Manual · Allen-Bradley
SLC 500 4-Channel Analog I/O Modules Installation Instructions
Manual28 pagesPDF 920 KB
Installation instructions for the Allen-Bradley SLC 500 4-channel analog I/O modules, including the 1746-NI4 analog input module.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation installation instructions for the SLC 500 4-channel analog I/O modules: 1746-NI4, -NIO4I, -NIO4V, -NO4I, -NO4V, -FIO4I and -FIO4V. It describes each module type, input and output resolution tables, hardware features, hazardous location ratings, backplane power requirements, DIP switch settings for current or voltage inputs, choosing a chassis slot, installing the module, wiring and grounding, labeling the terminal block, reducing electrical noise and full specifications.
Its parts
- For More Information
- Types of Analog Modules
- Hazardous Location Considerations
- Choosing a Slot in the Chassis
- Installing Your Module
- Wiring Considerations
- Wiring the Analog Module
- Labeling and Installing the Terminal Block
- Minimizing Electrical Noise on Analog Modules
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions for the SLC 500 4-channel analog I/O modules: 1746-NI4, -NIO4I, -NIO4V, -NO4I, -NO4V, -FIO4I and -FIO4V. They show how to set the input switches, choose a chassis slot, install and wire a module, and list the specifications of each module.
- Device
- 1746-NI4: analog input module with 4 channels, voltage or current selectable per channel p. 4
- Input type
- 1746-NI4: 4 differential inputs, not individually isolated p. 22
- Input ranges
- 1746-NI4: ±10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc, ±20 mA, 0 to 20 mA, 4 to 20 mA p. 5
- Resolution
- 1746-NI4: 16 significant bits, 305.176 µV/LSB on the ±10V dc range p. 5
- Backplane current
- 1746-NI4: 35 mA at 5V, 85 mA at 24V p. 8
- Update time
- 512 µs for all channels in parallel p. 21
- Isolation
- 500V dc, field wiring to backplane p. 21
- Data format
- 16-bit two's complement binary p. 21
- Input mode switches
- 1746-NI4: DIP switches 1 to 4 set channels 0 to 3; ON is current, OFF is voltage p. 9
- Operating temperature
- 0° to +60° C (+32° to +140° F) p. 21
- Storage and humidity
- -40° to +85° C (-40° to +185° F); 5 to 95% relative humidity, non-condensing p. 21
- Cable and wire
- Shielded Belden #8761; #14 AWG maximum wire size p. 21
- Terminal torque
- 0.57 Nm (5 lb-in) maximum, removable terminal block p. 15, 21
- Mounting
- One slot in a 1746 chassis p. 11, 21
What this manual walks you through
- Setting the voltage or current input switches p. 9, 10
- Calculating the load on the chassis power supply p. 8
- Choosing a slot in the chassis p. 10
- Installing and removing the module p. 11
- Grounding the Belden 8761 cable p. 13
- Preparing and wiring the cable ends p. 14, 15
- Labeling and installing the terminal block p. 16
- Reducing electrical noise on analog signals p. 17
- Wiring 2-, 3- and 4-wire transmitters p. 19
- Wiring single-ended input devices p. 20
Good to know
- The modules do not supply loop power for input devices. p. 19
- Voltages on the IN+ and IN- terminals must stay within 20 volts of ANL COM. p. 13
- A voltage source wired to a channel set for current input can damage the module. p. 9
- Unused input channels are jumpered; unused outputs are left unconnected. p. 15
- Never install, remove or wire a module with power applied to the chassis. p. 11
Questions this manual answers
How much backplane current does the 1746-NI4 draw?
35 mA at 5V and 85 mA at 24V. p. 8
How do I set a 1746-NI4 channel for current input?
Set that channel's DIP switch to ON; switch 1 is channel 0 through switch 4 for channel 3. OFF selects voltage input. p. 9
Does the 1746-NI4 supply loop power for transmitters?
No. Use a power supply that matches the transmitter specifications. p. 19
What cable should be used to wire the 1746-NI4?
Belden #8761, with the drain wire and foil shield grounded at one end of the cable only. p. 13
What is the operating temperature of the 1746-NI4?
0° to +60° C (+32° to +140° F). p. 21
Contents
Chapters and sections
Each line opens the PDF at its page.
- SLC™ 500 4-Channel Analog I/O Modules1
- For More Information3
- Types of Analog Modules4
- Hazardous Location Considerations7
- Environnements dangereux7
- Choosing a Slot in the Chassis10
- Installing Your Module11
- Wiring Considerations12
- Wiring the Analog Module14
- Labeling and Installing the Terminal Block16
- Minimizing Electrical Noise on Analog Modules17
- Specifications21
- Back Cover28
The whole text · 3 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.