Page 138
Appendix
D
Calculating Heat Dissipation for the SLC 500 Control System This appendix will assist you in calculating the heat dissipation of your SLC 500 control system. It consists of the following: • definition of key terms • table and graphs • example heat dissipation calculation • heat dissipation worksheet (page D–5) To select an enclosure for your SLC 500 control system, refer to chapter 1.
Definition of Key Terms
The following terms are used throughout this appendix. Familiarize yourself with them before proceeding further into the appendix. Watts per point, maximum heat dissipation that can occur in each field wiring point when energized. Minimum watts, amount of heat dissipation that can occur when there is no field power present. Maximum watts, maximum amount of heat that the module generates with field power present.
Module Heat Dissipation: There are two ways that you can calculate heat dissipation. Calculated Watts vs. Maximum Calculated Watts, if you want to determine the amount of heat generated Watts by the points energized on your module, use the formula below for calculating the heat dissipation of each module. Then use these values for calculating the heat dissipation of your control system, which is done using the worksheet.
(number of points energized x watts per point) + minimum watts = heat dissipation of module or controller
Maximum Watts, maximum amount of heat that the module generates with field power present. Use maximum watts especially if you are not sure how many points on a module will be energized at any time. Once you have determined which way you will calculate the heat dissipation of your modules, see the Example Worksheet for Calculating Heat Dissipation on page D–4. This worksheet shows you how to calculate the heat dissipation for the example SLC control system also on page D–4. Once you feel comfortable with the layout of the worksheet, go to the worksheet on page D–5 and fill it out for your control system. D–1
Page 139
Appendix D Calculating Heat Dissipation for the SLC 500 Control System
Use this Table to Calculate the Power Supply Loading
Use the table below to calculate the power supply loading for each chassis that you have (step 1 of the worksheet). Hardware Component
Fixed Controllers
Input Modules
Output Modules
D–2
Catalog Numbers 1747-L20A 1747-L30A 1747-L40A 1747-L20B 1747-L30B 1747-L40B 1747-L20C 1747-L30C 1747-L40C 1747-L20D 1747-L30D 1747-L20E 1747-L40E 1747-L20F 1747-L40F 1747-L20G 1747-L20L 1747-L30L 1747-L40L 1747-L20N 1747-L20P 1747-L30P 1747-L40P 1747-L20R 1746-IA4 1746-IA8 1746-IA16 1746-IM4 1746-IM8 1746-IM16 1746-IB8 1746-IB16 1746-IB32 1746-IV8 1746-IV16 1746-IV32 1746-IG16 1746-IN16 1746-OA8 1746-OA16 1746-OB8 1746-OB16 1746-OB32 1746-OV8
0.27 0.27 0.27 0.27 0.27 0.27 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.35 0.35 0.35 0.35 0.27 0.27 0.27 0.35 0.35 0.35 0.20 0.20 0.20 0.20 0.20 0.20 0.020 0.35 1.00 0.462 0.775 0.338 0.078
Minimum Watts 10.5 12.7 14.3 9.9 11.6 13.0 17.4 18.7 19.9 12.4 13.9 12.6 16.0 5.0 7.4 4.4 12.1 14.0 16.0 4.4 8.8 10.5 11.6 10.5 0.175 0.250 0.425 0.175 0.250 0.425 0.250 0.425 0.530 0.250 0.425 0.530 0.700 0.425 0.925 1.85 0.675 1.40 2.26
Maximum Watts 15.0 19.2 23.0 17.0 22.0 27.0 21.0 24.0 27.0 19.0 23.0 18.0 27.0 9.0 15.0 10.0 18.0 23.0 27.0 10.0 17.0 23.0 28.0 16.0 1.30 2.40 4.80 1.60 3.10 6.00 1.90 3.60 6.90 1.90 3.60 6.90 1.00 6.00 9.00 9.30 6.90 7.60 4.80
0.775
0.675
6.90
Watts per Point
Page 140
Appendix D Calculating Heat Dissipation for the SLC 500 Control System
Hardware Component
Output Modules
Catalog Numbers 1746-OV16 1746-OV32 1746-OW4 1746-OW8 1746-OW16 1746-OX8 1746-OG16 1746-IO4
Input & Output Modules
1746-IO8 1746-IO12
Specialty Modules
Peripheral Devices
NA
1746-NI4 1746-NIO4I 1746-NIO4V 1746-NO4I 1746-NO4V 1746-BAS 1747-DCM 1747-DSN 1747-KE 1747-AIC 1747-DTAM 1747-PT1 Series A & B 1747-PIC
Minimum Watts 1.40 2.26 1.31 2.59 5.17 2.59 0.900
Maximum Watts 7.60 4.80 1.90 3.70 5.70 8.60 1.50
0.75
1.60
1.38
3.00
2.13
4.60
2.17 3.76 3.04 4.96 3.78 3.75 1.8 4.5 3.75 2.0 2.5
2.2 3.8 3.1 5.0 3.8 3.8 1.8 4.5 3.8 2.0 2.5
NA
2.5
2.5
NA
2.0
2.0
Watts per Point 0.388 0.078 0.133 0.138 0.033 0.825 0.033 0.27 per input pt. 0.133 per output pt. 0.27 per input pt. 0.133 per output pt. 0.27 per input pt. 0.133 per output pt. NA NA NA NA NA NA NA NA NA NA NA
Not Applicable
D–3
Page 141
Appendix D Calculating Heat Dissipation for the SLC 500 Control System
Example Heat Dissipation Calculation
If your controller consisted of the following hardware components, you would calculate heat dissipation as shown in the example worksheet below. Hardware Components
Catalog Number
Minimum Watts
Maximum Watts
Fixed Controller
1747-L20A
10.5
15.0
Input Module
1746-IA16
0.425
4.8
Output Module
1746-OA16
1.85
9.3
Peripheral Device
1747-DTAM
2.5
2.5
Example Worksheet for Calculating Heat Dissipation Procedure 1.
Heat Dissipation
Calculate the heat dissipation for your fixed controller. Write in the watts (calculated watts or maximum watts, see page D-1) dissipated by the controller, I/O and specialty modules, and peripheral device attached to the controller. Add these values together. Catalog Number
Heat Dissipation
_________
_________
Slot 1 (if applicable) _________
_________
Slot 2 (if applicable) _________
_________
Fixed Controller Expansion Chassis
Peripheral Device
_________ Total:
2.
_________ _________ Place Total on this Line --->
Convert to BTUs/hr. Multiply the total heat dissipation of your SLC 500 fixed control system by 3.414.
_______ W x 3.414
Total heat dissipation of the SLC 500 control system: _______ BTUs/hr
D–4
Page 142
Appendix D Calculating Heat Dissipation for the SLC 500 Control System
Worksheet for Calculating Heat Dissipation
Use this worksheet to calculate the heat dissipation for your fixed controller.
Procedure
Heat Dissipation
1. Calculate the heat dissipation for your fixed controller. Write in the watts (calculated watts or maximum watts, see page D-1) dissipated by the controller, I/O and specialty modules, and peripheral device attached to the controller. Add these values together. Catalog Number
Heat Dissipation
_________
_________
Slot 1 (if applicable)
_________
_________
Slot 2 (if applicable)
_________
_________
Peripheral Device
_________
_________
Fixed Controller Expansion Chassis
Total:
_________
Place Total on this Line --->
2. Convert to BTUs/hr. Multiply the total heat dissipation of your SLC 500 fixed control system by 3.414.
___________ W x 3.414
Total heat dissipation of the SLC 500 control system: __________ BTUs/hr
D–5