The text of a manual · part 1 of 3

Discrete I/O Modules (Catalog Number 1746 Series) Installation Instructions, pages 1 to 8

Pages 1 to 8 of 24

The original document is the PDF (657 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1746-IA8

Page 1

MANUFACTURER DATA SHEET

Discrete I/O

Manufacturer:

Allen-Bradley/Rockwell Model Number:

1746 Series See www.geomartin.com for additional PDF datasheets

Martin Part Number:

VendorPartNumber:

E-014624-02 AB # 1746-IA8, AC Input, 8 Point E-014624-03 AB # 1746-IOA16, AC Output, 16 Point

PDF File: Doc_000003_Cover.pdf

Page 2

This page is intentionally left blank

Page 3

Discrete I/O Modules (Catalog Number 1746 Series)

Installation Instructions Input Module Catalog Numbers: 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IC16, -IG16, -IH16, -IM4, -IM8, -IM16, -IN16, -ITB16, -ITV16, -IV8, -IV16 Output Module Catalog Numbers: 1746-OA8, -OA16, -OAP12, -OB8, -OB6EI, -OB16, -OB16E, -OBP8, -OBP16, -OG16, -OV8, -OV16, -OVP16, -OW4, -OW8, OW16, -OX8 Combination Input/Output Module Catalog Numbers: 1746-IO4, -IO8, -IO12, -IO12DC Publication 1746-IN005A-US-P

Page 4

2

Discrete I/O Modules

Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, AllenBradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley Company, Inc., is prohibited. Throughout these installation instructions we use notes to make you aware of safety considerations:

!

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.

Attention statements help you to: • identify a hazard • avoid the hazard • recognize the consequences IMPORTANT: Identifies information that is critical for successful application and understanding of the product.

Publication 1746-IN005A-US-P

Page 5

This page is intentionally left blank

Page 6

38

Discrete I/O Modules

Recovery From Blown Fuse/Processor Fault/Processor Shutdown Processor operation will stop under the following conditions: • The output module fuse blows due to a short circuit. • JP1 is set to the Processor Faults position (pins 2 and 3 connected). If the above conditions occur, the following procedures should be used for recovery: 1. Follow fuse replacement procedures shown on page 39. 2. Clear the processor major fault bit S:1/13. 3. Clear processor status file S:6 major error code (optional). 4. Return processor to Run Mode. For additional information on processor fault codes and clearing processor fault bits, refer to the following user manuals: • Your programming device’s reference manual • HHT User Manual, publication 1747-NP002 Chapter 28, Troubleshooting Fault Chapter 29, Understanding the Fault Routine

Replacement Fuse Recommendations Use the following replacement fuses • 1746-OBP16/-OVP16 -Littelfuse #322010,10A. This fuse is required to maintain UL/CSA rating. Replacement Fuse Kit is catalog number 1746-F8. (5 fuses per kit). • 1746-OAP12 -Use SAN-O HQ 6.3A for replacement. This fuse is required to maintain UL/CSA rating. Replacement Fuse Kit is catalog number 1746-F9 (5 fuses per kit).

Publication 1746-IN005A-US-P

Page 7

Discrete I/O Modules

39

Fuse Replacement Procedure To replace a blown fuse:

!

ATTENTION: Never install, remove, or wire modules with power applied to chassis.

1. Remove SLC 500 system power and correct the conditions causing the short circuit. 2. Remove the output module from the chassis. 3. Remove the fuse. • 1746-OBP16/-OVP16: Use a wide tipped, slotted head screw driver to remove the blown fuse. Slide the screw driver tip under the fuse and use a twisting motion to pry the fuse from the fuse clip. Use care so that the printed circuit board and surrounding electronics are not damaged. • 1746-OAP12: A fuse holder is provided with each fuse. Simply grasp the fuse holder with needle-nose pliers, or your fingers, and pull it out. 4. Replace the fuse. • 1746-OBP16/OVP16: Center the replacement fuse over the fuse clip and press down. If a tool is used to press the fuse in place, apply pressure to the metal end caps only, not the center of the fuse. • 1746-OAP12: Insert a new fuse into the fuse holder, align fuse holder on fuse clips and press down. 5. Replace the output module in the chassis. 6. Restore SLC 500 system power. Clear processor fault bits as indicated in the steps provided on page 38.

Publication 1746-IN005A-US-P

Page 8

40

Discrete I/O Modules

Electronically Protected Modules (1746-OB6EI and OB16E) Electronic Protection The electronic protection of the 1746-OB6EI and -OB16E has been designed to provide protection for the modules from short circuit and overload current conditions. The protection is based on a thermal cut-out principle. In the event of a short circuit or overload current condition on an output channel, that channel will limit current within milliseconds after its thermal cut-out temperature has been reached. All other channels continue to operate as directed by the CPU (processor) module. IMPORTANT: The modules do not provide protection against reverse polarity wiring or wiring to AC power sources. Electronic protection is not intended to replace fuses, circuit breakers, or other code-required wiring protection devices.

OUTPUT OUTPUT EE FF UU SS EE

Front View

Publication 1746-IN005A-US-P

EFUSE LED

Note: There is no jumper setting on this module