SLC 500 4-Channel Analog I/O Modules Installation Instructions, pages 21 to 28

Pages 21 to 28 of 28

The original document is the PDF (920 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1746-NI4

Page 21

SLC™ 500 4-Channel Analog I/O Modules

21

Specifications General Specifications for NI4, NIO4I, NIO4V, NO4I, NO4V, FIO4I, FIO4V Description

Specification

SLC Communication Format

16-Bit Two’s Complement Binary

Field Wiring to Backplane Isolation

500V dc

Update Time

512 µs for all channels in parallel

Recommended Cable

Shielded Belden #8761

Maximum Wire Size

#14 AWG (maximum)

Terminal Block

Removable

Location

1746 chassis

Calibration

Factory Calibrated (1)

Noise Immunity

NEMA Standard ICS 2-230

Environmental Conditions Operating Temperature

0° to +60° C (+32° to +140° F)

Storage Temperature -40° to +85° C (-40° to +185° F) Relative Humidity

5 to 95% (non-condensing)

Agency Certification (when product or packaging is marked)

C-UL Listed Industrial Control Equipment Marked for all applicable directives Marked for all applicable acts N223

Functional Safety 1oo2D (AK 1 to 6, SIL 1 to 3, according to DIN V 19250 and IEC 61508 respectively) Category 1 to 4, according to EN954-1 (1)

For calibrating the 1746-FIO4I and 1746-FI04V analog modules, refer to the customer calibration program and procedure in the SLC 500 Fast Analog I/O Modules User Manual, publication number 1746-6.9.

Publication 1746-IN008C-EN-P - May 2004

-

Page 22

22

SLC™ 500 4-Channel Analog I/O Modules

Backplane Current Specification for NI4, NIO4I, NIO4V, NO4I, NO4V, FIo4I, and FIO4V Catalog 1746-

Input Channels per Output Module Channels per Module

Backplane Current Draw 5V (max.)

24V (max.)

External 24V dc Power Supply Tolerance

NI4

4 differential, NA voltage or current selectable per channel, not individually isolated

35 mA

85 mA

NA

NIO4I

2 differential, voltage or current selectable per channel, not individually isolated

2 current outputs, not individually isolated

55 mA

145 mA

NA

NIO4V

2 differential, voltage or current selectable per channel, not individually isolated

2 voltage outputs, not individually isolated

55 mA

115 mA

NA

NO4I

NA

4 current outputs, not individually isolated

55 mA

195 mA

24V dc ±10% at 195 mA max.

4 voltage outputs, not individually isolated

55 mA

NO4V

NA

(21.6 to 26.4V dc)(1) 145 mA

24V dc ±10% at 145 mA max. (21.6 to 26.4V dc)(1)

FIO4I

2 differential, select V or I per channel, not individually isolated

2 current outputs, not individually isolated

55 mA

150 mA

NA

FIO4V

2 differential, select V or I per channel, not individually isolated

2 voltage outputs, not individually isolated

55 mA

120 mA

NA

(1)

Required for some applications if sufficient power is not available from SLC power supply.

Publication 1746-IN008C-EN-P - May 2004

-

Page 23

SLC™ 500 4-Channel Analog I/O Modules

23

General Analog Input Specifications for NI4, NIO4I, NIO4V, FIO4I, and FIO4V Description

Specification NI4

NIO4I, NIO4V

FIO4I, FIO4V

Converter Resolution

16-Bit

Repeatability

±1 LSB

12-bit

Location of LSB in I/O image word

0000 0000 0000 0001

Non-linearity

0.01%

±0.073% of full scale max.

Common Mode Voltage Range

-20 to +20 volts

0 to +20 Volts (max)

Common Mode Rejection at 0 to 10 Hz (min.) 50 dB Common Mode Rejection at 60 Hz (min.)

105 dB

50 dB (min with 1K ohm imbalance)

Normal Mode Rejection at 60 Hz (min.)

55 dB

NA

Channel Bandwidth

10 Hz

7.0 kHz (min at 3dB point)

Step Response

60 ms at 95%

100 µsec

Conversion Method

Delta-Sigma Modulation

Successive approximation

Impedance to ANL COM

380K ohms

500K ohms

Impedance channel to channel

760K ohms(2)

1M ohms

(1)

(1)

The value listed is for Series B and greater. For series A, the impedance to ANL COM is 500K ohms.

(2)

The value listed is for Series B and greater. For Series A, the impedance channel to channel is 1M ohms.

Other Analog Input Specification for FIO4I, and FIO4V Descriptions

Specifications

Signal Convert from Hold

6.0 µsec (nominal)

Track and Hold Time to Acquire the Analog Signal Before Conversion

1.5 µsec (nominal)

Conversion Time

7.5 µsec every 512 msec (nominal)

Image Format (HEX)

OFF

Module Throughput Delay

1.10 ms (maximum(1)) 512 µsec (typical)

(1)

Worst case throughput occurs when the module just misses seeing an event occur.

Publication 1746-IN008C-EN-P - May 2004

-

Page 24

24

SLC™ 500 4-Channel Analog I/O Modules

Current-Loop Input Specifications for NI4, NIO4I, NIO4V, FIO4I, and FIO4V Description

Specification NI4, NIO4I, NIO4V

FIO4I, FIO4V

Input Range (Normal Operation)

-20 to +20 mA

0 to 20 mA (nominal)

Absolute Maximum Input Current

-30 to +30 mA

0 to 30 mA (maximum)

Absolute Maximum Input Voltage

±7.5V dc or 7.5V ac RMS

Current Input Coding -20 to +20 mA

-16,384 to +16,384

Input Impedance

250 Ohms

Resolution

1.22070 µA per LSB

Full Scale

20 mA

Overall Accuracy at +25° C (77°F) (max.)

±0.365% of full scale

0 to +2047 9.765 mA per bit ±0.510% of full scale

Overall Accuracy at 0° to +60°C (32° to 140° F) (max.)

±0.642% of full scale

Overall Accuracy Drift (max.)

+79ppm/5°C of full scale

±98 ppm/°C of full scale

Gain Error at +25° C (77° F) (max.)

+0.323%

±0.400% of full scale

Gain Error at 0° to +60°C (32° to 140°F) (max.)

±0.556%

±0.707% of full scale

Gain Error Drift (max.)

±67ppm/°C

±89 ppm/°C

Offset Error at +25° C (77°F) (max.) (lin = 0, Vcm = 0)

±7 LSB

±2 LSB

Offset Error at 0° to +60°C (32° to 140° F) (max.) (lin = 0, Vcm = 0)

±14 LSB

±4 LSB

Offset Error Drift (max.) (lin = 0, Vcm = 0)

±0.20 LSB/°C

±.14LSB/°C(2)

Overvoltage Protection

7.5V ac RMS (maximum)

(1)

±0.850% of full scale

(1)

For improved accuracy over temperature, see SLC 500 Analog I/O Modules User Manual, publication 1746-UM005.

(2)

See the SLC 500 Fast Analog I/O Modules User Manual, publication 1746-6.9.

Publication 1746-IN008C-EN-P - May 2004

-

Page 25

SLC™ 500 4-Channel Analog I/O Modules

25

Voltage Input Specifications for NI4, NIO4I, NIO4V, FIO4I, and FIO4V Description

Specification NI4

Input Range

NIO4I, NIO4V

-10 to +10V dc - 1 LSB

0 to +10V dc

Voltage Input Coding (-10 to +10V dc - 1 -32,768 to +32,767 LSB) Input Impedance

760K ohms(1)

Resolution

305.176 µV per LSB

Full Scale

10V dc

FIO4I, FIO4V 0 to +4095

1M ohms 2.4414 mV per LSB

Overall Accuracy at +25° C (77° F) (max.) ±0.284% of full scale

±0.440% of full scale

Overall Accuracy at 0° to +60° C (32° to 140° F) (max.)

±0.504% of full scale

±0.750% of full scale

Overall Accuracy Drift (max.)

±63ppm/° C of full scale

±88 ppm/°C (max)

Gain Error at +25° C (77° F) (max.)

±0.263%

±0.323% of full scale

Gain Error at 0° to +60° C (32° to 140° F) (max.)

±0.461%

±0.530% of full scale

Gain Error Drift (max.)

±57ppm/° C

±79 ppm/°C (max)

Offset Error at +25° C (77° F) (max.)

±7 LSB

±2 LSB/°C (max)

Offset Error at 0° to +60° C (32° to 140° F) (max.)

±14 LSB

±4 LSB (max)

Offset Error Drift (max.)

±0.20 LSB/° C

±0.14 LSB/°C (max)(3)

(2)

Overvoltage Protection (max. across IN+ either 220V ac RMS continuously or 220V dc continuously to IN- terminals)

220V ac RMS continuously

(1)

The value listed is for Series B and greater. For series A, the input impedance is 1M ohm.

(2)

For improved accuracy over temperature, see SLC 500 Analog I/O Modules User Manual, publication 1746-UM005.

(3)

See the SLC 500 Fast Analog I/O Modules User Manual, publication 1746-6.9.

Publication 1746-IN008C-EN-P - May 2004

-

Page 26

26

SLC™ 500 4-Channel Analog I/O Modules

Current Output Specifications for NIO4I, NO4I, and FIO4I Description

Specification NIO4I, NO4I

FIO4I

Converter Resolution

14 bit

Location of LSB in I/O image word

0000 0000 0000 01XX

Non–linearity

0.05%

Conversion Method

R-2R Ladder

Step Response

2.5 ms (at 95%)

Load Range

0 to 500 Ohms

Maximum Load Reactance

100 µH

Current Output Coding (0 to +21 mA - 1 LSB)

0 to +32764

Output Range (Normal)

0 to +20 mA

0 to +20 mA -1 LSB

Overrange Capability

5% (0 to +21 mA - 1 LSB)

5% (0 to +20 mA - 1 LSB)

Resolution

2.56348 µA per LSB

Full Scale

21 mA

Overall Accuracy at +25° C (77° F) (max.)

±0.298% of full scale

Overall Accuracy at 0° to +60° C (32° to 140° F) (max.)

±0.541% of full scale

Overall Accuracy Drift (max.)

±70ppm/° C of full scale

Gain Error at +25° C (77° F) (max.)

±0.298%

Gain Error at 0° to +60° C (32° to 140° F) (max.)

±0.516%

Gain Error Drift (max.)

±62ppm/° C

Offset Error at +25° C (77° F) (max.)

±10 LSB

Offset Error at 0° to +60° C (32° to 140° F) (max.) ±12 LSB Offset Error Drift (max.)

±0.06 LSB/° C

Publication 1746-IN008C-EN-P - May 2004

-

Page 27

SLC™ 500 4-Channel Analog I/O Modules

27

Voltage Output Specifications for NIO4V, NO4V, and FIO4V Description

Specification NIO4V and NO4V

FIO4V

Converter Resolution

14 bit

Location of LSB in I/O image word

0000 0000 0000 01XX

Non-linearity

0.05%of full scale

Conversion Method

R-2R Ladder

Step Response

2.5 ms (at 95%)

2.5 ms (normal)

Load Range

1K to ∞Ohms

1K to ∞ ohms

Maximum Load Current

10 mA

Maximum Load Reactance

1 µF

Voltage Output Coding (-10 to +10V dc - 1 LSB)

-32,768 to +32,764

-32,768 to +32,764

Output Range (Normal)

-10 to +10 volts - 1 LSB

±10V dc - 1 LSB

Resolution

1.22070 mV per LSB

Full Scale

10V dc

Overall Accuracy at +25° C (77° F) (max.)

±0.208% of full scale

Overall Accuracy at 0° to +60° C (32° to 140° F) (max.)

±0.384% of full scale

Overall Accuracy Drift (max.)

±54ppm/° C of full scale

Gain Error at +25° C (77° F) (max.)

±0.208%

Gain Error at 0° to +60° C (32° to 140° F) (max.)

±0.374%

Gain Error Drift (max.)

±47ppm/° C

Offset Error at +25° C (77° F) (max.)

±9 LSB

Offset Error at 0° to +60° C (32° to 140° F) (max.)

±11 LSB

Offset Error Drift (max.)

±0.05 LSB/° C

Publication 1746-IN008C-EN-P - May 2004

-

Page 28

Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States

1.440.646.3223 Monday – Friday, 8am – 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States

Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for return procedure.

SLC is a trademark of Rockwell Automation, Inc. Belden is a trademark of Belden Inc. C-UL is a registered trademark of Underwriters Laboratories.

Publication 1746-IN008C-EN-P - May 2004 Supersedes Publication 1746-IN008B-EN-P - May 2001

PN 40071-085-01(3) Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.

-