Page 9
Discrete I/O Modules
41
Auto Reset Operation IMPORTANT: The 1746-OB6EI and -OB16E perform auto-reset under overload conditions. When an output channel overload occurs as described on page 40, that channel will limit current within milliseconds after its thermal cut-out temperature has been reached. While in current limit, the output channel can cool below the thermal cutout temperature allowing the module to auto-reset and resume control of the output channel as directed by the processor until the thermal cut-out temperature is again reached. Removing power from an overloaded output channel would also allow the output channel to cool below the thermal cut-out temperature, allowing auto-reset to occur when power is restored. The output channel would operate as directed by the processor until the thermal cut-out temperature is again reached. To avoid auto-reset of an output channel under overload conditions, an external mechanical fuse can be used to open the circuit when overloaded.
Short Circuit/Overload Current Diagnostics If a short circuit or overload current condition occurs on an output channel: 1. The E-Fuse LED will illuminate provided that power is applied to the module. Power required: 5V dc via backplane and load power via an external supply. 2. All other channels continue to operate as directed by the CPU (processor) module.
Recovery From Channel Shutdown 1. Remove the SLC 500 system power and correct the conditions causing the short circuit or overload current condition. 2. Restore the SLC 500 system power. The module automatically resets and resumes control of the output channel and associated load.
Publication 1746-IN005A-US-P
Page 10
42
Discrete I/O Modules
Wiring Diagrams The wiring diagrams in these installation instructions are examples only. It is not necessary to connect an I/O device to each and every I/O module terminal.
Labeling for SLC/PLC® Systems In this document, 16-point I/O module wiring diagrams include both decimal and octal numbers for I/O addressing and wire identification (see figure below). To wire your 16-point I/O module when used in a SLC system, use the decimal numbers in the upper left portion of each box. When used in a PLC system, use the octal numbers in the lower right portion of the box. As shipped from the factory, the I/O module has a decimal address label on the inside of its door. An octal label kit should be included with your 16-point I/O modules, or a separate octal conversion kit can be ordered, to allow you to convert your module to the octal system. IMPORTANT: Ensure the octal labels are used with your PLC system. Directions on how to install the labels are included with the kit and on page 30 of this document. Figure 6:Decimal and Octal Labeling for 16-Point I/O Modules
L1
1746-IA16 100/120V ac IN 0
For SLC (decimal)
0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
IN 14
5
IN 6
100/120V ac
16
6
IN 7
10
IN 9
12
IN 11
7
IN 8
11
IN 10
13
IN 12
For PLC (octal)
14
IN 13 15
IN 14 16 IN 15
L2
17 AC COM AC COM
COMMONS CONNECTED INTERNALLY
Publication 1746-IN005A-US-P
SLC PLC
Page 11
Discrete I/O Modules
43
Input Modules - ac Figure 7:Wiring Diagrams (1746-IA4, -IA8, -IA16) 1746-IA8 100/120V ac
1746-IA4 100/120V ac
L1
NOT USED
IN 1
NOT USED
IN 2
NOT USED
L1
IN 0
NOT USED
IN 3
100/120V ac
IN 0
IN 4
IN 1
IN 5
100/120V ac
IN 2
IN 6
IN 3
IN 7
L2
AC COM
AC COM
L2 COMMONS CONNECTED INTERNALLY
AC COM
1746-IA16 100/120V ac
L1 IN 0 0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
5
IN 6
100/120V ac
6
IN 7
10
IN 9
7
IN 8
11
IN 10 12
IN 11
14
IN 13
13
IN 12 IN 14
15 16 IN 15
L2
17 AC COM AC COM
COMMONS CONNECTED INTERNALLY
SLC PLC
Publication 1746-IN005A-US-P
Page 12
44
Discrete I/O Modules
Figure 8:Wiring Diagrams (1746-IM4, -IM8, -IM16) 1746IM4 200/240V ac
1746-IM8 200/240V ac
L1
NOT USED
IN 0
NOT USED
IN 1
NOT USED
IN 2
NOT USED
L1
IN 3
200/240V ac
IN 0
IN 4
IN 1
200/240V ac
IN 5
IN 2
IN 6
IN 3
L2
IN 7
L2
AC COM
AC COM
COMMONS CONNECTED INTERNALLY
1746-IM16 200/240V ac
L1 IN 0 0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
200/240V ac
5
IN 6 6
IN 7
10
IN 9
7
IN 8
11
IN 10 12
IN 11
14
IN 13
13
IN 12
15
IN 14 16 IN 15
L2
17 AC COM AC COM
COMMONS CONNECTED INTERNALLY
Publication 1746-IN005A-US-P
SLC PLC
AC COM
Page 13
Discrete I/O Modules
45
Input Modules - dc Figure 9:Wiring Diagram (1746-IN16) 1746-IN16 24V ac/dc SINKING
L1 or +DC IN 0 0
IN 1
2
IN 3
1
IN 2
3
IN 4 4 IN 6
V ac/dc
IN 5 5
6 IN 7 7
IN 8 10 IN 9
11
IN 10 12 IN 11
13
IN 12 14 IN 13 IN 14
15
16 IN 15 17 AC/DC COM AC/DC COM
L2 or -DC
COMMONS CONNECTED INTERNALLY
SLC PLC
Figure 10:Wiring Diagram (1746-IB8, -IB16, -ITB16, -IC16, -IH16) 1746-IB8 24V dc SINKING
1746-IB16, -ITB16 24V dc SINKING
1746-IC16 1746-IH16 48V dc SINKING 125V dc SINKING
+DC +DC
IN 0
IN 0
IN 1
IN 2
IN 2 IN 3
24V dc
24V dc (IB16, ITB16) 48V dc (IC16)
IN 4 IN 5
COMMONS CONNECTED
1 2 IN 3 3
IN 4
4 IN 5
5 6 IN 7 7 6 10 IN 9 11 IN 10 IN 6
IN 8
125V dc (IH16)
12 IN 11
IN 6
IN 12
IN 7
IN 14
DC COM
±DC
0 IN 1
±DC
13
14 IN 13 15 16 IN 15
DC COM
17 DC COM
DC COM
COMMONS CONNECTED
SLC PLC
Publication 1746-IN005A-US-P
Page 14
46
Discrete I/O Modules
Figure 11:Wiring Diagram (1746-IV8, -IV16, -ITV16) 1746-IV8 24V dc SOURCING
1746-IV16, -ITV16 24V dc SOURCING
±DC ±DC
IN 0
IN 0
3
6
IN 7
10
IN 9
24V dc
IN 5
IN 10
IN 6
IN 12
11 12 IN 11 13 14 IN 13
IN 14
+DC
VDC
5 7
IN 8
IN 4
15 16 IN 15
17
VDC VDC
VDC CONNECTED INTERNALLY
VDC VDC CONNECTED INTERNALLY
Figure 12:Wiring Diagram (1746-IG16) 1746-IG16 TTL INPUT (Low = True) +5 DC
IN 0 0
IN 1 1
IN 2
3
IN 4
5
IN 6
7
IN 8
2
IN 3
4
IN 5
6
IN 7
+5V dc
1
4 IN 5
IN 7
+DC
IN 3
IN 6
IN 3
+DC
IN 1
2
IN 4
IN 2
24V dc
0 IN 2
IN 1
10 IN 9 11 IN 10 12 IN 11 13 IN 12 IN 13 14 15 IN 14 IN 15 16 17 DC COM
±DC SLC PLC
Publication 1746-IN005A-US-P
SLC PLC
Page 15
Discrete I/O Modules
47
Output Modules - ac Figure 13:Wiring Diagrams (1746-OA8, -OA16) 1746-OA8 100 to 240V ac TRIAC OUTPUT
L1
VAC 1 OUT 0
100-240V ac
OUT 1 CR
OUT 2
L2
CR
OUT 3
L1
VAC 2 OUT 4
100-240V ac
OUT 5 OUT 6
CR
OUT 7
CR
L2
1746-OA16 100 to 240V ac TRIAC OUTPUT
L1
VAC 1
OUT0 0
OUT 1 1 OUT 2
2
OUT 3
100-240V ac
3 OUT 4
CR
CR
4
OUT 5 CR
5 OUT 6 CR
6
OUT 7 7
L2 L1
VAC 2 OUT 9
11 OUT 8 10
OUT 11 13 OUT 10 CR CR
15 OUT 12 14
OUT 15 17 OUT 14
16
SLC PLC
100-240V ac
12
OUT 13
CR CR
L2
Publication 1746-IN005A-US-P
Page 16
48
Discrete I/O Modules
Figure 14:Wiring Diagram (1746-OAP12) 1746-OAP12 100 to 240V ac HIGH CURRENT TRIAC OUTPUT COMMONS CONNECTED INTERNALLY
VAC 1
L1
VAC 1
OUT 1 1 CR
100-240V ac
CR
OUT 3 OUT 5
OUT 0 0
3 OUT 2 5 OUT 4
NOT USED
2 4
CR
NOT USED
L2 L2 OUT 7 CR CR
7 OUT 6 6 11 OUT 8 10 OUT 11 13 OUT 10 12 VAC 2 VAC 2
OUT 9
100-240V ac CR
L1
COMMONS CONNECTED INTERNALLY
SLC PLC
Output Modules - dc Figure 15:Wiring Diagrams (1746-OB6EI) 1746-OB6EI 10-30V dc TRANSISTOR OUTPUT-SOURCING CHANNEL-TO-CHANNEL ISOLATED VDC 1
+DC 10-30V dc
CR
-DC
DC COM 1
+DC
VDC 3
10-30V dc
CR
DC COM 3
+DC
VDC 5
-DC
CR
+DC
OUT 0
10-30V dc
DC COM 0
-DC
VDC 2
+DC
OUT 2
10-30V dc
DC COM 2
-DC
VDC 4
+DC
OUT 4
10-30V dc
DC COM 4
-DC
OUT 3
-DC
10-30V dc
VDC 0 OUT 1
OUT 5 DC COM 5
Publication 1746-IN005A-US-P