SLC 500 4-Channel Analog I/O Modules User Manual: 5 - Testing Your Module

Pages 55 to 62 of 113, from SLC 500 4-Channel Analog I/O Modules User Manual

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1746-NI4

Page 55

Chapter

5

Testing Your Module

The purpose of this chapter is to help you isolate problems in a systematic and controlled manner before beginning normal system operation. If your analog module is installed in the expansion chassis of a fixed system, test your system using the procedures described in the SLC 500 Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21) before executing the analog module start up procedures.

Testing the SLC 500 System

If your analog module is installed in a modular system, test the modular system using the procedures described in the SLC 500 Modular Hardware Style User Manual (publication 1747-UM011) before executing the analog module start up procedures.

Start-up Procedures Once you have tested your SLC 500 system, follow the steps below in sequence to test your analog module: 1. Inspect the analog module. 2. Disconnect prime movers. 3. Power up the SLC 500 system. 4. Test the analog inputs. 5. Test the analog outputs. 6. Start up the system.

1

Publication 1746-UM005B-EN-P - June 2004

Page 56

5-2

Testing Your Module

Inspect the Analog Module Problems can be prevented by inspecting the analog module before installing it in the SLC 500 system. Inspection should include the following steps: 1. Make sure that all voltage/current mode selection DIP switches are set properly (inputs only). 2. Make sure that all analog module wiring connections are correct and that there are no missing or broken wires. Check the tightness of all terminals to make certain wires are secure.

ATTENTION

Care should be taken to avoid connecting a voltage source to a channel configured for a current input. Improper module operation or damage to the module can occur.

3. Make sure that the shield for the cable used to wire the analog module is properly grounded. Refer to chapter 3 for additional information.

ATTENTION

Do not connect the Belden #8761 foil shield and drain wire to the analog module terminal block. The foil shield and drain wire must be connected to earth ground, which is not available on the analog module terminal block.

4. Make certain that the removable terminal block on the analog module is secured on the module.

Disconnect Prime Movers (Motion Devices) During the following test procedures the processor is energized. As a safety precaution, make sure that machine motion does not occur. To achieve this: • Disconnect the motor wires at the motor starter or the motor itself. This allows you to test the operation of the starter coil, verifying that your output circuit is wired correctly and functioning. • To disconnect a solenoid, disengage the valve, leaving the coil connected.

Publication 1746-UM005B-EN-P - June 2004

Page 57

Testing Your Module

5-3

In some instances, you may not be able to disconnect a device the preferred way. In these cases, open the output circuit at a point as close as possible to the motion-causing device. For example, your output might be a relay coil which in turn energizes a motor starter. If you cannot disconnect the motor wires, open the circuit at a point between the motor starter and the relay contact.

ATTENTION

Machine motion during system checkout can be hazardous to personnel. During all checkout procedures, you must disconnect all devices which, when energized, might cause machine motion.

Power Up the SLC 500 System Apply power to the fixed or modular system. The analog module LED (red) should be illuminated, indicating that the module is receiving 24V dc power. While an illuminated analog module LED does not ensure that the module is operating properly, a non-illuminated LED indicates that the analog module is not functional. Do not continue with the test procedures until the LED is illuminated. The four most probable causes of a non-illuminated LED are: • The SLC 500 system is not receiving power from its power supply. Check the POWER LED on the fixed system unit or the power supply on the modular system. If the LED is not illuminated, refer to the Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21) or the Modular Hardware Style User Manual (publication 1747-UM011). If the module is a 1746-NO4I or NO4V, check the state of the optional 24V dc power switch. If external power is selected, but not connected to the front of the module, the power LED will not illuminate. • The power from the supply is not being received by the remainder of the SLC 500 system. You can test this by attempting to go online with the programming device. • The slot in the chassis where the analog module is located is not operational. Remove the power from the SLC 500 system, move the analog module to another slot and restore power. If it appears that the slot is defective, replace the chassis. • The analog module is defective.

Publication 1746-UM005B-EN-P - June 2004

Page 58

5-4

Testing Your Module

Testing Analog Inputs Before testing the analog module input channels, the SLC 500 system must be installed and tested according to the SLC 500 Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21) or the SLC 500 Modular Hardware Style User Manual (publication 1747-UM011). The processor must be connected to a programming device, properly configured, and must have no rungs in its ladder program. The analog module LED must also be illuminated.

ATTENTION

The procedure described in this section for testing analog module input channels assumes that all I/O module outputs that normally activate prime movers or other potentially dangerous devices have been disconnected from these devices. Do not attempt to test the analog module input channels unless prime movers and/or other potentially dangerous devices are disconnected from the I/O modules.

The devices connected to the analog module input channels are referred to as “sensors.” If the sensors can be manually varied over their normal operating range, use these devices to test the analog module input channels. If the sensors cannot be manually varied, a voltage source or current source is necessary to test the input channels. In this case, disconnect the analog module input channels at the sensor to test the terminal block wiring. The following information applies to either test procedure. IMPORTANT

ATTENTION

Publication 1746-UM005B-EN-P - June 2004

The following procedure does not ensure that the input mode DIP switch is properly configured. Visually inspect the input mode DIP switch before installing the analog module in the chassis.

Care should be taken to avoid connecting a voltage source to a channel configured for a current input. Improper module operation or damage to the module can occur.

Page 59

Testing Your Module

5-5

To test the analog inputs follow these steps: 1. Determine the boundary conditions for the analog module input channel. For example, if the input channel is connected to a sensor that has an output range of 1 mA to 5 mA, the boundary conditions would be 1 mA (lower) and 5 mA (upper). 2. Using the formulas from page, calculate the input decimal values that should appear in the processor image table when the boundary conditions are present on the analog module input channel. For example, if 1 mA and 5 mA are boundary conditions, the decimal values would be 819 and 4096. 3. Assuming that the programming device is on–line with the processor, select the test mode and continuous scan mode function. 4. Display the data in File 1 (Input Image Table). 5. Change the radix of the display to decimal. 6. If the input channel of the module has been disconnected from its sensor, attach a voltage source (voltage input) or current source (current input) to the input and set the source to the lower boundary condition. If the input channel is connected to its sensor, set the sensor to its lower boundary condition. 7. Locate the input channel image data in the image table. The input image word for the input channel being tested should read approximately the lower boundary calculated in step 2. The exact value of the image word is affected by the accuracy of the analog module and the input sensor. Ensure that the deviation from the boundary value is within tolerances for the analog application. 8. If the input channel has been disconnected from its sensor, attach the voltage source (voltage input) or current source (current input) to the input and set the source to the upper boundary condition. If the input channel is connected to its sensor, set the sensor to its upper boundary condition. 9. Repeat step 7 for the upper boundary condition.

Publication 1746-UM005B-EN-P - June 2004

Page 60

5-6

Testing Your Module

10. Repeat steps 1 through 8 for the remaining analog inputs. 11. If any of the analog input channels do not pass the start–up procedure, check for the following potential causes: • The processor is not in the TEST/CONTINUOUS scan mode. • The terminal block is not secured on the analog module. • The analog module terminal block is not wired properly or wires are broken. See chapter 3 for details on wiring the analog module. • The analog module input channel sensor (or test voltage or current source) is not operating properly. If a current source is not available to test a current input channel, a test voltage can be applied to the current input channel to achieve the input boundary conditions. In normal operation, a voltage source should not be connected to an analog input channel in the current mode. To determine the boundary conditions use the following equation: Voltage Input (V) = Current Input (mA) x 0.25 EXAMPLE

If the current input boundary conditions are 1 mA and 5 mA, the boundary conditions in volts would be 0.25 volts and 1.25 volts. If this calculation is done correctly, the test voltage should never exceed 5 volts.

Testing Analog Outputs Before testing the analog module output channels, the SLC 500 system must be installed and tested according to the SLC 500 Modular Hardware Style User Manual (publication 1747-UM011) or the SLC 500 Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21). The processor must be connected to a programming

Publication 1746-UM005B-EN-P - June 2004

Page 61

Testing Your Module

5-7 device, properly configured, and must have no rungs in its ladder program. The analog module LED must be illuminated.

ATTENTION

The procedure described in this section for testing analog module output channels assumes that all I/O module outputs that normally activate prime movers or other potentially dangerous devices have been disconnected from these devices. Do not attempt to test the analog module output channels unless prime movers and/or other potentially dangerous devices are disconnected from the I/O modules.

The devices connected directly to the analog module outputs are referred to as “actuators.” If the actuators do not affect prime movers or initiate any other potentially dangerous operation, use these devices to test the outputs. If the actuators affect prime movers or initiate a potentially dangerous operation, use a voltmeter to test the voltage outputs and an ammeter to test the current outputs. Note that these meters have some inherent error of their own. In the latter case, disconnect actuators at the analog module outputs to test the terminal blocks. The following procedure applies to either of the previous situations. 1. Determine the boundary conditions for the analog module output channel. For example, if the output channel is connected to an actuator that has an input range of 1 volt to 5 volts, the boundary conditions are 1 volt (lower) and 5 volts (upper). 2. Using the formulas from page, calculate the output decimal values that must be entered into the processor image table to produce the analog module output channel boundary conditions determined in step 1. For example, if 1 volt and 5 volts are boundary conditions, the decimal values would be 3277 and 16384.

Publication 1746-UM005B-EN-P - June 2004

Page 62

5-8

Testing Your Module

3. Create and save the test rung shown below. MOV MOVE Source Dest

N7:0 O:e.x

"e" is the slot number of the analog module "x" is the number of the analog module output channel being tested

4. Download the program to the processor and enter the RUN mode. 5. Display the data in address N7:0. 6. Enter lower boundary condition value in N7:0. For example, if the lower boundary condition is 1 volt, enter 3277 into N7:0. 7. If the output channel has not been disconnected from its actuator, the actuator should assume its lower boundary condition. If the output channel has been disconnected from its actuator, connect either the ammeter (current output) or voltmeter (voltage output) to the analog module output channel. The exact value of the meter reading is affected by the accuracy of the analog module and the meter. Ensure that the deviation from the lower boundary condition is within tolerances for the application in which the analog module is used. For example, if 1 volt was the lower boundary condition, the voltmeter should read approximately 1 volt. 8. Enter upper boundary condition value in N7:0. For example, if the upper boundary condition is 5 volts, enter 16384 into N7:0. 9. Repeat step 7 for the upper boundary condition. 10. Repeat steps 1 through 9 for each output channel. 11. If any of the output channels do not pass the start–up procedure, check for the following potential causes: • The processor is not in the RUN mode. • The terminal block is not secured in the analog module. • The analog module terminal block is not wired properly or wires are broken. See chapter 3 for details on wiring the analog module. • The actuator or test ammeter/voltmeter is not operating properly. Publication 1746-UM005B-EN-P - June 2004