Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 24 of 26

SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual: E - Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller, pages 204 to 209

Pages 204 to 209 of 223, from SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C

Page 204

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L40L (24) 24 VDC Sourcing Inputs, High-Speed Counter Input & (16) Transistor Sinking Outputs

Wiring Diagram

+ DC

- DC 10-50 VDC

CR

+ DC

- DC 10-50 VDC

1

CR

CR

CR

CR

CR

1

CR

CR

VDC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 DC VDC 2 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 OUT 13 OUT 14 OUT 15 DC COM 1 COM 2

Sinking Device (Hi) L1

(Lo) L2

85-265 VAC

120/240 VAC VAC NEUT

PWR OUT VDC +24VDC 2

EARTH PWR OUT VDC COM 2 GND

VDC

VDC

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

IN 9 IN 8

IN 11 IN 10

IN 13

IN 12

IN 15

IN 14

IN 17

IN 16

IN 19

IN 18

IN 21

IN 20

IN 23

IN 22

VDC Connected Internally + DC

10-30 VDC

- DC

➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.

➁ 24 VDC, 200mA user power is available for sensors.

E–61

Page 205

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Input Circuit Diagram VDC

560

0.01 µ F

390

0.1 µ F

560

560

INPUT 0 (HSC)

1. 5K

OTHER INPUTS

1. 5K

On/Off State Voltage Ranges – Input 0 (HSC) 0 VDC

ÉÉÉÉÉÉ ÉÉÉÉÉÉ

10 VDC

4 VDC

Off-state

30 VDC On-state

Input State Not Guaranteed

On/Off State Voltage Ranges – All Other Inputs 0 VDC

ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC

Off-state

10 VDC

Input State Not Guaranteed

E–62

30 VDC On-state

Page 206

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Output Circuit Diagram VDC

OUT

OUT

DC COM

Operating Voltage Range

ÉÉÉÉÉÉ ÉÉÉÉÉÉ

10 VDC

0 VDC

(Voltage is applied between +VDC and DC common.)

50 VDC Recommended Operating Range

Operation Not Guaranteed

E–63

Page 207

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Catalog Number 1747-L40P (24) 240 VAC Inputs & (16) Triac Outputs

(Hi) L1

(Hi) L1

(Lo) L2

1

85-265 VAC

CR

Wiring Diagram

85-265 VAC

CR

CR

CR

CR

(Lo) L2

1

CR

CR

CR

VAC 1 VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 VAC 2 VAC 2 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 OUT 13 OUT 14 OUT 15

VAC 1 Connected Internally

VAC 2 Connected Internally

(Hi) L1

(Lo) L2

(Lo) L2

(Hi) L1

170-265 VAC

85-265 VAC

120/240 VAC VAC NEUT CHASSIS GND

NOT USED

NOT USED

AC COM

AC COM

AC COM

AC COM

IN 0

IN 1

IN 3 IN 2

IN 5 IN 4

IN 7 IN 6

IN 9 IN 8

IN 11 IN 10

IN 13

IN 12

IN 15

IN 14

IN 17

IN 16

IN 19

IN 18

IN 21

IN 20

IN 23

IN 22

Commons Connected Internally

➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.

E–64

Page 208

Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller

Input Circuit Diagram 270

1870

AC COM 1 µF

261

0.15 µF IN

270

1870

1 µF

261

0.15 µF IN

On/Off State Voltage Ranges 0 VAC Off-state

ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ

265 VAC

170 VAC

50 VAC

Input State Not Guaranteed

On-state

Output Circuit Diagram L1

OUT

OUT

Operating Voltage Range

ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 0 VAC

85 VAC

Operation Not Guaranteed

265 VAC Recommended Operating Range

Important: If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 VAC even though the output is off.

E–65

Page 209

This page is a scan with no text; see it in the PDF.