Page 9
High-Speed Counter Module
9
JW1 Settings Select 300 µs or 10 ms filtering to debounce the limit switch input. Position the jumper as follows:
321
32 1 JW 1
JW 1 10 ms filter
300 µs filter
The LS input allows you to make a direct connection to nominal voltage levels of 5, 12, or 24V dc. The ON voltage ranges are as follows: Wiring Terminal
ON Range
LS (24V dc)
16.5 to 30V dc
LS (12V dc)
9.4 to 16.5V dc
LS (5V dc)
3.8 to 5.5V dc
See page 19 for limit switch wiring instructions. ATTENTION
Connect only one LS input range at a time, or the module will be damaged.
Publication 1746-IN011C-EN-P - April 2005
Page 10
10
High-Speed Counter Module
Install the Module Installation procedures for this module are the same as for any other discrete I/O or specialty module. IMPORTANT
Set the dip switches before installing the module.
ATTENTION
Disconnect power before attempting to install, remove, or wire the module. Make sure your SLC power supply has adequate reserve current capacity. The module requires 320 mA at 5V dc.
Top and Bottom Module Release(s)
Card Guide
1. Align the full-size circuit board with the chassis card guide. The first slot of the first chassis is reserved for the CPU. 2. Slide the module into the chassis until the top and bottom latches are latched. Make sure the removable terminal wiring block is attached to the module and all wires are connected to the terminal block. 3. Insert the cable tie in the slots and secure the cable. 4. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2. Publication 1746-IN011C-EN-P - April 2005
Page 11
High-Speed Counter Module
11
Remove the Terminal Block The removable terminal wiring block eliminates the need to rewire a module if it is removed from the chassis. Each terminal accepts two #14 AWG wires.
ATTENTION
Disconnect power before attempting to install, remove, or wire the removable terminal wiring block. To avoid cracking the removable terminal block, alternate the removal of the slotted terminal block release screws.
Remove the terminal block by turning the slotted terminal block release screws counterclockwise. The screws are attached to the terminal block, so it will follow as the screws are turned out.
Wire the Removable Terminal Block Use a flat or cross slot screwdriver to tighten terminal screws. Each screw should be turned tight enough to immobilize the wire’s end. Overtightening can strip the terminal screw. Do not exceed 0.7 to 0.9 Nm (6 to 8 in-lbs.).
Publication 1746-IN011C-EN-P - April 2005
Page 12
12
High-Speed Counter Module
Important Wiring Considerations Use the following guidelines when planning the system wiring for the module: • Install the SLC 500 system in a NEMA-rated enclosure. • Disconnect power to the SLC processor and the module before wiring. • Make sure the SLC 500 system is properly grounded. • Group this module and low-voltage DC modules away from AC I/O or high-voltage DC modules. • Shielded cable is required for high-speed input signals A, B, and Z. We recommend Belden 9503 or equivalent for lengths up to 305 m (1000 ft). • When the LS input is driven by an electromechanical device, route the wiring away from other inputs. In addition, JW1 should be set for the 10 ms filter. • When the LS input is driven by a solid-state device, use a shielded cable. You do not have to route the cable away from other inputs. • Shields should be grounded only at the end of the signal source end of the cable. Ground the shield to the case of the signal source, so energy coupled to the shield will not be delivered to signal source’s electronics.
Publication 1746-IN011C-EN-P - April 2005
Page 13
High-Speed Counter Module
13
Input and Output Connections Input and output wiring terminals are located on the front of the module, behind the terminal cover. When you connect input and output devices, you must also be concerned with the settings of dip switch SW1 (input connections), dip switch SW2 (output connections), and jumper JW1 (limit switch input connections). The location and description of these are shown on pages 6 through 9.
OUTPUT
0 1 2 3
Upper Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)
Discrete Output Wiring NOTE: V dc must be externally supplied by the user. See page 14 for output wiring.
Terminal Wiring max. 2 wires per terminal max. torque: 0.9 Nm (8 in-lbs) Limit Switch and Encoder Input Wiring See pages 15 through 19 for input wiring.
VDC OUT 0 OUT 1 OUT 2 OUT 3 DC COM A+ B+ ABNot used Not used Z+ LS (24 VDC ) ZLS (12 VDC ) LS COM LS (5 VDC )
INPUT
4 5 6 7
A B
Z LS FAULT
HSCE
VDC OUT 0 OUT 1 OUT 2 OUT 3 A+
DC COM B+
ANot Used Z+ ZLS COM
BNot Used LS (24V dc) LS (12V dc) LS (5V dc)
Lower Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)
Publication 1746-IN011C-EN-P - April 2005
Page 14
14
High-Speed Counter Module
Outputs The module features four physical outputs. They can be controlled by the module when certain counter conditions are met, or they can be controlled from the user program (refer to the High-Speed Counter Module User Manual, publication 1746-6.5 for M0:e.0 information). The outputs are bipolar transistors connected in a sinking (open collector sinking) configuration. When the output is energized, it sinks the current.
Do not use incandescent lamps as output indicators. The high peak inrush current required to heat the filament can damage the module’s output circuits. Use LED indicators that satisfy the output circuit ratings, such as Allen-Bradley 800A and 800T LED indicators.
ATTENTION
You can select an output voltage range of 4.5 to 10V dc or 10 to 30V dc. Refer to page 21 for the maximum current specifications for each voltage range. Dip switch SW2, located on the PC board, is used to select the voltage range. See pages 6 and 8 for switch SW2 location and settings. The figure below indicates wiring connections for four 24V dc outputs. All switches of SW2 are OFF for this output voltage.
VDC OUT 0 User Supplied 24V dc
+
OUT 1
-
OUT 2
All switches OFF ON
OUT 3 DC COM
1 234
OFF Dip Switch SW2 wiring terminals HSCE module
The outputs are not electrically isolated from each other. (They are referenced to the same output common terminal.) However, outputs are isolated from the rest of the circuitry to a level of 1500 volts.
Publication 1746-IN011C-EN-P - April 2005
Page 15
High-Speed Counter Module
15
Encoders The wiring diagrams on the following pages are provided to support the Allen-Bradley encoders you may already have. Differential encoders provide the best immunity to electrical noise.
Differential Encoder Wiring cable (1)
+ V DC COM
VS GND Belden 9503 or equivalent 305m (1000ft) max length
Allen-Bradley 845H Series differential encoder
A
A(+)
A
A(-)
B
B(+)
B
B(-)
Z
Z(+)
Z
Z(-)
Power Supply
Shield(2) SW1 encoder connector Earth
ON 1 2 3 4 OFF
(all switches Module Inputs
(1) Refer to your encoder manual for proper cable type and length. (2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity to EMI interference. Connect EARTH ground directly to the encoder connector housing.
Differential Encoder Output Waveforms The illustration below shows the different encoder output waveforms. If your encoder matches these waveforms, the encoder signals can be directly connected to the associated screw terminals on the module. For example, the A lead from the encoder is connected to the module’s A+ screw. If your encoder does not match these waveforms, some wiring modifications may be necessary. Refer to the High-Speed Counter Module User Manual, publication 1746-6.5 for a description of these modifications. A A B B Z Z
Publication 1746-IN011C-EN-P - April 2005
Page 16
16
High-Speed Counter Module
Single-Ended Encoder Wiring (Open Collector) cable(1)
VS GND
+ VDC COM
Power Supply
(3)
R
Allen-Bradley 845H Series single-ended encoder
Shield(2)
A
A(+) A(-)
B
B(+) B(-) Z(+) Z(-)
Z
Belden 9503 or equivalent 305m (1000tft) max length encoder connector housing
ON SW1
1 234
OFF (All switches OFF) Module Inputs
Earth (1) Refer to your encoder manual for proper cable type and length.
(2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity to EMI interference. Connect EARTH ground directly to the encoder connector housing. (3) The pullup resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical power supply values. These resistors must be located at the encoder end of the cable.
VS Value
R Value
Maximum Output Leakage
+5V dc
150 ohm 1/4W 5%
6.3 mA
+12V dc
1800 ohm 1/4W 5%
1.5 mA
+24V dc
4700 ohm 1/4W 5%
1.2 mA
Single-Ended Encoder Output Waveforms The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is ON. A low = transistor ON high = transistor OFF
B Z
Publication 1746-IN011C-EN-P - April 2005