For the Allen-Bradley 1746-NI4
Page 1
Installation Instructions
SLC™ 500 4-Channel Analog I/O Modules
(Catalog Numbers 1746-NI4, -NIO4I, -NIO4V, -NO4I, -NO4V, -FIO4I, and -FIO4V)
Inside… ........................................................................................... page Important User Information ...................................................................... 2 For More Information ............................................................................. 3 Types of Analog Modules....................................................................... 4 Hazardous Location Considerations ....................................................... 7 Environnements dangereux .................................................................... 7 Choosing a Slot in the Chassis............................................................. 10 Installing Your Module ......................................................................... 11 Wiring Considerations.......................................................................... 12 Wiring the Analog Module................................................................... 14 Labeling and Installing the Terminal Block .......................................... 16 Minimizing Electrical Noise on Analog Modules................................. 17 Specifications ....................................................................................... 21
Publication 1746-IN008C-EN-P - May 2004
-
Page 2
2
SLC™ 500 4-Channel Analog I/O Modules
Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence
Publication 1746-IN008C-EN-P - May 2004
-
Page 3
SLC™ 500 4-Channel Analog I/O Modules
3
For More Information Related Publications For
Refer to this Document
Pub. No.
A more detailed description on how to configure the SLC 500 Analog I/O Modules.
SLC 500 Analog I/O Modules User Manual
1746-UM005
A more detailed description on how to install and integrate SLC 500 Fast Analog I/O Modules.
SLC 500 Fast Analog I/O Modules User Manual
1746-6.9
A more detailed description on how to install and use SLC 500 Modular Hardware Style your modular SLC 500 system. User Manual
1747-UM011
A reference manual that contains status file data, instruction set, and troubleshooting information.
1747-RM001
SLC 500 Instruction Set Reference Manual
If you would like a manual, you can: • download an electronic version from the internet: www.theautomationbookstore.com • order a printed manual by: – contacting your local distributor or Rockwell Automation representative – visiting www.theautomationbookstore.com and placing your order – calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574 (Outside USA/Canada)
Publication 1746-IN008C-EN-P - May 2004
-
Page 4
4
SLC™ 500 4-Channel Analog I/O Modules
Types of Analog Modules 1746-NI4 Analog Input Module The NI4 Analog Input module contains 4 analog input channels that are user selectable per channel for voltage or current to support a variety of monitoring and controlling applications.
1746-NO4I and NO4V Analog Output Modules The NO4I and NO4V Analog Output Modules provide 4 analog output channels. The NO4I module contains 4 current outputs. The NO4V module contains 4 voltage outputs. Both of these modules support a variety of control applications.
1746-NIO4I and NIO4V Analog Combination Modules The NIO4I and NIO4V Analog Combination I/O modules provide 2 input and 2 output channels in a single-slot module. The 1746-NIO4I module contains 2 current or voltage inputs (user selectable per channel) and 2 current outputs. The 1746-NIO4V module contains 2 current or voltage inputs (user selectable per channel) and 2 voltage outputs.
1746-FIO4I and FIO4V Fast Analog Combination Modules The FIO4I and FIO4V Fast Analog Combination modules are 2-input/2-output combination modules ideal for high speed applications with more rapidly changing analog signals. These fast response modules are best suited for control of pressure and position in equipment such as hydraulic presses and molding machines.
Publication 1746-IN008C-EN-P - May 2004
-
Page 5
SLC™ 500 4-Channel Analog I/O Modules
5
Analog Modules Operation The module converts analog input signals to 16-bit binary values for storage in the SLC processor’s input image table. The decimal range, number of significant bits, and converter resolution depend on the input range that you use for the channel.
Analog Input A/D Characteristics
NI4, NIO4I, & NIO4V Input Range
Decimal Range (input image table)
Number of Significant Bits
Nominal Resolution
±10V dc -1 LSB
-32,768 to +32,767
16
305.176 µV/LSB
0 to 10V dc -1 LSB
0 to 32,767
15
0 to 5V dc
0 to 16,384
14
1 to 5V dc
3,277 to 16,384
13.67
±20 mA
±16,384
15
0 to 20 mA
0 to 16,384
14
4 to 20 mA
3,277 to 16,384
13.67
FIO4I and FIO4V Input Range
Decimal Range (input image table)
Number of Significant Bits
Nominal Resolution
0 to 10V dc -1 LSB
0 to 4095
12
2.4414 mV/LSB
0 to 5V dc
0 to 2047
11
1 to 5V dc
409 to 2047
10.67
0 to 20 mA
0 to 2047
11
4 to 20 mA
409 to 2047
10.67
1.22070 µA/LSB
9.7656 µA/LSB
Analog Output D/A Characteristics The analog modules have the same output characteristics. Module
Output Range
Decimal Range (output Significant Bits Resolution image table)
FIO4I
0 to 21 mA - 1 LSB
0 to 32,764
13 bits
0 to 20 mA
0 to 31,208
12.92 bits
4 to 20 mA
6,242 to 31,2089
12.6 bits
±10V dc - 1 LSB
-32,768 to +32,764
14 bits
0 to 10V dc -1 LSB
0 to 32,764
13 bits
0 to 5V dc
0 to 16,384
12 bits
1 to 5V dc
3,277 to 16,384
11.67 bits
NIO4I
2.56348 µA/LSB
NO4I FIO4V NIO4V NO4V
1.22070 mV/LSB
Publication 1746-IN008C-EN-P - May 2004
-
Page 6
6
SLC™ 500 4-Channel Analog I/O Modules
Analog Module Hardware Features The module contains a removable terminal block providing connection for the analog input and/or output channels, which is specifically designed to interface with analog current and voltage input signals. The channels can be wired as either single-ended or differential inputs. There are DIP switches on the circuit board for selecting voltage or current input.
Function Label
Power Status LED OUTPUT
INPUT
POWER
ANALOG
(1) IN 0+
Removable Terminal Block
(1) IN 0± (2) ANL COM
Door Label
(3) IN 1+ (4) IN 1± (5) ANL COM (6) NOT USED (7) OUT 0 (8) ANL COM (9) NOT USED
Door
(10) OUT 1 (11)ANL COM
Hardware Feature
Function
Function Label
Indicates input, output, or both.
Power Status LED
Indicates when backplane power is applied to the module.
Removable Terminal Block
Provides physical connection to input devices.
Door Label
Permits easy terminal identification.
Door
Protects terminal connections and label.
Publication 1746-IN008C-EN-P - May 2004
-
Page 7
SLC™ 500 4-Channel Analog I/O Modules
7
Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off. • Do not connect or disconnect components unless power has been switched off. • All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
DANGER D’EXPLOSION • La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe 1, Division 2. • Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée. • Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée.
Publication 1746-IN008C-EN-P - May 2004
-
Page 8
8
SLC™ 500 4-Channel Analog I/O Modules
Determining Your Power Requirements for a Modular Controller Analog modules require both 5V dc and 24V dc power from the backplane of the SLC 500 system. However, the NO4I and NO4V analog modules can use an external 24V dc power supply. This eliminates the 24V dc backplane power requirements, providing configuration flexibility if SLC power supply loading is critical. These two modules provide user-supplied external 24V dc power supply connections. The following table shows the power requirements for each analog module using backplane power. Use this table to calculate the total load on the modular system power supply. For more information refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011.
IMPORTANT
The analog modules do not supply loop power for the input device. You must supply the appropriate loop power for loop-powered input devices.
Catalog Number
5 Volt Current
24 Volt Current
1746-NI4
35 mA
85 mA
1746-NIO4I
55 mA
145 mA
1746-NIO4V
55 mA
115 mA
1746-NO4I
55 mA
195 mA(1) (2)
1746-NO4V
55 mA
145 mA(1) (2)
1746-FIO4I
55 mA
150 mA
1746-FIO4V
55 mA
120 mA
(1)
The 24V dc user power connection on a fixed SLC 500 can power an NO4I or NO4V analog module. However, the regulation of the 24V dc user connection on a modular SLC 500 power supply, catalog number 1746-P1, -P2, and -P4 is outside of the requirements of the NO4I and NO4V analog modules and cannot be used.
(2)
Omit these values from your SLC power supply loading calculations if you decide to use an external power supply.
Determining Your Power Requirements for a Fixed Controller
IMPORTANT
The 2-slot, SLC 500 fixed I/O expansion chassis (1746-A2) will support only specific combinations of modules. If you wish to use an I/O module in a 2-slot expansion chassis with another SLC I/O or communication module, refer to the SLC 500 Analog I/O Modules User Manual, publication 1746-UM005 for valid combinations of modules.
Publication 1746-IN008C-EN-P - May 2004
-
Page 9
SLC™ 500 4-Channel Analog I/O Modules
9
Configuring Your Module The NI4, NIO4I, NIO4V, FIO4I, and FIO4V analog modules have user-selectable DIP switch settings, which allow you to configure the input channels as either current or voltage inputs. The switches are located on the analog module board. The following illustration shows the ON and OFF switch settings. Switch orientation is also provided on the nameplate of the module.
ON - Configures channel for current input OFF - Configures channel for voltage input
ATTENTION
Care should be taken to avoid connecting a voltage source without a current transmitter, etc. to a channel configured for current input. Improper module operation or damage to the module can occur.
Switch Settings for the 1746-NI4 The NI4 has 4 individual DIP switches that control the input mode of channels 0 through 3. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input.
Current O N
1234
Voltage
Switch 1 = Channel 0 Switch 2 = Channel 1 Switch 3 = Channel 2 Switch 4 = Channel 3
Publication 1746-IN008C-EN-P - May 2004
-
Page 10
10
SLC™ 500 4-Channel Analog I/O Modules
Switch Settings for the 1746-NIO4I, -NIO4V, -FIO4I, and -FIO4V The NIO4I and NIO4V have 2 individual switches labeled 1 and 2. These switches control the input mode of channel 0 and 1. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input. Current O N
12
Switch 1 = Channel 0 Switch 2 = Channel 1
Voltage
External Power Switch for the 1746-NO4I and -NO4V The NO4I and NO4V analog output modules have an external 24V dc power switch, SW1, which gives you the option of using an external power supply. In the UP position, power is drawn from an external power source. In the DOWN position, power is drawn from the backplane of the module. The switch is located on the analog module board. Switch orientation is also provided on the nameplate of the module. External SW1
24V dc Power Selector Backplane
Choosing a Slot in the Chassis Two factors determine where the analog module should be located in the chassis: ambient temperature and electrical noise. Consider the following conditions when selecting a slot for an analog module. Position the module: • in a slot away from an ac or high voltage dc modules • in the chassis closest to the bottom of the enclosure where the SLC 500 system is installed • away from the chassis power supply if installed in a modular system
Publication 1746-IN008C-EN-P - May 2004
-