DH-485/RS-232C Interface Module, Catalog Number 1747-KE, User Manual: 7 - Interpret the LED Indicators

Pages 85 to 88 of 139, from DH-485/RS-232C Interface Module, Catalog Number 1747-KE, User Manual

The original document is the PDF (1.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1747-AIC DH-485

Page 85

Chapter

7

Interpret the LED Indicators

This chapter contains the following information. • Interface module status indicators • Input image description • SLC fault code

Interface Module Status Indicators

For a full description of the eight LED indicators on the front of the module, see page 1-3. During normal operation, the LED indicators are illuminated as shown below LED Indicators

Solid Green Solid Green

Off Flashing during communications.

1

DH-485/RS-232C ACT

FAULT

485

BA LOW

CFG

H/D

DF1

F/D

INTERFACE

Off Off

One of these will be on depending on the configuration chosen.

Publication 1747-UM005B-EN-P - March 2006

Page 86

7-2

Interpret the LED Indicators

Shown below are possible error conditions represented by the LED indicators and their possible solutions.

LED

LED Indicator Error Conditions Color Status Condition

ACT

Green

Solution

Flashing The module requires configuration. The module requires configuration. OFF

The module is not receiving power from the backplane. A fault condition exists.

Check the SLC power supply. Make sure the interface module is properly installed in the rack.

485

Green

OFF

The DH485 port is not active for communication.

Check DH-485 cabling. Make sure the module’s JW4 jumper is not in Configuration mode.

DF1

Green

OFF

DF1 host is transmitting data and LED indicator is not flashing.

Check DF1 cabling. Make sure the module’s JW4 jumper is not in Configuration mode.

FAULT

Red

ON

A system problem was detected during background diagnostics.

Contact your Allen-Bradley representative.

BA LOW Red

ON

The voltage of the battery that Replace battery. backs up configuration RAM is low.

CFG

OFF

The CONFIG port is transmitting data and LED indicator is not flashing.

Green

Input Image Description

Check ASCII terminal cabling. Make sure the module’s JW4 jumper is in Configuration mode.

Shown below is the input image that provides status to the SLC processor. Bit 13 indicates the battery status. The status information contained in bit 13 corresponds to the module’s BA LOW LED indicator. Bit 15 indicates whether the module requires configuration or not. Input Image Data Handshake Bit (1) 0 = Input image data may not be valid. 1 = SLC output image data is accepted by the interface module. Input image data is valid.

Reset Acknowledge Bit (1) 1 = Acknowledges that the module was reset from the SLC processor.

Bit Number (decimal) 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0 = Module is running. 1 = Module requires configuring or is in software Configuration mode.

Battery Status Bit

Modem Lost Bit (1)

Data ID Value Bits (1)

0 = Battery is good. 1 = Battery is low.

0 = Modem carrier detected. 1 = Modem carrier inactive (no modem connected).

(echoed from Output Image)

(1) Applies to series B, or later, interface modules only.

Publication 1747-UM005B-EN-P - March 2006

0

I:e.0

Status Word, Word 0

Module Mode Bit

Status Code Bits

Page 87

Interpret the LED Indicators

Status Codes from the Module to the Processor

7-3

The module informs the SLC processor on the status of the configure or read transaction by placing a status value in the Input Image file word 0, bits 4 to 10. A value of 00 indicates that the status is okay. Status Codes from the Module to the SLC Processor Value Value Indicates improper status for (hex) (dec) 01 01 Day 02 02 Month 03 03 Year 04 04 Day of the Week 05 05 Hour 06 06 Minute 07 07 Second 08 08 Data ID 09 09 (Not Used) 0A 10 (Not Used) 0B 11 DF1 Enq/Msg Retry 0C 12 Modem Init String Delay 0D 13 Master Station/NAK Rec Retry 0E 14 Slave Address/Group Number 0F 15 (Not Used) 10 16 DF1 Message Timeout 11 17 (Not Used) 12 18 RTS Off Delay 13 19 DH-485 Node Address 14 20 DH-485 Max Node Address 15 21 DH-485 Communication Rate 16 22 DH-485 Message TImeout 17 23 Modem Init String character 18 24 A write operation is attempted, but the configuration bit is not set (still in software Run mode).

SLC Fault Code

If a fault has occurred in the SLC system and the SLC fault code indicates the slot the interface module is installed in, the fault might be associated with the module I/O configuration. Refer to the table below. SLC Fault Codes SLC Fault Code (S:6) xx54

(1)

xx55(1) (1)

Possible Reason Wrong ID code was entered. Wrong ID code was entered or wrong input and output size were entered.

xx refers to the slot where the module is installed.

Publication 1747-UM005B-EN-P - March 2006

Page 88

7-4

Interpret the LED Indicators

Publication 1747-UM005B-EN-P - March 2006