Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of SLC 500 4-Channel Analog I/O Modules Installation Instructions

Manual · Allen-Bradley

SLC 500 4-Channel Analog I/O Modules Installation Instructions

Manual28 pagesPDF 920 KB

Installation instructions for the Allen-Bradley SLC 500 4-channel analog I/O modules, including the 1746-NI4 analog input module.

Download the PDF920 KB

Covers · 1 model

The models it covers

Summary

What is in it

Rockwell Automation installation instructions for the SLC 500 4-channel analog I/O modules: 1746-NI4, -NIO4I, -NIO4V, -NO4I, -NO4V, -FIO4I and -FIO4V. It describes each module type, input and output resolution tables, hardware features, hazardous location ratings, backplane power requirements, DIP switch settings for current or voltage inputs, choosing a chassis slot, installing the module, wiring and grounding, labeling the terminal block, reducing electrical noise and full specifications.

Its parts

  1. For More Information
  2. Types of Analog Modules
  3. Hazardous Location Considerations
  4. Choosing a Slot in the Chassis
  5. Installing Your Module
  6. Wiring Considerations
  7. Wiring the Analog Module
  8. Labeling and Installing the Terminal Block
  9. Minimizing Electrical Noise on Analog Modules
  10. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation instructions for the SLC 500 4-channel analog I/O modules: 1746-NI4, -NIO4I, -NIO4V, -NO4I, -NO4V, -FIO4I and -FIO4V. They show how to set the input switches, choose a chassis slot, install and wire a module, and list the specifications of each module.

Device
1746-NI4: analog input module with 4 channels, voltage or current selectable per channel p. 4
Input type
1746-NI4: 4 differential inputs, not individually isolated p. 22
Input ranges
1746-NI4: ±10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc, ±20 mA, 0 to 20 mA, 4 to 20 mA p. 5
Resolution
1746-NI4: 16 significant bits, 305.176 µV/LSB on the ±10V dc range p. 5
Backplane current
1746-NI4: 35 mA at 5V, 85 mA at 24V p. 8
Update time
512 µs for all channels in parallel p. 21
Isolation
500V dc, field wiring to backplane p. 21
Data format
16-bit two's complement binary p. 21
Input mode switches
1746-NI4: DIP switches 1 to 4 set channels 0 to 3; ON is current, OFF is voltage p. 9
Operating temperature
0° to +60° C (+32° to +140° F) p. 21
Storage and humidity
-40° to +85° C (-40° to +185° F); 5 to 95% relative humidity, non-condensing p. 21
Cable and wire
Shielded Belden #8761; #14 AWG maximum wire size p. 21
Terminal torque
0.57 Nm (5 lb-in) maximum, removable terminal block p. 15, 21
Mounting
One slot in a 1746 chassis p. 11, 21

What this manual walks you through

  • Setting the voltage or current input switches p. 9, 10
  • Calculating the load on the chassis power supply p. 8
  • Choosing a slot in the chassis p. 10
  • Installing and removing the module p. 11
  • Grounding the Belden 8761 cable p. 13
  • Preparing and wiring the cable ends p. 14, 15
  • Labeling and installing the terminal block p. 16
  • Reducing electrical noise on analog signals p. 17
  • Wiring 2-, 3- and 4-wire transmitters p. 19
  • Wiring single-ended input devices p. 20

Good to know

  • The modules do not supply loop power for input devices. p. 19
  • Voltages on the IN+ and IN- terminals must stay within 20 volts of ANL COM. p. 13
  • A voltage source wired to a channel set for current input can damage the module. p. 9
  • Unused input channels are jumpered; unused outputs are left unconnected. p. 15
  • Never install, remove or wire a module with power applied to the chassis. p. 11

Questions this manual answers

How much backplane current does the 1746-NI4 draw?

35 mA at 5V and 85 mA at 24V. p. 8

How do I set a 1746-NI4 channel for current input?

Set that channel's DIP switch to ON; switch 1 is channel 0 through switch 4 for channel 3. OFF selects voltage input. p. 9

Does the 1746-NI4 supply loop power for transmitters?

No. Use a power supply that matches the transmitter specifications. p. 19

What cable should be used to wire the 1746-NI4?

Belden #8761, with the drain wire and foil shield grounded at one end of the cable only. p. 13

What is the operating temperature of the 1746-NI4?

0° to +60° C (+32° to +140° F). p. 21

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. SLC™ 500 4-Channel Analog I/O Modules1
    1. For More Information3
    2. Types of Analog Modules4
    3. Hazardous Location Considerations7
    4. Environnements dangereux7
    5. Choosing a Slot in the Chassis10
    6. Installing Your Module11
    7. Wiring Considerations12
    8. Wiring the Analog Module14
    9. Labeling and Installing the Terminal Block16
    10. Minimizing Electrical Noise on Analog Modules17
    11. Specifications21
    12. Back Cover28

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 2821-28

The file

Revision and size

Part no.1746-IN008C-EN-P
RevisionMay 2004