SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual: E - Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller, pages 154 to 163

Pages 154 to 163 of 223, from SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C

Page 154

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L20D (12) 24 VDC Sinking Inputs, High-Speed Counter Input & (8) Triac Outputs

Wiring Diagram (Hi) L1

(Lo) L2

1

85-265 VAC

(Hi) L1 85-265 VAC

CR

CR

(Lo) L2

1

CR

CR

VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 VAC 2 OUT 4 OUT 5 OUT 6 OUT 7

(Hi) L1

(Lo) L2

85-265 VAC Sourcing Device 120/240 VAC VAC NEUT CHASSIS GND

PWR OUT DC +24VDC 2 COM

PWR OUT DC COM 2 COM

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

IN 9 IN 8

IN 11 IN 10

Commons Connected Internally - DC

10-30 VDC

+ DC

➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.

➁ 24 VDC, 200mA user power is available for sensors.

E–11

Page 155

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Input Circuit Diagram 560

560

INPUT 0 (HSC) 0.01 µ F

1. 5K

OTHER INPUTS

390

1. 5K 0.1 µ F

560

COM

On/Off State Voltage Ranges – Input 0 (HSC)

0 VDC

ÉÉÉÉÉÉ ÉÉÉÉÉÉ

10 VDC

4 VDC

Off-state

30 VDC On-state

Input State Not Guaranteed

On/Off State Voltage Ranges – All Other Inputs 0 VDC

ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC

Off-state

10 VDC

Input State Not Guaranteed

E–12

30 VDC On-state

Page 156

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Output Circuit Diagram L1

OUT

OUT

Operating Voltage Range

ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 0 VAC

85 VAC

Operation Not Guaranteed

265 VAC Recommended Operating Range

Important: If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 VAC even though the output is off.

E–13

Page 157

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L20E (12) 24 VDC Sinking Inputs, High-Speed Counter Input & (8) Transistor Sourcing Outputs

Wiring Diagram + DC

- DC 10-50 VDC

CR

VDC

(Hi) L1

CR

CR

CR

OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 DC COM

(Lo) L2

85-265 VAC Sourcing Device 120/240 VAC VAC NEUT CHASSIS GND

PWR OUT DC +24VDC 1 COM

PWR OUT DC COM 1 COM

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

Commons Connected Internally - DC

10-30 VDC

+ DC

➀ 24 VDC, 200mA user power is available for sensors.

E–14

IN 9 IN 8

IN 11 IN 10

Page 158

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Input Circuit Diagram 560

560

IN 0 HSC 0.01 µ F

1. 5K

IN OTHER INPUTS

390

1. 5K 0.1 µ F

560

COM

On/Off State Voltage Ranges – Input 0 (HSC) 0 VDC

ÉÉÉÉÉ ÉÉÉÉÉ

10 VDC

4 VDC

Off-state

30 VDC On-state

Input State Not Guaranteed

On/Off State Voltage Ranges – All Other Inputs 0 VDC

ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC

Off-state

10 VDC

30 VDC On-state

Input State Not Guaranteed

E–15

Page 159

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Output Circuit Diagram VDC

OUT

OUT

DC COM

Operating Voltage Range

ÉÉÉÉÉÉ ÉÉÉÉÉÉ

10 VDC

0 VDC

(Voltage is applied between +VDC and DC common.)

E–16

Operation Not Guaranteed

50 VDC Recommended Operating Range

Page 160

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L20F (12) 24 VDC Sinking Inputs, High-Speed Counter Input & (8) Relay Outputs

Wiring Diagram (Hi) L1

(Lo) L2

5-265 VAC or 5-125 VDC 1

CR

(Hi) L1

(Lo) L2

5-265 VAC or 5-125 VDC 1

CR

CR

CR

VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 OUT 6 OUT 7 VDC 1 VDC 2

- DC +

+ DC

10-30 VDC

-

24 VDC +10% + 24 VDC

VDC NEUT

CHASSIS GND

NOT USED

DC COM

NOT DC USED COM

IN 1

IN 0 HSC

Commons Connected Internally

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

IN 9 IN 8

IN 11 IN 10

Sourcing Device

➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.

E–17

Page 161

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Input Circuit Diagram 560

560

INPUT 0 (HSC) 0.01 µ F

1. 5K

OTHER INPUTS

390

1. 5K 0.1 µ F

560

COM

On/Off State Voltage Ranges – Input 0 (HSC)

0 VDC

ÉÉÉÉÉÉ ÉÉÉÉÉÉ

10 VDC

4 VDC

Off-state

30 VDC On-state

Input State Not Guaranteed

On/Off State Voltage Ranges – All Other Inputs 0 VDC

ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC

Off-state

10 VDC

Input State Not Guaranteed

E–18

30 VDC On-state

Page 162

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Output Circuit Diagram VAC/VDC

OUT

OUT

Operating Voltage Range 0 V 5 VAC 0 V 5 VDC

ÉÉ ÉÉ

265 VAC 125 VDC Recommended Operating Range

Operation Not Guaranteed

E–19

Page 163

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L20G (12) 24 VDC Sinking Inputs, High-Speed Counter Input & (8) Transistor Sourcing Outputs

Wiring Diagram + DC

- DC 10-50 VDC

CR

VDC

CR

CR

CR

OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 DC COM

- DC

+ DC 10-30 VDC

+

-

24 VDC +10%

+ 24 VDC

VDC NEUT

CHASSIS GND

NOT USED

NOT DC USED COM

Commons Connected Internally

E–20

DC COM

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

IN 9 IN 8

IN 11 IN 10

Sourcing Device