Omega Series Configurable Press Control System User Manual (Cat. No. 6556-SCBK3 and 6556-SCBK3DC), pages 37 to 45

Pages 37 to 45 of 54

The original document is the PDF (241 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1746-HS, Allen-Bradley 1746-IA16, Allen-Bradley 1746-IB8, Allen-Bradley 1746-IB32, Allen-Bradley 1746-IO8, Allen-Bradley 1746-ITB16, Allen-Bradley 1746-IV16, Allen-Bradley 1746-IV32, and 7 more models

Page 37

Determining Your DM and PLS Requirements Objectives

This chapter helps you:

• • • • • • select DM operating modes apply DM “windows” select DM output responses use DM worksheet select PLS operating modes use PLS worksheet

1 2 3 3 5 5

Important: For instructions on using PanelView 600 screens to configure DM and PLS channels, refer to the panelView 600 Operating Instructions (publication 6556-5.8).

Operation of DM Modes

The purpose of DM channels is to verify that predictable conditions in your press operation take place. When the software detects a fault condition, it sets a selected output response. You select the type of mode for each channel from the following:

• • • • cyclic in-position transfer static Use the following table to help you select the types of channel modes required for your application. When Input Signals Are:

We Call This Mode:

Used, For Example To:

Synchronized with crankshaft rotation, and detected within a zone or rotation (window)

Cyclic or In-position detect parts in position, or parts ejected

Synchronized with crankshaft rotation as parts are moved through multiple transfer locations

Transfer verify the progression of the part from one transfer location to the next

Independent of press stroke

Static detect the end of stock

Publication 6556-6.5.11 August 1998

Page 38

6–2

Determining Your

Definition of Window and Description of Modes Window Input signals for Cyclic (CYC) and In-position (POS) modes are synchronized with the rotation of the crankshaft, and must be detected within a zone of crankshaft rotation. We call this zone a window. For example, a part-detect signal could be expected within a window of 80-110o to indicate that a part was inside a die before it was hit by a stroke. When the software detects input signals that are different from those described here, the software generates a fault signal. We graphically define these (window) inputs as follows: angle ON

Window angle OFF

ON

Crankshaft rotation

OFF

Input transition

Cyclic (CYC) Use this mode to verify that a pulse from the sensor (OFF-ON-OFF) occurred within the window once each stroke. For example, use it to detect that a part moved past a monitor. Transition Diagram a b

For These Expected Transitions

Input is NOT ALLOWED When Sensor:

Which Results in a Fault Signal Sent After:

Sensor turns ON then OFF within window

1. stays ON beyond window window goes OFF

2. turns ON outside window sensor turns ON

3. remains OFF for the cycle next window goes ON

In-position (POS) Use this mode to verify that the sensor signal remained ON within the entire window once each stroke. The signal must cycle OFF outside the window. Use it to detect if ejector and other automation parts are retracted to home position. Transition Diagram a b

For These Expected Transitions

Input is NOT ALLOWED When the Sensor Signal:

Which Results in a Fault signal Sent After:

Sensor turns ON before, and OFF after window

1. turns OFF before window goes OFF sensor turns OFF

2. does not turn OFF outside window next window goes ON

3. remains OFF for the cycle next window goes OFF

Transfer Mode (XFR) Use transfer mode to monitor the transfer of a part in a transfer press, from one transfer location to the next for each stroke of the press. Typically, each transfer location has an in-position sensor. The logic of transfer mode is similar to that of a first-in-first-out (FIFO) shift register. It monitors sensor stations in sequence, a pair at a time. Important – When setting up XFR-mode channels, you must: 1. Assign consecutive channels to consecutive sensor stations in the sequence. 2. Configure the first input in the transfer-mode sequence (upstream input) as the first channel in the sequence with its output bypassed 3. Configure remaining channel outputs for the desired fault response.

Publication 6556-6.5.11 August 1998

Page 39

Determining Your

6–3

In the following 4-station example, the software looks for signals from in-position switches to be in correct state when the window is ON. It monitors the up-stream station 1 and station 2 as a pair. Then, it monitors consecutive pairs of stations (stations 2 & 3, 3 & 4, etc.) Stroke n

Window ON

Stroke n +1

Stroke n +2

OFF

OFF

Window ON

Window ON

Stroke n +3 OFF Window ON

Part in the die

Part in transfer

Part in the die

Part in transfer

Up-stream Station 1

Station 2

Station 3

Station 4

120V ac or 24V dc Channel Setup

Channel 1 XFR mode input Output bypassed channel 2 channel 3 channel 4 XFR-mode Input XFR-mode Input XFR-mode Input Select desired output response for channels 2-4.

Static Mode (STC) Use this mode to detect that an event occurred independent of the press stroke. When a static-mode input turns Off, the programmed output is turned On. For example, use it to detect end of stock.

Output Responses for DM Channels

When the software detects a channel fault, it displays the channel number and type of fault on a PanelView screen. The software also sets a fault response that you select from the following: warning (PanelView 600 displays alarm banner on the active screen) stop on top stop now output by-passed (no fault response) for XFR-mode up-stream station or channels not used

Worksheet A for DM Channels

Use this worksheet to identify your DM channels. Write down these items in the space provided: Purpose of DM channel Mode of DM channel (by code) Type of input switch Location of input switch Output response (by code)

Publication 6556-6.5.11 August 1998

Page 40

6–4

Determining Your

We repeat the codes for channel mode and output response: Channel Mode

Code

Channel mode

Code

Cyclic

CYC

Transfer

XFR

In-position

POS

Static

STC

Output Response

Code

Warning

WRN

Stop on Top

ST

Stop Now

SN

Bypass

BP

Job Name #

Purpose of DM Channel

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Publication 6556-6.5.11 August 1998

Type of Switch / Device

Location of Switch / Device

Mode

Output

Page 41

Determining Your

Operation of the Programmable Limit Switch (PLS)

6–5

Allen-Bradley Programmable Limit Switch software is designed to turn outputs ON and OFF at precise crankshaft positions synchronized with crankshaft rotation monitored with a resolver. You can preset up to 8 ON/OFF settings at angles from 0-359o. You can also turn the output OFF with a timer. A PLS output turns ON and OFF according to how you configure it. For example: Turn ON a PLS Output with a:

Turn OFF a PLS Output with a:

crankshaft ON angle that you preset crankshaft OFF angle that you preset, or PLS timer that you preset 0o Near-top Zone

The output turns ON at a preset angle. Down stroke 90o Zone

Up 270o stroke Zone The output turns OFF at a preset angle or time. Bottom 180o

As a result, you can use PLS outputs to effectively control auxiliary press machinery such as lifters, grippers blow-off valves, and inter-press automation by programming your application-specific output responses. The output of each PLS channel is directed to the 1746-OA16 module in chassis A, slot 4, points 8-15 for PLS channels 1-8.

Worksheet B for PLS Channels

Use this worksheet to identify your PLS channels. Write down these items in the space provided: Name of the PLS-controlled function Preset angle to turn ON Preset time or angle to turn OFF Output point to control the function (1746-OA16, points 8-15, in chassis A, slot 4)

Publication 6556-6.5.11 August 1998

Page 42

6–6

Determining Your

Job Name slot 4 Output Pt 8 9 10 11 12 13 14 15

Publication 6556-6.5.11 August 1998

PLS-controlled Function

Preset ON Angle (0–359o)

Preset OFF Angle or Time (ms)

Page 43

Testing DM and PLS Channels Objectives

This chapter gives you procedures for testing the following:

• • • •

Testing a DM Channel

Data monitor (DM) channel DM transfer-mode channel Resolver inputs Programmable limit switch (PLS) channel

1 2 3 3

In this procedure, you test one channel at a time to verify:

• signal thru-put is correct from the input switch into the data table • that the software detects and indicates a channel fault • that the software and wiring are set up to reset a fault Use these screens: Active DM screen to enter values, and Status screen for fault prompts. Observe or set up the following initial conditions before starting, regardless of how you intend to use each channel later.

• all DM channels are set for by-pass mode (Active DM screen) • all DM channel outputs are set for by-pass mode (Active DM screen) • the fault prompt states “Channels 1-16 Cleared” (Status screen) Important: Your SLC processor must be programmed, and in Run mode. Start with channel 1. 1. Close the input switch. 2. From the Active DM screen, select – channel mode = static – channel output = warning 3. Go to the Status screen. 4. Open the input switch. 5. Observe the fault prompt “Channel 1 Warning”. If you do not see a warning on the Status screen, check for errors in input switch wiring (chapter 3). 6. Close the input switch. 7. Press the fault reset pushbutton. 8. Observe that the fault prompt returns to “Channels 1-16 Cleared”. Important: Repeat this procedure for each operational DM channel.

Publication 6556-6.5.11 August 1998

Page 44

7–2

Testing DM and PLS Channels

Testing DM Transfer-mode Channels

Test the series of channels that you assigned as transfer mode to verify that you have correctly set them up. Before you begin, be sure that:

• Important: you tested all your DM channels as described above to verify DM channel mapping and wiring • the entry station is set up correctly with a bypassed output; – its channel number is the first in the series of XFR-mode channels – its output mode is set to “by-passed” – its window is set correctly (A part must be in position throughout the window.) • you set up your sequence of XFR-mode channels with: – consecutive (uninterrupted) channel numbers – window On/Off setpoints (A part must be in position throughout the window.) – channel mode = transfer mode – output mode = stop now (top stop or warning) • channel switches are actuated in the same order as their channel numbers, ie channel 1 switch first, channel 2 switch second, etc.) Follow this procedure: 1. With the press in motion, transfer a part through the first two stations: [channel 1 with bypassed output & channel 2]. 2. Stop the press. If the part transfers correctly, the software should not indicate a fault. If it does, check that the window turn On and Off settings are correct. 3. Restart the press and transfer the part to the next station, either stopping at each station or completing the series of stations. The software should not indicate a fault. If it does, check that the window turn On and Off settings are correct. 4. As appropriate, stop the press and safely remove a part. 5. Restart the press and machinery. When the crankshaft position reaches the next window, the software should indicate a fault at the next station because the part is missing. Observe fault prompt on Status screen. 6. To resume transfer-mode operation: • Press the Resume Operation pushbutton. (This pushbutton resets the logic of the remaining transfer-mode channels according to the status of the errant part: you can remove it or place it back in position to resume operation.) • Press the fault reset pushbutton. • Restart the press. If the software faults, check wiring of the Resume Operation pushbutton (chapter 3).

Publication 6556-6.5.11 August 1998

Page 45

Testing DM and PLS Channels

Testing the Resolver Input

7–3

In this procedure, you observe that the angular position of the crankshaft matches the observed die position of the stamping press. Use these screens: Active PLS/DM menu to read indicated crankshaft position 1. Jog the press through one stroke. 2. Observe that reported position matches the crankshaft position. Top dead center and bottom are the best positions to observe. If the press position is not reported, refer to the manufacturer’s troubleshooting information for your resolver and resolver input module. Also check for errors in resolver input wiring (chapter 3) If the reported press position shows rotation in a direction opposite to the crankshaft, reverse the resolver input wires.

Testing a PLS Channel

Test one channel at a time to verify signal thru-put from the data table to the output module (or output device). Use these screens: Active PLS to turn On each channel. (You also observe the channel LED indicator to verify that the output turned ON. You may also observe the output device that you wired to the output terminal for each channel.) Observe or set up the following initial conditions before starting.

• all PLS channel setpoints are cleared (Active PLS screen) • all PLS channels are OFF 1. From the Active PLS screen, cursor to PLS channel 1. ATTENTION: Before going to step 2, be aware that when you turn ON a PLS channel, the PLS output may turn on immediately. 2. Turn on PLS channel 1 with an up/down arrow key, plus return key. 3. At the output module, observe that the LED indicator for PLS channel 1 turned on (or that the output device turned on). If the output LED for the channel did not turn on (or the output device did not turn on), check for errors in wiring of your output device (chapter 3) 4. Turn off the PLS channel with an up/down arrow key plus return key. 5. Cursor to the next channel and repeat steps 1-4 until you have tested all PLS channels wired into your system.