégagements nécessaires......................................................................18 Installation du châssis ............................................................................19 Mise à la terre du châssis ......................................................................21 Installation du câble d’interconnexion de châssis (en option) ...............24 Installation des modules d’E/S et raccordement de l’alimentation.......24

Références Pour ces informations .......................................................... Voir page Caractéristiques......................................................................................25 Environnements dangereux ....................................................................26 Dimensions de montage .........................................................................75 Pour de plus amples informations sur l’installation, consultez la publication 1747-UM011, SLC 500 Modular Style User Manual.

Publication 1746-IN016C-MU-P - Décembre 2003

Page 16

16

Châssis modulaire SLC 500™

Informations importantes destinées à l’utilisateur En raison de la diversité des utilisations des produits décrits dans le présent manuel, les personnes qui en sont responsables doivent s’assurer que toutes les mesures ont été prises pour que l’application et l’utilisation des produits soient conformes aux exigences de performance et de sécurité, ainsi qu’aux lois, règlements, codes et normes en vigueur. La société Rockwell Automation ne saurait en aucun cas être tenue pour responsable des dommages indirects ou résultant de l’utilisation ou de l’application de ces produits. Les illustrations, schémas et exemples de programmes contenus dans cette publication sont présentés à titre indicatif seulement. En raison du nombre important de variables et d’impératifs associés à chaque installation, la société Rockwell Automation ne saurait être tenue pour responsable ni être redevable (y compris en matière de propriété intellectuelle) des suites d’utilisation réelle basée sur les exemples et schémas présentés dans cette publication. La publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (disponible auprès de votre agence commerciale Rockwell Automation), décrit certaines différences importantes entre les équipements électroniques et les équipements électromagnétiques, qui devront être prises en compte lors de l’application de ces produits, comme indiqué dans la présente publication. Toute reproduction totale ou partielle du présent manuel sans autorisation écrite de la société Rockwell Automation est interdite. Des remarques sont utilisées tout au long de cette publication pour attirer votre attention sur les mesures de sécurité à prendre en compte. Les symboles suivants vous aident à identifier un danger potentiel, à l’éviter et à en discerner les conséquences : AVERTISSEMENT

!

Actions ou situations risquant de provoquer une explosion dans un environnement dangereux et d’entraîner des blessures pouvant être mortelles, des dégâts matériels ou des pertes financières.

ATTENTION

! IMPORTANT

Actions ou situations risquant d’entraîner des blessures pouvant être mortelles, des dégâts matériels ou des pertes financières.

Informations particulièrement importantes dans le cadre de l’utilisation du produit.

Publication 1746-IN016C-MU-P - Décembre 2003

Page 17

Châssis modulaire SLC 500™

17

Préparation de l’installation Vérifiez que vous disposez du matériel suivant.

Vis M4 ou M5 (n° 10 ou n° 12) • des vis cruciformes et des rondelles éventail (ou vis SEM, vis cruciforme avec rondelle éventail imperdable) pour les pattes de fixation du châssis ; Ce châssis :

Comporte :

1746-A4

4 pattes de fixation

1746-A7

4 pattes de fixation

1746-A10

6 pattes de fixation

1746-A13

8 pattes de fixation

• un tournevis cruciforme ; • une perceuse.

Documentation La documentation sur : • votre processeur ou adaptateur d’E/S ; • votre bloc d’alimentation ; • vos modules de communication et/ou modules d’E/S.

Remarque sur l’installation Le panneau de fixation de l’alimentation (panneau de gauche) comporte des vis, comme le montre la figure ci-dessous. Les panneaux du centre et de droite sont maintenus en position par un loquet moulé et ne requièrent pas de vis. vis loquet loquet vis loquet loquet

Publication 1746-IN016C-MU-P - Décembre 2003

Page 18

18

Châssis modulaire SLC 500™

Dégagements nécessaires

IMPORTANT

Veillez à respecter les dégagements minimum requis. Vous pouvez connecter jusqu’à trois châssis SLC (pour un maximum de 30 emplacements d’E/S).

> 15,3 cm Armoire

> 10,2 cm

1746-C9

1746-C7

15,3 à 20 cm

> 10,2 cm > 15,3 cm 7,7 à 10,2 cm

IMPORTANT

Lorsque vous connectez deux châssis 1746-A13 verticalement avec un câble 1746-C9, l’espace entre les châssis ne doit pas dépasser 15,3 cm.

Pour les dimensions du :

Voir page :

côté gauche de tous les châssis

75

1746-A4, -A7

75

1746-A10, -A13

76

Publication 1746-IN016C-MU-P - Décembre 2003

Page 19

Châssis modulaire SLC 500™

19

Installation du châssis 1. Percez des trous dans le panneau arrière de l’armoire pour les pattes de fixation du châssis.

ATTENTION

!

Faites attention aux copeaux métalliques lors du perçage des trous de fixation du châssis SLC. Ne percez pas de trous au dessus d’un châssis SLC s’il contient un processeur et des modules d’E/S.

2. Mettez en place les vis pour les pattes de fixation supérieures.

Vis cruciforme M4 ou M5 (n° 10 ou n° 12) et rondelle éventail (ou vis SEM)

CONSEIL

Grattez la peinture du panneau arrière pour établir un contact électrique entre le châssis et le panneau arrière.

Publication 1746-IN016C-MU-P - Décembre 2003

Page 20

20

Châssis modulaire SLC 500™

3. Installez le châssis sur les vis que vous avez mises en place, puis serrez les vis. ATTENTION

!

Si les pattes de fixation du châssis ne sont pas droites avant le serrage des vis, utilisez des rondelles supplémentaires comme cales afin que le châssis ne se déforme pas lorsque vous serrerez les vis. Le gauchissement du châssis peut endommager le fond de panier et provoquer des mauvais contacts.

4. En laissant les pattes aux extrémités droite et gauche desserrées pour la mise à la terre, installez les vis restantes sur les autres pattes de fixation (pour un châssis à quatre emplacements, laissez les deux pattes desserrées).

Publication 1746-IN016C-MU-P - Décembre 2003