Page 144
Appendix
E
Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller This appendix covers the following for your fixed controller. • wiring diagrams • circuit diagrams • voltage ranges
Wiring Symbols
The following table provides an explanation of the symbols used in the wiring diagrams. The symbols do not indicate the only type of I/O devices that can be connected, but rather a “typical” device. As long as your I/O device meets the I/O circuit specifications, it should be compatible. This Symbol
Represents Typical Input Device Mechanical switch Solid-state switch
This Symbol
Represents Typical Output Device Solenoid
CR
Control relay
The connections illustrated in the wiring diagrams are shown for example purposes only. • You can connect I/O devices in any order to the I/O circuits. If you are not going to load all of your circuits, space the connections evenly apart to help in heat dissipation. • All the input circuits on any one fixed controller are the same with one exception: input 0 is unique for all fixed controllers which have 24 VDC input circuits. In this case, input 0 can be used as a high–speed counter. The diagrams in this appendix show the differences in operating characteristics. • All the output circuits on any one fixed controller are the same. In the wiring diagrams for the fixed controller with 24 VDC input circuits and 120/240 VAC line power, the User Power Source (terminals next to Power Supply terminals, “PWR OUT 24 VDC” and “PWR OUT COM”) is shown to power some input devices. This is optional. The User Power Source can provide up to 200mA at 24 VDC for input devices. E–1
Page 145
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Wiring and Circuit Diagrams and Voltage Range Locations Catalog Numbers 1747-L20A 1747-L20B 1747-L20C
Description➀ (12) 120 VAC Inputs and (8) Relay Outputs (12) 120 VAC Inputs and (8) Triac Outputs (12) 24 VDC Sinking Inputs, High-Speed Counter Input and (8) Relay Outputs
Wiring Diagram
Input Circuit Diagram
On/Off State Voltage
Output Circuit Diagram
Operating Voltage Range
E-4
E-5
E-5
E-5
E-5
E-6
E-7
E-7
E-7
E-7
E-8
E-9
E-9
E-10
E-10
1747-L20D
(12) 24 VDC Sinking Inputs, High-Speed Counter Input and (8) Triac Outputs
E-11
E-12
E-12
E-13
E-13
1747-L20E
(12) 24 VDC Sinking Inputs, High-Speed Counter Input and (8) Transistor Sourcing Outputs
E-14
E-15
E-15
E-16
E-16
1747-L20F
(12) 24 VDC Sinking Inputs, High-Speed Counter Input and (8) Relay Outputs
E-17
E-18
E-18
E-19
E-19
1747-L20G
(12) 24 VDC Sinking Inputs, High-Speed Counter Input and (8) Transistor Sourcing Outputs
E-20
E-21
E-21
E-22
E-22
1747-L20L
(12) 24 VDC Sourcing Inputs, High-Speed Counter Input and (8) Transistor Sinking Outputs
E-23
E-24
E-24
E-25
E-25
1747-L20N
(12) 24 VDC Sourcing Inputs, High-Speed Counter Input and (8) Transistor Sinking Outputs
E-26
E-27
E-27
E-28
E-28
E-29
E-30
E-30
E-30
E-30
E-31
E-32
E-32
E-32
E-32
E-33
E-34
E-34
E-34
E-34
E-35
E-36
E-36
E-36
E-36
E-37
E-38
E-38
E-39
E-39
1747-L20P 1747-L20R 1747-L30A 1747-L30B 1747-L30C
(12) 240 VAC Inputs and (8) Triac Outputs (12) 240 VAC Inputs and (8) Relay Outputs (18) 120 VAC Inputs and (12) Relay Outputs (18) 120 VAC Inputs and (12) Triac Outputs (18) 24 VDC Sinking Inputs, High-Speed Counter Input and (12) Relay Outputs
1747-L30D
(18) 24 VDC Sinking Inputs, High-Speed Counter Input and (12) Triac Outputs
E-40
E-41
E-41
E-42
E-42
1747-L30L
(18) 24 VDC Sourcing Inputs, High-Speed Counter Input and (12) Transistor Sinking Outputs
E-43
E-44
E-44
E-45
E-45
E-46
E-47
E-47
E-47
E-47
E-48
E-49
E-49
E-49
E-49
1747-L30P 1747-L40A E–2
Use the table below to locate the appropriate wiring and circuit diagrams and voltage ranges.
(18) 240 VAC Inputs and (12) Triac Outputs (24) 120 VAC Inputs and (16) Relay Outputs
Page 146
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Wiring Diagram
Input Circuit Diagram
On/Off State Voltage
Output Circuit Diagram
Operating Voltage Range
E-50
E-51
E-51
E-51
E-51
E-52
E-53
E-53
E-54
E-54
1747-L40E
(24) 24 VDC Sinking Inputs, High-Speed Counter Input and (16) Transistor Sourcing Outputs
E-55
E-56
E-56
E-57
E-57
1747-L40F
(24) 24 VDC Sinking Inputs, High-Speed Counter Input and (16) Relay Outputs
E-58
E-59
E-59
E-60
E-60
1747-L40L
(24) 24 VDC Sourcing Inputs, High-Speed Counter Input and (16) Transistor Sinking Outputs
E-61
E-62
E-62
E-63
E-63
1747-L40P
(24) 240 VAC Inputs and (16) Triac Outputs
E-64
E-65
E-65
E-65
E-65
Catalog Numbers 1747-L40B 1747-L40C
Description➀ (24) 120 VAC Inputs and (16) Triac Outputs (24) 24 VDC Sinking Inputs, High-Speed Counter Input and (16) Relay Outputs
➀
Refer to page 1-5 for line power specifications.
E–3
Page 147
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L20A (12) 120 VAC Inputs & (8) Relay Outputs
Wiring Diagram (Hi) L1
(Lo) L2
5-265 VAC or 5-125 VDC 1
CR
(Hi) L1
(Lo) L2
5-265 VAC or 5-125 VDC 1
CR
CR
CR
VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 OUT 6 OUT 7 VDC 1 VDC 2
(Hi) L1
(Lo) L2
(Lo) L2
(Hi) L1
85-132 VAC
85-265 VAC
120/240 VAC VAC NEUT CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
IN 0
IN 1
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
Commons Connected Internally
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–4
Page 148
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.3 µ F IN
270
1870
1 µF
261
0.3 µ F IN
On/Off State Voltage Ranges
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ
85 VAC
30 VAC
0 VAC Off-state
Input State Not Guaranteed
132 VAC On-state
Output Circuit Diagram VAC/VDC
OUT
OUT
Operating Voltage Range 0 V 5 VAC 0 V 5 VDC
ÉÉ ÉÉ
265 VAC 125 VDC Recommended Operating Range
Operation Not Guaranteed
E–5
Page 149
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L20B Wiring Diagram (12) 120 VAC Inputs & (8) Triac (Hi) Outputs L1 85-265 VAC
(Lo) L2
1
(Hi) L1 85-265 VAC
CR
(Lo) L2
1
CR
CR
CR
VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 VAC 2 OUT 4 OUT 5 OUT 6 OUT 7
(Hi) L1
(Lo) L2
(Lo) L2
(Hi) L1
85-132 VAC
85-265 VAC
120/240 VAC VAC NEUT CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
IN 0
IN 1
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
Commons Connected Internally
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–6
Page 150
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.3 µ F IN
270
1870
1 µF
261
0.3 µ F IN
On/Off State Voltage Ranges
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ
85 VAC
30 VAC
0 VAC Off-state
Input State Not Guaranteed
132 VAC On-state
Output Circuit Diagram L1
OUT
OUT
Operating Voltage Range
ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 0 VAC
85 VAC
Operation Not Guaranteed
265 VAC Recommended Operating Range
Important: If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 VAC even though the output is off.
E–7
Page 151
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L20C (12) 24 VDC Sinking Inputs, High-Speed Counter Input & (8) Relay Outputs
Wiring Diagram (Hi) L1
5-265 VAC 5-125 VDC
(Lo) L2
(Hi) L1
5-265 VAC 5-125 VDC
1
CR
(Lo) L2 1
CR
CR
CR
VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 OUT 6 OUT 7 VDC 1 VDC 2
(Hi) L1
(Lo) L2
85-265 VAC Sourcing Device 120/240 VAC VAC NEUT CHASSIS GND
PWR OUT DC +24VDC 2 COM
PWR OUT DC COM 2 COM
IN 1
IN 0 HSC
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
Commons Connected Internally - DC
10-30 VDC
+ DC
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
➁ 24 VDC, 200mA user power is available for sensors.
E–8
Page 152
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 560
560
INPUT 0 (HSC) 0.01 µ F
1. 5K
OTHER INPUTS
390
1. 5K 0.1 µ F
560
COM
On/Off State Voltage Ranges – Input 0 (HSC) 0 VDC
ÉÉÉÉÉ ÉÉÉÉÉ
10 VDC
4 VDC
Off-state
30 VDC On-state
Input State Not Guaranteed
On/Off State Voltage Ranges – All Other Inputs 0 VDC
ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC
Off-state
10 VDC
30 VDC On-state
Input State Not Guaranteed
E–9
Page 153
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Output Circuit Diagram VAC/VDC
OUT
OUT
Operating Voltage Range 0 V 5 VAC 0 V 5 VDC
ÉÉ ÉÉ
Operation Not Guaranteed
E–10
265 VAC 125 VDC Recommended Operating Range