Page 13

Chapter

1

Overview

This chapter provides: • an overview of the interface module. • features (communication ports, LED indicators, and jumpers). • guidelines outlining the type of modems you can use with the module. • a brief discussion on using RSLinx software with your module. • typical configurations.

Interface Module Overview The DH-485/RS-232C Interface Module, catalog number 1747-KE, is a communications interface module that acts as a bridge between DH-485 networks and devices requiring DF1 protocol. The DF1 port on the interface module can be configured for RS-232/423, RS-422, or RS-485 devices. Residing in an SLC 500 chassis, the module is ideally used as an interface module, linking remote DH-485 networks via a modem to a central host. Interface Module Overview

Local Host

Modem

Interface Module (1747-KE)

Link Coupler (1747-AIC)

Modem DH-485

Link Coupler (1747-AIC) DH-485

Link Coupler (1747-AIC)

1

Remote Network

Publication 1747-UM005B-EN-P - March 2006

Page 14

1-2

Overview

Features

The features of the module are shown below. 1747-KE Module Features JW1 LEDs

DH-485/RS-232C

CAT

FRN

SLC 500 INTERACE MODULE SER

SERIAL NO.

CONFIG Port

9 87 6

54 3 2 1 CONFIG

5 4 3 2 1

CONFIG

DF1 Port 9 87 6

54 3 2 1 DF1

5 4 3 2 1

DH-485 Port

Battery JW4

9 8 7 6

DF1

DH485

JW2

9 8 7 6

DH485

Door Label

There are three communication ports on the front of the module. They are: • CONFIG - used to configure the module with an ASCII terminal. This serial port accommodates RS-232/423, RS-422, and RS-485 communication interfaces. The CONFIG port is capable of operating at 300, 600, 1200, 2400, 4800, 9600, and 19200 Kbps. It is electrically isolated to 500V dc. • DF1 - used to interface the module to a modem or other user devices using DF1 protocol. This serial port accommodates RS-232/423, RS-422, and RS-485 communication interfaces. The DF1 port is capable of operating at 300, 600, 1200, 2400, 4800, 9600, and 19200 Kbps. It is electrically isolated to 500V dc. • DH485 - used to interface the module with the DH-485 network. This port is not isolated and cannot directly drive a multi-node DH-485 network. You must use a 1747-AIC link coupler to connect this port to a DH-485 network that includes multiple SLC 500 processors. The 1747-C11 or 1747-C13 cables can connect the interface module’s DH-485 port to a 1747-AIC link coupler. The 1747-C13 cable can also connect the module’s DH-485 port directly to a single SLC processor. See page 4-11 for cable connections.

Publication 1747-UM005B-EN-P - March 2006

Page 15

Overview

1-3

LED Indicators There are eight LED indicators on the front of the module. These LED indicators are used for module diagnostics and operator interface. The LED indicators and their descriptions are provided below. LED Indicators

DH485/RS-232C ACT

FAULT

485 CFG

BA LO W H/D

DF1

F/D

INTERFACE

LED Indicator Status LED

Color

Status

Indication

ACT

Green

ON(1)

The module is receiving power from the backplane, is configured properly, and is placed in Run mode.

Flashing

The module requires configuration or is being configured.

OFF

The module is not receiving power from the backplane. A fault condition exists.

ON

The DH485 port is active on the network.

OFF

The DH485 port is not active on the network or the module is in Configuration mode.

Flashing

The CONFIG port is transmitting or receiving signals.

OFF

The CONFIG port is not transmitting or receiving signals.

Flashing

The DF1 port is transmitting or receiving signals. (The flashing may occur so rapidly that the LED indicator appears to be on.)

OFF

The DF1 port is not transmitting or receiving signals or the module is in Configuration mode.

ON

A system problem was detected during diagnostics. Cycle power to reset. If it remains on, contact your Allen-Bradley representative.

OFF

No system problems are detected during diagnostics.

ON

The voltage of the battery that backs up configuration RAM is low. A new battery is needed.

OFF

The voltage of the battery that backs up configuration RAM is at an acceptable level.

ON

The module is configured for half-duplex DF1 protocol (local or remote).

OFF

The module is not configured for half-duplex DF1 protocol.

ON

The module is configured for full-duplex DF1 protocol.

OFF

The module is not configured for full-duplex DF1 protocol.

485

CFG DF1

FAULT

BA LOW

H/D F/D

(1)

Green

Green Green

Red

Red

Amber Amber

Indicates normal operation after the module has been configured.

Publication 1747-UM005B-EN-P - March 2006

Page 16

1-4

Overview

Jumper JW1 JW1 lets you to select the communication interface for the CONFIG port. Refer to page 4-5.

Jumper JW2 JW2 lets you to select the communication interface for the DF1 port. Refer to page 4-6.

Jumper JW4 JW4 lets you to select the functionality and mode of the interface module. The orientation of the jumper determines the module’s functionality. A horizontal orientation gives the module functionality equivalent to a series A module (module configuration ID=4209), while a vertical orientation of the jumper accesses the added functionality of a series B module (module configuration ID=3509). The position of the jumper determines the module’s mode (Configuration or Run), and thus, which method is used to configure the module (ASCII terminal or backplane communications). Refer to Chapter 4. Jumper Placement JW1

54 3 2 1 CONFIG

9 87 6

54 3 2 1 DF1

9 87 6

DH485

Publication 1747-UM005B-EN-P - March 2006

SLC 500 INTERACE MODULE SER

FRN

JW2

CAT

SERIAL NO.

JW4

Page 17

Overview

Use a Modem with Your Interface Module

1-5

The module can be connected to most types of dial-up network or direct connect modems. IMPORTANT

Some modems are designed to respond to the DTR signal by answering the phone whether it is ringing or not. Since the module asserts DTR at all times (except during the hang-up sequence), the phone appears to be busy at all times. Do not use the interface module with any type of modem that answers the phone as soon as DTR is asserted.

The type of modems you can use are: • Manual - typically acoustically-coupled modems. A person on each end of the phone line establishes the connection. They then insert the handsets into an acoustic coupler to complete the connection. • DTE controlled answer - these unattended modems are attached directly to the phone lines. The interface module acts as the Data Terminal Equipment (DTE), which controls the modem via the DTR, DSR, and DCD signals. The module incorporates timeouts and tests to properly operate these types of modems. • Auto answer - these modems have self-contained timeouts and tests. They can answer and hang up the phone automatically. The module has no means of controlling an auto-dial modem, but it can be used in conjunction with a separate auto-dialer. • Direct connect - these modems connect to a dedicated, leased phone line and remain active at all times.

Use DF1 Protocol and Your Module

RSLinx software supports DF1 communications directly from your computer’s serial communication port. Connecting a modem to this port lets you to call remote networks and control them as if you were connected locally. DF1 Protocol Interface Module (1747-KE)

DF1 DF1 Protocol

1747-C13 Cable Modem

DF1 Protocol

Modem

Publication 1747-UM005B-EN-P - March 2006

Page 18

1-6

Overview

Typical Configurations

The following configurations illustrate some of the possible uses for the module.

Full-duplex (Point-to-point) Full-duplex (Point-to-point) Interface Module (1747-KE)

DF1

Modem Modem 1747-C13 Cable

This illustration shows a connection to a single remote SLC node. The 1747-C13 cable eliminates the need for a 1747-AIC link coupler.

Full-duplex (Network, Example 1) Full-duplex (Network, Example 1)

RSLInx Link Coupler (1747-AIC)

Interface Module (1747-KE)

Modem Modem

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

This illustration shows a connection to a remote DH-485 network of up to 31 SLC nodes.

Publication 1747-UM005B-EN-P - March 2006

Page 19

Overview

1-7

Full-duplex (Network, Example 2) Full-duplex (Network, Example 2)

RSLinx Interface Module (1747-KE) Modem Host computer is capable of calling and interfacing with one network at a time.

Link Coupler (1747-AIC)

Modem

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

Interface Module (1747-KE)

Interface Module (1747-KE) Link Coupler (1747-AIC)

Modem Link Coupler (1747-AIC)

Modem

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

This configuration allows the host to call more than one remote network (one network connected at a time). Each remote network can consist of up to 31 SLC nodes.

Publication 1747-UM005B-EN-P - March 2006

Page 20

1-8

Overview

Half-duplex (Local Mode) Half-duplex (Local Mode) Master Link Coupler (1747-AIC)

PLC-5 processor

Interface Module (1747-KE)

Modem

Modem

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

This configuration allows the host controller to interface on a remote DH-485 network of up to 31 SLC nodes using the half-duplex protocol.

Publication 1747-UM005B-EN-P - March 2006

Page 21

Overview

1-9

Half-duplex (Remote Mode) Half-duplex (Remote Mode) Master

SLC 5/05 processor Dedicated Line Modem

Interface Module (1747-KE) Interface Module (1747-KE)

Group 00

Dedicated Line Modem

Interface Module (1747-KE)

Group 01

Dedicated Line Modem

Dedicated Line Modem

Group 02

This illustration shows a host connect up to eight groups of DH-485 networks, connecting up to a total of 254 SLC nodes.

Publication 1747-UM005B-EN-P - March 2006

Page 22

1-10

Overview

Half-duplex (Slave-to-slave Communication) Half-duplex (Slave-to-slave Communication)

Dedicated Line Modem

SLC 5/05 processor

Dedicated Line Modem

RSLinx

Dedicated Line Modem

Interface Module (DF1 Slave) Link Coupler (1747-KE) (1747-AIC)

Link Coupler (1747-AIC)

Link Coupler (1747-AIC)

(DF1 Slave)

This configuration allows a DF1 slave device send a message to another DF1 slave device. In this example, RSLinx can communicate to an SLC slave.

Publication 1747-UM005B-EN-P - March 2006