Page 17
High-Speed Counter Module
17
Single-Ended Encoder Wiring (Sourcing) cable(1)
VS
+ VDC COM
GND
Power Supply
Belden 9503 or equivalent 305m (1000tft) max length
A(+)
A
R (3) A(-) B(+) R (3) B(-) Z(+) R (3) Z(-)
B single ended encoder(4)
Z Shield(2)
SW1
ON 1 2 34
OFF (All switches OFF) Earth
Module Inputs
(1) Refer to your encoder manual for proper cable type and length. (2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity (3) The resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical power supply values. These resistors must be located at the encoder end of the cable. (4) The Allen-Bradley 845H sourcing encoder is not compatible with this module.
VS Value
R Value
Maximum Output Leakage
+5V dc no resistor needed
100 µA
+12V dc
1800 ohm 1/4W 5%
100 µA
+24V dc
4700 ohm 1/4W 5%
100 µA
Single-Ended Encoder Output Waveforms (Sourcing) The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is OFF. low = transistor OFF high = transistor ON
A B Z
Publication 1746-IN011C-EN-P - April 2005
Page 18
18
High-Speed Counter Module
Single-Ended Wiring (Discrete Devices) +VDC COM proximity sensor with sourcing output
VS OUT COM
R1
A(+) A(-)
solid-state switch (5V output)
VS OUT CO M
Power Supply
R2 photoelectric sensor with open collector sinking output
VS OUT CO M
B(+) B(-) Z(+) Z(-)
ON 1 2 34 SW1 OFF (All switches OFF) Module Inputs
IMPORTANT
• This diagram shows the sensors operation from a common power supply. Separate power supplies for each circuit can be used. • The resistor (R1) value depends on the power supply value (VS). The table on page 17 provides the resistor values for typical power supply values. These resistors must be located at the module end of the cable. • The pull-up resistor (R2) value depends on the power supply value (VS). The table on page 16 provides the resistor values for typical power supply values. These resistors must be located at the sensor end of the cable.
Publication 1746-IN011C-EN-P - April 2005
Page 19
High-Speed Counter Module
19
Limit Switch Wiring Connect only one LS input range at a time, or the module will be damaged.
ATTENTION
24V dc Hard Contact Hard Contact Limit Switch LS (24V dc) VS 24V dc
HSCE module
LS (12V dc) LS (5V dc)
+ -
COM
LS COM Do not connect LS (5V dc) or LS (12V dc) Terminals
321 Jumper placed for 10 ms filtering
JW1
12V dc Hard Contact HSCE module Hard Contact Limit Switch VS 12V dc
+
LS (24V dc) LS (12V dc) LS (5V dc)
-
LS COM
COM
Do not connect LS (5V dc) or LS (12V dc) Terminals
321 JW1
Jumper placed for 10 ms filtering
5V dc Solid State Solid State Limit Switch HSCE module VS VS
+
5V dc COM
-
COM LS (24V dc) OUT LS (12V dc) LS (5V dc) LS COM
Do not connect LS (12V dc) or LS (24V dc) Terminals
Jumper placed for 300 µs filtering
321
JW1
Publication 1746-IN011C-EN-P - April 2005
Page 20
20
High-Speed Counter Module
Specifications General Description
Specification
Operating Temperature
0° C to +60° C (+32° F to +140° F)
Storage Temperature
-40° C to +85° C (-40° F to +185° F)
Humidity
5 to 95% without condensation
Backplane Current Consumption (power supply loading)
320 mA at +5V dc 0 mA at +24V dc
Maximum Cable Length(1)
305 m (1000 ft)
Agency Certification (when product or packaging is marked)
• •
CSA certified CSA Class I, Division 2 Groups A, B, C, D
• •
UL® listed CE marked for all applicable directives
(1)
Belden 9503 or equivalent
Inputs A, B, and Z Differential (Switch 1 on)
Single Ended (Switch 1 off)
Input Voltage
±5V dc
0 to 5V dc(2)
On-State Voltage
2.8 to 4.5V dc
3.1 to 5.5V dc
Off-State Voltage
-5.5 to 0.8V dc
0 to 0.8V dc
Max Off-State Leakage Current
100 µA
600 µA
Input Current (mA)
2.5 mA at 2.8V dc 7.5 mA at 4.5V dc
2.5 mA at 3.1V dc 7.5 mA at 5.5V dc
Nominal Input Impedance
700Ω
825Ω
Min. Pulse Width
10 µs
Min. Phase Separation(1)
4.5 µs
Max. Input Frequency Sequencer and Range Rate
50k Hz 32.767k Hz
Isolation (from backplane)
1500 volts
(1)
12 and 24 volts must be used with a pull-up resistor.
(2)
Channel A to channel B.
Publication 1746-IN011C-EN-P - April 2005
Page 21
High-Speed Counter Module
21
Limit Switch Input 5V dc
12V dc
24V dc
On-State Voltage
3.8 to 5.4V dc
9.4 to 16.5V dc
16.5 to 30V dc
Off-State Voltage
0 to 1.2V dc
0 to 2.4V dc
0 to 3.9V dc
Input Current minimum nominal maximum
4.6 mA 6.8 mA 9.2 mA
Max. Off-State Leakage Current
1 mA (all ranges)
Isolation (from backplane)
1500 volts
Outputs (Open Collector, Sinking) 4.5 to 10V dc (Switch 2 on)
10 to 30V dc (Switch 2 off)
Max. On-State Output Current
16 mA at 4.5V dc 40 mA at 10V dc
40 mA at 10V dc 125 mA at 30V dc
Max. On-State Voltage Drop
0.4V dc
1.0V dc
Max. Off-State Leakage Current
100 µA
Isolation (from backplane)
1500 volts
Publication 1746-IN011C-EN-P - April 2005
Page 22
22
High-Speed Counter Module
Publication 1746-IN011C-EN-P - April 2005
Page 23
High-Speed Counter Module
23
Publication 1746-IN011C-EN-P - April 2005
Page 24
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running. United States
1.440.646.3223 Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned. United States
Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for return procedure.