Page 67
Chapter
6
Module Configuration Using the Backplane
IMPORTANT
Configuration through the backplane is an alternate configuration method than that presented in Chapter 5. If you prefer to configure your module using an ASCII terminal, or have already done so, you do not need to go through this chapter. Instead, return to Chapter 5 for directions on configuration with a terminal or move on to Chapter 7.
The interface module can be configured through backplane communications using any SLC fixed, 5/01, 5/02, 5/03, 5/04, or 5/05 processor. This chapter guides you through the configuration of your interface module using backplane communications. Once you complete the configuration, return to page 4-15 for instructions on completing the installation of your module. Topics for this chapter include: • configuring the interface module from the SLC processor. • placing the module into software Run mode from the SLC processor. • reading the module’s configuration from the SLC processor. • examining the SLC processor’s status word. • building the DF1, DH-485, and Modem Init String configuration packets. • using the Real Time Clock. • establishing a Data Echo between the interface module and the SLC processor. • resetting the interface module from the SLC processor.
Overview
1
In this method of configuration, the SLC processor uses the backplane to load the configuration data into the Output Image file for the interface module. By assigning a Data ID value in the Output Image file you designate which parameters to configure.
Publication 1747-UM005B-EN-P - March 2006
Page 68
6-2
Module Configuration Using the Backplane
There are six valid Data ID values, one for each of the configuration packets you create to configure your interface module. Valid Data ID Values Data ID value Lets you build a configuration packet for 01
Calendar/Clock Function
02
DF1 Set Up Parameters
03
DH-485 Set Up Parameters
04
Modem Init String (1...14 characters)
05
Modem Init String (15...28 characters)
06
Data Echo
IMPORTANT
Configure the Interface Module from the SLC Processor
The steps for configuring the module from the SLC processor follow. Use these instructions to build the configuration packets described in the remainder of this chapter. IMPORTANT
Publication 1747-UM005B-EN-P - March 2006
Any of the configuration packets can be sent independently and do not need to be in a particular sequence, with the exception of the Modem Init String packets (Data ID 4 and 5). In this instance, packet ID 4 must be sent before packet ID 5.
The terms software Configuration mode and software Run mode in this chapter refer to the SLC processor changing the interface module’s mode across the backplane. The module’s JW4 jumper must remain in the vertical Run mode (module configuration ID=3509) while using backplane communications.
Page 69
Module Configuration Using the Backplane
6-3
Configure the Module From the SLC Processor With the SLC processor you
The interface module then
1. Place the module into software Configuration mode, if it is not already. Do this setting the Module Mode Bit (O:e.0/15). 2. Load the correct Data ID value for the parameters you will configure (O:e.0/0...3). 3. Build the Output Image file with configuration data (O:e.1...7). 4. Write the configuration data by resetting the Read or Write bit (O:e.0/13). 5. Set the Data Handshake bit to indicate the data in the Output Image file is valid (O:e.0/14). 6. Gets the configuration data from the SLC Output file. 7. Configures parameters on the Interface Module. 8. Echoes the Data ID (I:e.0/0...3) and configuration data (I:e.1...7), and places the status of the configuration transaction in the SLC Input File (I:e.0/4...10). 9. Sets the Data Handshake bit to indicate the image data is valid (I:e.0/14). 10. Reset the Data Handshake bit (O:e.0/14). 11. Resets the Data Handshake bit (I:e.0/14). 12. Save your configuration changes by putting the module in software Run mode.
IMPORTANT
The configuration data that is loaded does not take effect until the interface module goes to software Run mode. Therefore, to save your configuration changes be sure to put the module in software Run mode.
Publication 1747-UM005B-EN-P - March 2006
Page 70
6-4
Module Configuration Using the Backplane
Place the Module into Software Run Mode from SLC Processor
When configuration is complete, place the module in software Run mode by following these steps. Place the Module in Run Mode With the SLC processor you
The interface module then
1. Reset the Module Mode bit to software Run (O:e.0/15). 2. Set the Data Handshake bit to indicate the data in the Output Image file is valid (O:e.0/14). 3. Resets the Module Mode bit to software Run in the SLC Input Image File (I:e.0/15). 4. Sets the Data Handshake bit (I:e.0/14). 5. Reset the Data Handshake bit (O:e.0/14). 6. Resets the Data Handshake bit (I:e.0/14).
Publication 1747-UM005B-EN-P - March 2006
Page 71
Module Configuration Using the Backplane
Read the Module’s Configuration from the SLC Processor
6-5
The interface module’s current configuration can be read back to the SLC processor using the Input and Output Image files. IMPORTANT
The interface module can be in software Run or software Configuration mode during the read operation.
Read the Module’s Configuration from the SLC Processor With the SLC processor you The interface module then 1. Set the Read or Write bit to indicate a configuration read operation (O:e.0/13). 2. Set the Data ID value for the configuration parameters to be read (O:e.0/0...3). 3. Set the Data Handshake bit to indicate the data in the Output Image file is valid (O:e.0/14). 4. Interprets the Data ID value. 5. Gets the configuration data from the Interface Module. 6. Loads the data into the Input Image file (I:e.1...7). 7. Sets the Data Handshake bit to indicate the image data is valid (I:e.0/14). 8. Read configuration data. 9. 9. Reset the Data Handshake bit (O:e.0/14). 10. 10. Resets the Data Handshake bit (I:e.0/14).
Publication 1747-UM005B-EN-P - March 2006
Page 72
6-6
Module Configuration Using the Backplane
Examine the SLC Processor’s Status Word
SLC Output Status Word to the Interface Module The output status word reserved for implementing backplane configuration and for resetting the interface module is shown below. Those status bits not defined here are reserved for future use. SLC Output Status Word Status Bits Data Handshake Bit 0 = Data in the output image may not be valid. 1 = Data in the Output Image file is valid.
Reset Interface Module Bit 1 = Reset the module.
Bit Number (decimal) 15 14 13 12 11 10 9
8
7
6
5
Read or Write Bit
Module Mode Bit
4
3
2
1
0
O:e.0
R R R R R R R R
Status Word, Word 0
0 = Place module in software Run mode. 1 = Place module in software Configuration mode.
Data ID Value BIts
0 = Write 1 = Read
Valid Values: 01 = Calendar/Clock Setup 02 = DF1 Configuration 03 = DH-485 Configuration 04 = Modem Init String (characters 1 through 14) 05 = Modem Init String (characters 15 through 28) 06 = Data Echo Function (all other values are invalid)
SLC Input Status Word from the Interface Module This is the input status word reserved for implementing backplane configuration and for resetting the interface module. Those status bits not defined below are reserved for future use. SLC Input Status Word Status Bits Data Handshake Bit (1)
Reset Acknowledge Bit (1)
0 = Input image data may not be valid. 1 = SLC output image data is accepted by the interface module. Input image data is valid.
1 = Acknowledges that the module was reset from the SLC processor.
Bit Number (decimal) 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0 = Module is running. 1 = Module requires configuring or is in software Configuration mode.
Battery Status Bit
Modem Lost Bit (1)
0 = Battery is good. 1 = Battery is low.
0 = Modem carrier detected. 1 = Modem carrier inactive (no modem connected).
(1) Applies to series B, or later interface modules only.
Publication 1747-UM005B-EN-P - March 2006
0
I:e.0
Status Word, Word 0
Module Mode Bit
Status Code Bits
Data ID Value Bits (1)
Page 73
Module Configuration Using the Backplane
6-7
Status Codes from the Module to the Processor The module informs the SLC processor on the status of the configure or read transaction by placing a status value in the Input Image file word 0, bits 4 to 10. A value of 00 indicates that the status is okay. Status Codes from the Module to the SLC Processor Value Value Indicates improper status for (hex) (dec) 01
01
Day
02
02
Month
03
03
Year
04
04
Day of the Week
05
05
Hour
06
06
Minute
07
07
Second
08
08
Data ID
09
09
(Not Used)
0A
10
(Not Used)
0B
11
DF1 Enq/Msg Retry
0C
12
Modem Init String Delay
0D
13
Master Station/NAK Rec Retry
0E
14
Slave Address/Group Number
0F
15
(Not Used)
10
16
DF1 Message Timeout
11
17
(Not Used)
12
18
RTS Off Delay
13
19
DH-485 Node Address
14
20
DH-485 Max Node Address
15
21
DH-485 Communication Rate
16
22
DH-485 Message TImeout
17
23
Modem Init String character
18
24
A write operation is attempted, but the configuration bit is not set (still in software Run mode).
Publication 1747-UM005B-EN-P - March 2006
Page 74
6-8
Module Configuration Using the Backplane
Build the DF1 Configuration Packet
15
14
13
12
Use the SLC processor to set up the DF1 port. Build the configuration packet shown by following the configuration instructions found on page 6-2. SLC Output File to the Interface Module 11 10 9 8 7
6
5
4
3
2
1
0
Bit Word 0(1)
Module Data Read or Reset Reserved Mode Handshake Write Interface Bit Bit Bit Module Bit
1
Data ID=2
Embedded Half or Constant Hardware Check Duplicate Stop Response Full- Carrier Handsum Packet Bits Detect duplex Detect(2) shaking(2) Detection (Full) or Local/Rem ote Mode (Half)
Parity
Bits per DF1 Character Communication Rate
2
Modem Init String Delay (0...25 s)
Enq/Msg Retries (0...254)
3
Slave Address (Local) (0...254) Group Number (Remote) (0...7)
Master Station Address (Half Duplex) (0...254) NAK Rec Retries (Full Duplex) (0...254)
4
ACK/POLL Timeout (0...65,535 x 5 ms)
5
Message Timeout (100...12,750 ms)
6
RTS ON Delay (0...65,535 x 5 ms)(3)
7
RTS OFF Delay (0...65,499 x 5 ms)(3)
(1)
The output status word is defined on page 6-6. To configure the DF1 parameters the Read or Write Bit must be 0 and the Module Mode Bit must be 1. To read the DF1 parameters, the Read or Write Bit must be 1 and the Module Mode Bit can either be 0 or 1.
(2)
If Constant Carrier Detect is enabled, Hardware Handshaking is forced on.
(3)
The value is ignored if full-duplex is chosen.
Publication 1747-UM005B-EN-P - March 2006
Page 75
Module Configuration Using the Backplane
6-9
DF1 Port Setup Parameters When the module is powered up for the first time, the DF1 port will be set to the default parameters shown in the table below. If these parameters are changed and the setup is saved (by changing to software Run mode), then the module will always power up with the new settings, unless the battery fails and power to the module’s RAM is lost. DF1 Port Setup Parameters Options
Parameter
Default
Description
Communication Rate
1200
0=300, 1=600, 2=1200, 3=2400, 4=4800, 5=9600, 6 and 7=19200
The speed in bits per second at which data is transferred. Must be set the same as the DF1 device.
Bits Per Character
8 bits
0=7 bits, 1=8 bits
The size in number of bits of each character to be transferred. Must be set the same as the DF1 device.
Parity
None
0 and 3=None, 1=Even, 2=Odd
Used for checking data during the transfer. Must be set the same as the DF1 device.
Stop Bits
1 bit
0=1 bit, 1=2 bits
Used for delineating data during the transfer. Must be set the same as the DF1 device.
Publication 1747-UM005B-EN-P - March 2006