Page 204
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L40L (24) 24 VDC Sourcing Inputs, High-Speed Counter Input & (16) Transistor Sinking Outputs
Wiring Diagram
+ DC
- DC 10-50 VDC
CR
+ DC
- DC 10-50 VDC
1
CR
CR
CR
CR
CR
1
CR
CR
VDC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 DC VDC 2 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 OUT 13 OUT 14 OUT 15 DC COM 1 COM 2
Sinking Device (Hi) L1
(Lo) L2
85-265 VAC
120/240 VAC VAC NEUT
PWR OUT VDC +24VDC 2
EARTH PWR OUT VDC COM 2 GND
VDC
VDC
IN 1
IN 0 HSC
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
IN 19
IN 18
IN 21
IN 20
IN 23
IN 22
VDC Connected Internally + DC
10-30 VDC
- DC
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
➁ 24 VDC, 200mA user power is available for sensors.
E–61
Page 205
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram VDC
560
0.01 µ F
390
0.1 µ F
560
560
INPUT 0 (HSC)
1. 5K
OTHER INPUTS
1. 5K
On/Off State Voltage Ranges – Input 0 (HSC) 0 VDC
ÉÉÉÉÉÉ ÉÉÉÉÉÉ
10 VDC
4 VDC
Off-state
30 VDC On-state
Input State Not Guaranteed
On/Off State Voltage Ranges – All Other Inputs 0 VDC
ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC
Off-state
10 VDC
Input State Not Guaranteed
E–62
30 VDC On-state
Page 206
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Output Circuit Diagram VDC
OUT
OUT
DC COM
Operating Voltage Range
ÉÉÉÉÉÉ ÉÉÉÉÉÉ
10 VDC
0 VDC
(Voltage is applied between +VDC and DC common.)
50 VDC Recommended Operating Range
Operation Not Guaranteed
E–63
Page 207
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L40P (24) 240 VAC Inputs & (16) Triac Outputs
(Hi) L1
(Hi) L1
(Lo) L2
1
85-265 VAC
CR
Wiring Diagram
85-265 VAC
CR
CR
CR
CR
(Lo) L2
1
CR
CR
CR
VAC 1 VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 VAC 2 VAC 2 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 OUT 13 OUT 14 OUT 15
VAC 1 Connected Internally
VAC 2 Connected Internally
(Hi) L1
(Lo) L2
(Lo) L2
(Hi) L1
170-265 VAC
85-265 VAC
120/240 VAC VAC NEUT CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
AC COM
AC COM
IN 0
IN 1
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
IN 19
IN 18
IN 21
IN 20
IN 23
IN 22
Commons Connected Internally
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–64
Page 208
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.15 µF IN
270
1870
1 µF
261
0.15 µF IN
On/Off State Voltage Ranges 0 VAC Off-state
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ
265 VAC
170 VAC
50 VAC
Input State Not Guaranteed
On-state
Output Circuit Diagram L1
OUT
OUT
Operating Voltage Range
ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 0 VAC
85 VAC
Operation Not Guaranteed
265 VAC Recommended Operating Range
Important: If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 VAC even though the output is off.
E–65