The text of a manual · part 2 of 3

SLC 500 4-Channel Analog I/O Modules Installation Instructions, pages 11 to 20

Pages 11 to 20 of 28

The original document is the PDF (920 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1746-NI4

Page 11

SLC™ 500 4-Channel Analog I/O Modules

11

Installing Your Module All modules are mounted in a single slot. Remember that in a modular system the processor always occupies the first slot of the first chassis. ATTENTION

Never install, remove, or wire modules with power applied to the chassis. Also, do not expose analog modules to surfaces or other areas that may typically hold an electrostatic charge. Electrostatic charges can destroy the analog circuitry.

IMPORTANT

The potentiometer sets the voltage during factory calibration to 2.5 volts. It is set and sealed at the factory and does not require any adjustments.

1. Verify that all switches are set correctly for the application.

ATTENTION

Care should be taken to avoid connecting a voltage source without a current transmitter, etc. to a channel configured for current input. Improper module operation or damage to the module can occur.

2. Align the circuit board of the analog module with the card guide of the chassis as shown on page 12. 3. Slide the module in until both top and bottom retaining clips are secured. 4. To remove the module, depress the retaining clips at the top and bottom of the module and slide the module out.

Publication 1746-IN008C-EN-P - May 2004

-

Page 12

12

SLC™ 500 4-Channel Analog I/O Modules

Top and Bottom Module Release (s)

Card Guide

Wiring Considerations The following section provides system wiring guidelines, how to ground your Belden™ cable, and how to determine the cable length.

ATTENTION

Before wiring any analog module, disconnect power from the SLC 500 system and from any other source to the analog module.

Publication 1746-IN008C-EN-P - May 2004

-

Page 13

SLC™ 500 4-Channel Analog I/O Modules

13

System Wiring Guidelines Use the following guidelines in planning the system wiring for the analog modules: • all analog common terminals (ANL COM) are electrically connected inside the module. ANL COM is not connected to earth ground inside the module. • voltages on IN+ and IN- terminals must remain within ± 20 Volts with respect to ANL COM to ensure proper input channel operation. This is true for current and voltage input channel operation. • voltage outputs (OUT 0 and OUT 1) of the NIO4V and NO4V are referenced to ANL COM. Load resistance (R1) for a voltage output channel must be greater than or equal to 1K ohms. • current output channels (OUT 0 and OUT 1) of the NIO4I and NO4I source current that returns to ANL COM. Load resistance (R1) for a current output channel must remain between 0 and 500 ohms. After the analog input module is properly installed in the chassis, follow the wiring procedure below using Belden 8761 cable.

ATTENTION

Care should be taken to avoid connecting a voltage source without a current transmitter, etc. to a channel configured for current input. Improper module operation or damage to the module can occur.

Grounding Your Cable Belden cable #8761 has two signal wires (black and clear), one drain wire and a foil shield. Refer to illustration on page 14 for Belden cable #8761. The drain wire and foil shield must be grounded at one end of the cable. Do not earth ground the drain wire and foil shield at both ends of the cable. Input Channel - Use a chassis mounting tab as a ground for the drain wire and foil shield. Output Channel - Ground the drain wire and foil shield at the analog load. IMPORTANT

If you cannot ground the output channel at the load, ground the drain wire and foil shield at the chassis mounting tab. Do not connect the foil shield or drain wire to the analog terminal block. They must be connected to an earth ground, which is not provided at the analog module.

Publication 1746-IN008C-EN-P - May 2004

-

Page 14

14

SLC™ 500 4-Channel Analog I/O Modules

Belden Cable #8761 Foil Shield Black Wire

Clear Wire

Drain Wire

Determining the Cable Length Determine the length of cable you will need to connect a channel to its input or output device. Remember to leave additional length to route the drain wire and foil shield for earth grounding.

Wiring the Analog Module After the analog module is properly installed in the chassis, use the following wiring procedure. Belden cable #8761 is recommended when wiring analog modules. This section assumes that you have properly installed the analog module.

ATTENTION

Before wiring any analog module, disconnect power from the SLC 500 system and from any other source to the analog module.

To wire your analog module, follow these steps and refer to the illustrations on page 15. 1. Designate the end of the cable where the drain wire and foil shield is earth grounded as END 1. Designate the other end as END 2. 2. At each end of the cable, strip some casing to expose the individual wires. 3. Trim the signal wires to 50 mm (2 inch) lengths. Strip 5 mm (about 3/16 inch) of insulation away to expose the end of the wire. Publication 1746-IN008C-EN-P - May 2004

-

Page 15

SLC™ 500 4-Channel Analog I/O Modules

15

4. At END 1, twist the drain wire and foil shield together, bend them away from the cable, and apply shrink wrap. 5. At END 2, cut the drain wire and foil shield back to the cable and apply shrink wrap. 6. Connect the signal wires (black and clear) to the terminal block and the input and output devices. The recommended maximum torque is 0.57 Nm (5 lb-in) for all terminals. • Input channels - connect END 1 at module. Use a chassis mounting tab as a ground for the drain wire and foil shield. • Output channel- connect END 2 at the module. Ground the drain wire and foil shield at the analog load. 7. Repeat steps 1 through 6 for each channel on the analog module. Jumper the unused plus (+), minus (-) and common terminals of each input channel individually. Unused output and common terminals should be left unconnected. The following illustrations depict the proper cable preparation for END 1 and END 2. Shrink wrap is applied to each cable end. Make sure the foil shield and drain wires on END 1 are long enough to reach their designated earth ground points. Cable Preparation END 1

Foil Shield and Drain Wire Black Wire

Insulation

Clear Wire Black Wire

Cable Preparation END 2

Insulation Clear Wire

Publication 1746-IN008C-EN-P - May 2004

-

Page 16

16

SLC™ 500 4-Channel Analog I/O Modules

Labeling and Installing the Terminal Block The terminal block has a write-on label. Labeling the terminal block will help ensure that it is installed on the correct module. When installing the analog module in a chassis, it is not necessary to remove the terminal block from the module. However, if the terminal block is removed, use the write–on label located on the side of the terminal block to identify the module location and type.

Terminal Block SLOT ____ RACK ____ MODULE _____

TIP

The black dot on the terminal block label indicates the position of terminal 0.

Once you have wired your analog module and properly labeled the terminal block, install the terminal block on the analog module. To install the terminal block: 1. Align the terminal block with the receptacle. 2. Insert the terminal block and press firmly at the top and bottom until it is properly secured. To remove the terminal block, grasp it on the top and bottom and pull outward and down.

Publication 1746-IN008C-EN-P - May 2004

-

Page 17

SLC™ 500 4-Channel Analog I/O Modules

17

Minimizing Electrical Noise on Analog Modules Inputs on analog modules employ digital high frequency filters that significantly reduce the effects of electrical noise on input signals. However, because of the variety of applications and environments where analog modules are installed and operating, it is impossible to ensure that all environmental noise will be removed by the input filters. Although it is not the purpose of this installation instruction to address SLC 500 system procedures, several specific steps can be taken to help reduce the effects of environmental noise on analog signals: • Install the SLC 500 system in a properly rated (i.e., NEMA) enclosure. Make sure that the SLC 500 system is properly grounded. • Use Belden cable #8761 for wiring the analog modules making sure that the drain wire and foil shield are properly earth grounded. • Route the Belden cable separate from any other wiring. Additional noise immunity can be obtained by routing the cables in grounded conduit. • Group analog and low voltage dc modules away from ac I/O or high voltage dc modules. A system may malfunction due to a change in the operating environment after a period of time. Periodically check system operation, particularly when new machinery or other noise sources are installed near the SLC 500 system. For further details on system installation and start-up refer to: • SLC 500 Modular Hardware Style User Manual, publication 1747-UM011 • SLC 500 Fixed Hardware Style User Manual, publication 1747-6.21 • Safety Guidelines for the Application, Installation Maintenance of Solid State Control, publication SGI-1.1.

Publication 1746-IN008C-EN-P - May 2004

-

Page 18

18

SLC™ 500 4-Channel Analog I/O Modules

Wiring Diagram (showing differential inputs) NI4

+ analog source

- earth ground

+ analog source

- earth ground Jumper unused inputs.

NIO4I, NIO4V, FIO4I, and FIO4V

0 1 2 3 4 5 6 7 8 9 10 11

IN 0+ IN 0ANL COM IN 1+ IN 1ANL COM

0 1 2 3 4 5 6 7 8 9 10 11

IN 0+ IN 0ANL COM IN 1+ IN 1ANL COM

0 1

+24V dc dc COM

0 1 2 3 4 5 6 7

OUT 0 ANL COM

IN 2+ IN 2ANL COM IN 3+ IN 3ANL COM

+ analog source

- earth ground

Jumper unused inputs.

LOAD earth ground

NO4I and NO4V

24V dc power supply if external power is selected. Cable length from external 24V dc power supply to analog module

Do not jumper unused

Ext. pwr sup.

LOAD earth ground LOAD Analog commons are internally connected in the module. Channels are not isolated from each other.

earth ground

Do not jumper unused outputs.

not used OUT 0 ANL COM not used OUT 1 ANL COM

OUT 1 ANL COM OUT 2 ANL COM OUT 3 ANL COM

Publication 1746-IN008C-EN-P - May 2004

-

Page 19

SLC™ 500 4-Channel Analog I/O Modules

ATTENTION

19

Any individual single-ended input device can be connected to any single differential input shown on page 18. The single-ended input common is connected to the negative differential input point.

Wiring Schematics for 2, 3, and 4-Wire Analog Input Devices

IMPORTANT

The module does not provide loop power for analog inputs. Use a power supply that matches the transmitter specifications.

2-Wire Transmitter Transmitter Power Supply

+ -

3-Wire Transmitter

+

-

Module IN + IN ANL COM

Transmitter Supply Signal GND

Power + Supply -

4-Wire Transmitter Power Supply

+ -

Transmitter Supply Signal

+ -

+ -

Module IN + IN ANL COM

Module IN + IN ANL COM

Publication 1746-IN008C-EN-P - May 2004

-

Page 20

20

SLC™ 500 4-Channel Analog I/O Modules

Wiring Schematic for Single-Ended Analog Input Connections When wiring single-ended analog input devices to the analog input card, the number of total wires necessary can be limited by using the ANALOG COMMON terminal. Note that differential inputs are more immune to noise than single-ended inputs.

Transmitter Power Supply

+ -

NI4

+ Signal

IN 0+ IN 0-

Transmitter

ANL COM

+ Signal

IN1+ IN 1-

Transmitter

ANL COM

+ Signal

IN 2+ IN 2-

Transmitter Supply

+

ANL COM Signal

Ground

IN 3+ IN 3ANL COM

Publication 1746-IN008C-EN-P - May 2004

-