For the Allen-Bradley 1746-HSCE
Page 1
Installation Instructions
High-Speed Counter Module (Catalog Number 1746-HSCE)
Inside ................................................................................................Page For More Information............................................................................... 3 Hazardous Location Considerations ........................................................ 4 Environnements dangereux ..................................................................... 4 High-Speed Counter Module Overview................................................... 5 Dip Switch and Jumper Locations ........................................................... 6 Install the Module.................................................................................. 10 Remove the Terminal Block.................................................................... 11 Wire the Removable Terminal Block...................................................... 11 Important Wiring Considerations .......................................................... 12 Input and Output Connections ............................................................... 13 Outputs................................................................................................... 14 Encoders................................................................................................. 15 Single-Ended Wiring (Discrete Devices)................................................ 18 Limit Switch Wiring ............................................................................... 19 Specifications ........................................................................................ 20
Publication 1746-IN011C-EN-P - April 2005
Page 2
2
High-Speed Counter Module
Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence
SHOCK HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.
Publication 1746-IN011C-EN-P - April 2005
Page 3
High-Speed Counter Module
3
For More Information Related Publications For
Refer to this Document
Pub. No.
A more detailed description on how to configure and program the High-Speed Counter Module.
High-Speed Counter Module User Manual
1746-6.5
A more detailed description on how to install and use your modular SLC™ 500 system.
SLC 500 Modular Hardware Style Installation and Operation Manual
1747-UM011
A reference manual that contains status file data, instruction set, and troubleshooting information.
SLC 500 Instruction Set Reference Manual
1747-RM001
To view and download pdfs, go to Literature Library at http://www.rockwellautomation.com/literature. To order printed copies, contact your Allen-Bradley® Distributor or Rockwell Automation® Sales Office.
Publication 1746-IN011C-EN-P - April 2005
Page 4
4
High-Speed Counter Module
Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. WARNING
EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. • Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous. • All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux Cet équipement est conçu pour être utilisé dans des environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux. AVERTISSEMENT
DANGER D’EXPLOSION • La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe I, Division 2. • Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée. • Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée.
Publication 1746-IN011C-EN-P - April 2005
Page 5
High-Speed Counter Module
5
High-Speed Counter Module Overview The High-Speed Counter Module, Catalog Number 1746-HSCE is an SLC 500 family compatible device except with the 1747-ASB Remote I/O Adapter Module. It can be used with SLC™ 5/02 (and above) processors. The module’s bidirectional counting ability allows it to detect movement in either direction. In addition, x2 and x4 counting modes are provided to fully use the capabilities of high-resolution quadrature encoders. High-speed inputs from quadrature encoders and various high-speed switches are supported. Accepting input pulse frequencies of up to 50k Hz allows precise control of fast motions. In addition, an Accumulated Counter, the module provides a Rate Counter to determine Rate Measurement by indicating the pulse input frequency in Hz. (See the block diagram on page 6.) The Rate Measurement is determined by accumulating input pulses over a fixed period of time. You set the Rate Period to best match your application requirements. Background Rate calculation is provided in Sequencer and Range Modes. This operation accepts input rates up to 32,767 Hz. The dynamically configurable Rate Period ranges from 10 ms to 2.55 seconds. The module’s four current sink (open collector) outputs can be controlled in the user program or the module. Control of the counter reset is configured through user-set parameters. The counter can be reset from any combination of the Z input, Limit Switch input, or Soft Reset control bits. Module operation is determined by selections made in the Setup and Control Word (M0:e.1). Setting the Function Control bit to 1 triggers the module to start the proper pulse counter, rate measurement, and output control functions. Many parameters are dynamic and can be changed without disrupting counter operation. The module’s block diagram is shown on page 6. Inputs from the terminal block enter the diagram at the left, outputs to the terminal block exit at the right. M0 and Output file parameters from the SLC enter the logic blocks from the top. Input file data to the SLC exit the logic blocks from the bottom.
Publication 1746-IN011C-EN-P - April 2005
Page 6
6
High-Speed Counter Module
Dip Switch and Jumper Locations Counter Input Parameters
Rate Period Parameters
Z LS LS Filter (JW1)
Input Logic
Rate Counter
Pulse and Direction
Operating Mode Logic
Reset Parameters
Reset Logic
Rate Counter Inputs
Reset Condition
Output Control Parameters
Rate Measurement
Rate
Operating Mode Outputs
Output Control Logic
4 Physical Outputs
Sequencer Pulse Counter Parameters
Output Status Inputs
Range Pulse Counter Reset Input Bit
Counter Input Parameters Input Type (M0:e.1/9–11) Up/Down Count Direction (M0:e.1/3) –d Reset Parameters Soft Reset bit (M0:e.1/4) –d Reset Mode (M0:e.1/5–7) Rate Period Parameters Rate Period (M0:e.9/0–7 or M0:e.16/0–7) –d
To Terminal Block
From Terminal Block
Operating Mode Parameters
A B
Accumulated Count Operating Mode Inputs
Pulse Counter Inputs
Pulse Counter Parameters Reset Value (M0:e.34 or M0:e.41) –d Maximum Count Value (M0:e.34 or M0:e.41) Counter Hold bit (M0:e.1/2) –d Counter Type bit (M0:e.1/13) Output Control Parameters Direct Outputs (O:e.0/0–7) –d Output Source Select (M0:e.0/0–7) –d Enable Outputs bit (M0:e.1/1) –d
Reset Input bit (I:e.0/12) Operating Mode Inputs Sequencer Inputs Current Sequencer Step (I:e.5/0–7) Next Sequencer Step (I:e.5/8–15) Sequence Done (I:e.0/6) Range inputs Ranges Active (I:e.6/0–11) Output Status Inputs (I:e.4/8–15)
Operating Mode Parameters Operating Mode (M0:e.1/14–15) Function Control Bit (M0:e.1/12) Range Definitions: Range Starting Values (M0:e.10 – 33) –d Range Ending Values (M0:e.10 – 33) –d Range Outputs (M0:e.3 – 8) –d Valid Ranges (M0:e.2) –d Sequencer Definitions: Valid Steps (M0:e.2 and M0:e.3/0–7) –d Step Presets (M0:e.17 – 40) –d Step Outputs (M0:e.4 – 15) –d Initial Outputs (M0:e.3/8–15) –d Sequencer Reset (M0:e.1/0) –d
Rate Counter Inputs Rate Valid (I:e.0/3) Rate Counter Overflow (I:e.0/4) Rate Measurement Overflow (I:e.0/5) Zero Rate Period Count (I:e.0/2) Rate Period Count (I:e.2) Rate Measurement (I:e.3)
Error Inputs Critical Error (I:e.0/10) Configuration Error bit (I:e.0/11) Configuration Error Code (I:e.4/0–7)
Pulse Counter Inputs Accumulated Count (I:e.1) Overflow/Underflow (I:e.0/13) Pulse Counter State (I:e.0/14–15)
–d indicates a dynamic parameter
Two dip switches (SW1 and SW2) and one jumper (JW1) are located on the side of the module. • SW1 selects the type of input (single ended or differential). • SW2 selects the output voltage range (4.5 to 10V dc or 10 to 30V dc). • JW1 selects the filtering rate (300 µs or 10 ms) used to debounce the limit switch input.
Publication 1746-IN011C-EN-P - April 2005
Page 7
High-Speed Counter Module
7
Default settings are shown below:
O N
1 234
SW 2
SW 2 JW 1
JW 1
SW2 Default 10 to 30V dc
3 JW1
1 JW1 Default 10 ms filter O N
1234
SW 1
SW1 Default Single-ended
ATTENTION
Use a small screwdriver to change dip switch positions. Graphite from pencils will damage the switch.
Publication 1746-IN011C-EN-P - April 2005
Page 8
8
High-Speed Counter Module
SW2 Settings Select an output voltage range that coincides with your supply voltage. The selections are 4.5 to 10V dc or 10 to 30V dc.
ON OFF
1234 10 to 30V dc
ON
1234
OFF
4.5 to 10V dc
Switch
1
2
3
4
Output
0
1
2
3
All switches of SW2 must be ON or all switches must be OFF. Permanent damage may result if some are ON and some are OFF.
ATTENTION
Operating in the 10 to 30V dc range with the switches set for the 4.5 to 10V dc range damages the module.
SW1 Settings Select a single-ended or differential input connection. ON
1234
OFF
Dip switch SW1
Position
Switch
1
2
3
4
Channel
A
B
Z not used
Input Connection
Input ON Range
ON differential
2.8 to 4.5V dc
OFF single-ended
3.1 to 5.5V dc
You can configure different inputs in different modes. For example, input A (CHA) can be configured as differential and input Z (CHZ) can be configured as single-ended.
Publication 1746-IN011C-EN-P - April 2005