Page 20
Chapter
1
Selecting Your Hardware Components This chapter provides general information on what your SLC 500 controller can do for you and an overview of the fixed control system. It also explains how to select: • 2–slot chassis • discrete I/O modules • specialty I/O modules • enclosures • operator interfaces • memory modules • isolation transformers • suppressors • output contact protection There is also a section on special considerations for controller installations. This chapter does not provide you with all the information that you need to select a complete SLC 500 control system. To do this, we recommend that you use the latest version of the system overview, SLC 500 Family of Small Programmable Controllers, Publication Number 1747–2.30.
What Your SLC 500 Controller Can Do for You
The SLC 500 programmable controller has features that previously could only be found in large programmable controllers. It has the flexibility and power of a large controller with the size and simplicity of a small controller. The SLC 500 controller offers you more control options than any other programmable controller in its class. These programmable controllers make up a technologically advanced control system having inherent flexibility and advantages characteristic of other programmable controllers, but with one important difference, simplicity!
1–1
Page 21
Chapter 1 Selecting Your Hardware Components
Overview of Your Fixed Control System
The basic fixed controller consists of a processor with 1,024 (1K) instruction capacity, a power supply, and a fixed number of I/O contained in a single package. The figure below shows typical hardware components for a fixed controller.
Fixed Hardware Components
Fixed Hardware Controller
Operator Interface
1–2
Input Module
Fixed Controller with 2-slot Expansion Chassis
Output Module
2-Slot Expansion Chassis for I/O Modules
Page 22
Chapter 1 Selecting Your Hardware Components
Fixed Controller Specifications
This section provides the specifications for the SLC 500 Fixed Controller. Description
Specification
Memory Type
Capacitor-backed RAM memory. Battery back-up optional.
Memory Backup Options
EEPROM or UVPROM
Program Memory
1K Instruction Capacity
Capacitor Memory Back-up Time
Refer to curve on page 1-4.
Battery Life
5 years
Typical Scan Time➀
8 milliseconds/1K
Bit Execution (XIC)
4 microseconds
Program Scan Hold-up Time after Loss of Power
20 milliseconds to 700 milliseconds (dependent on loading)
Power Supply Operating Voltage
AC units: 85-265 VAC 47-63 Hz DC units: 21.6-26.4 VDC (24 VDC ± 10%)
Power Supply Fuse Protection
AC units: 120/240 VAC DC units: 24 VDC
Power Supply Inrush Rating
30 Amperes maximum
Maximum Power Requirement
50 VA➁
24 VDC User Power Output Current➂
200mA
24 VDC User Power Output Voltage➂
20.4 - 27.6 VDC (24 VDC ± 15 %)
Wire Size
#14 AWG Max.
I/O Electrical-Optical Isolation
1500 VAC at 1 minute
1747-AIC Link Coupler Electrical-Optical Isolation
1500 VDC
LED Indicators
POWER, PC RUN, CPU FAULT, FORCED I/O, and BATTERY LOW
Noise Immunity
NEMA Standard ICS 2-230
Ambient Temperature Rating
Operating: 0°C to +60°C (+32°F to +140°F) Storage: 40°C to +85°C (-40°F to +185°F)
Humidity
5 to 95% without condensation
1.25A 1.6A
Displacement: .015 inch, peak-to-peak @ 5-57 Hz Vibration
Acceleration: 2.5 Gs @ 57-2000 Hz Duration: 1 hr per axis (x, y, z)
Certification
UL listed/ CSA approved
➀ The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication servicing. Actual scan times depend on your program size, instructions used, and the DH-485 communication.
➁ This specification does not include input and output values. (See page 1-6.) ➂ This applies only to fixed controllers that have AC line power and DC input circuits.
1–3
Page 23
Chapter 1 Selecting Your Hardware Components
Memory Backup for the SLC 500 Fixed Controller The curve below illustrates the ability of the memory back–up capacitor to maintain the contents of the RAM in a fixed controller. To back up the memory for a longer period of time, a lithium battery, Catalog Number 1747–BA, is required. 30
25 Capacitor Memory Back-up Time VS Temperature
20 Time (Days)
15
10
5 25 (77°)
30
35
40
45
50
55
60
(86°)
(95°)
(104°)
(113°)
(122°)
(131°)
(140°)
Temperature °C (°F)
1–4
Page 24
Chapter 1 Selecting Your Hardware Components
Configuration Options The following table provides configuration options for 20, 30, or 40 I/O points. Catalog Number
Line Power
I/O Configuration Input Output
High-Speed Counter
User Power
1747-L20A
(12) 120 Volts AC
(8) AC/DC Relay
No
NA
1747-L30A
(18) 120 Volts AC
(12) AC/DC Relay
No
NA
1747-L40A
(24) 120 Volts AC
(16) AC/DC Relay
No
NA
1747-L20B
(12) 120 Volts AC
(8) AC Triac
No
NA
1747-L30B
(18) 120 Volts AC
(12) AC Triac
No
NA
1747-L40B
(24) 120 Volts AC
(16) AC Triac
No
NA
1747-L20C
(12) 24 Volts DC Sink
(8) AC/DC Relay
Yes
24V-200mA
1747-L30C
(18) 24 Volts DC Sink
(12) AC/DC Relay
Yes
24V-200mA
1747-L40C
(24) 24 Volts DC Sink
(16) AC/DC Relay
Yes
24V-200mA
1747-L20D
(12) 24 Volts DC Sink
(8) AC Triac
Yes
24V-200mA
1747-L30D
(18) 24 Volts DC Sink
(12) AC Triac
Yes
24V-200mA
(12) 24 Volts DC Sink
(8) DC Transistor Source
Yes
24V-200mA
1747-L40E
(24) 24 Volts DC Sink
(16) DC Transistor Source
Yes
24V-200mA
1747-L20L
(12) 24 Volts DC Source
(8) DC Transistor Sink
Yes
24V-200mA
1747-L30L
(18) 24 Volts DC Source
(12) DC Transistor Sink
Yes
24V-200mA
1747-L40L
(24) 24 Volts DC Source
(16) DC Transistor Sink
Yes
24V-200mA
1747-L20R
(12) 240 Volts AC
(8) AC/DC Relay
No
NA
1747-L20P
(12) 240 Volts AC
(8) AC Triac
No
NA
1747-L30P
(18) 240 Volts AC
(12) AC Triac
No
NA
1747-L40P
(24) 240 Volts AC
(16) AC Triac
No
NA
1747-L20F
(12) 24 Volts DC Sink
(8) AC/DC Relay
Yes
NA
(24) 24 Volts DC Sink
(16) AC/DC Relay
Yes
NA
(12) 24 Volts DC Sink
(8) DC Transistor Source
Yes
NA
(12) 24 Volts DC Source
(8) DC Transistor Sink
Yes
NA
1747-L20E
120/240 VAC
1747-L40F 1747-L20G 1747-L20N
24 VDC± 10%
1–5
Page 25
Chapter 1 Selecting Your Hardware Components
Input Specifications The following table details the input specifications for SLC 500 Fixed I/O units. See the glossary for a definition of specifications. Inputs
120 VAC
240 VAC
DC Sink & Source
1–6
Specifications On-State Voltage
85-132 VAC
Frequency
47-63 Hz
Off-State Voltage
30 VAC (maximum)
Inrush Current
0.8A peak
Nominal Input Current
12mA at 120 VAC
Turn-On Time
35 milliseconds (maximum)
Turn-Off Time
45 milliseconds (maximum)
Maximum Off-State Current
2mA
On-State Voltage
170-265 VAC
Frequency
47-63 Hz
Off-State Voltage
50 VAC (maximum)
Inrush Current
1.6A peak
Nominal Input Current
12mA at 240 VAC
Turn-On Time
35 milliseconds (maximum)
Turn-Off Time
45 milliseconds (maximum)
Maximum Off-State Current
2mA
On-State Voltage
10-30 VDC
Off-State Voltage
4 VDC maximum for input 0 (HSC) 5 VDC for all others
Nominal Input Current
20mA at 24 VDC (for input 0 only) 8mA at 24 VDC (all others inputs)
Turn-On Time
8 milliseconds (maximum)
Turn-Off Time
8 milliseconds (maximum)
Maximum Off-State Current
1mA
Page 26
Chapter 1 Selecting Your Hardware Components
Output Specifications The following table details the output specifications for SLC 500 Fixed I/O Units. Outputs
Triac
Transistor Sink & Source
Relay➂
Specifications Output Voltage
85-265 VAC
Continuous Current (per output)
0.5 Amp at +30°C 0.25 Amp at +60°C (maximum)
Minimum Load Current
10mA
Turn-On Time
0.1 milliseconds (maximum)
Turn-Off Time
10 milliseconds (maximum)
Maximum Off-State Leakage Current
2mA
Maximum On-State Voltage Drop
1.5V @ 0.5 Amps
Maximum Surge Current
10 Amps for 25 milliseconds➀
Output Voltage
10-50 VDC
Continuous Current (per output)
0.5 Amp at +30°C 0.25 Amp at +60°C (maximum)
Minimum Load Current
1mA
Turn-On Time
0.1 millisecond (maximum)
Turn-Off Time
1 millisecond (maximum)
Maximum Off-State Leakage Current
1mA
Maximum On-State Voltage Drop
1.5V @ 0.5 Amps
Maximum Surge Current
3.0 Amps for 25 milliseconds➀
Output Voltage Range
5-265 VAC, 5-125 VDC
Continuous Current (per output)
2.5 Amps (maximum)
Continuous Current (per group)➁
8 Amps (maximum)
Maximum Load (per chassis)
1440 VA
Turn-On Time
10 milliseconds (maximum)
Turn-Off Time
10 milliseconds (maximum)
Maximum Off-State Leakage Current
0mA
Minimum Load Current at 5 VDC
10mA
➀ Repeatability is once every 1 second at +30°C. Repeatability is once every 2 seconds at +60°C. ➁ Refer to the wiring diagrams for output groupings on the fixed I/O chassis. ➂ Surge suppression across the output device is recommended to protect relay contacts.
1–7
Page 27
Chapter 1 Selecting Your Hardware Components
Relay Contact Ratings Maximum Volts 240 VAC 120 VAC
Make 7.5A 15A
Amperes
Break
0.75A 1.5A
Amperes Continuous 2.5A
Voltamperes Make Break 1800 VA
180 VA
125 VDC
0.22A
1.0A
28 VA
24 VDC
1.2A
2.0A
28 VA
To calculate make and break ratings for other load voltages, divide the voltampere rating by the load voltage; for example: 28 VA/48 VDC = 0.583 A
Selecting the 2-Slot Chassis
For the 20, 30, and 40 I/O fixed controllers, an optional 2–slot expansion chassis lets you add two additional I/O modules providing even more versatility. The power supply provides backplane power for the modules in the optional expansion chassis. Refer to chapter 3 for chassis dimensions and chapter 4 for mounting directions.
Selecting Discrete I/O Modules
There are three types of I/O modules: input, output, and combination I/O. They are available in a wide variety of densities including 4, 8, 16, and 32 point and can interface to AC, DC, and TTL voltage levels. Output modules are available with solid–state AC, solid–state DC, and relay contact type outputs. For a complete, up–to–date listing of discrete I/O modules and their specifications, contact your Allen–Bradley sales office for the latest product data entitled Discrete Input and Output Modules, Publication Number 1746–2.35. Refer to chapter 4 for installation directions.
Selecting Speciality I/O Modules
The SLC 500 family offers specialty I/O modules that enhance your control system. These modules range in function from analog interface to motion control, from communication to high–speed counting. For a complete, up–to–date listing of specialty I/O modules and their specifications, contact your Allen–Bradley sales office for the latest System Overview entitled SLC 500 Family of Small Programmable Controllers, Publication Number 1747–2.30, or for a related product data. Refer to chapter 4 for installation directions.
1–8
Page 28
Chapter 1 Selecting Your Hardware Components
Selecting Enclosures
Selecting Operator Interfaces
The enclosure protects the equipment from atmospheric contamination. Standards established by the National Electrical Manufacturer’s Association (NEMA) define enclosure types, based on the degree of protection an enclosure will provide. Use a fan to circulate the air of sealed enclosures that use convection cooling to dissipate heat. Select a NEMA–rated enclosure that suits your application and environment. The enclosure should be equipped with a disconnect device. To calculate the heat dissipation of your controller, see appendix D.
Use an operator interface to program and/or monitor your SLC 500 controller. You can choose from several Allen–Bradley operator interface devices.
Programming with a Hand-Held Terminal (1747-PT1) Use the Hand–Held Terminal (HHT) to configure the SLC 500 controller, enter/modify a user program, download/upload programs, monitor control operation, and test/troubleshoot. When equipped with a battery (1747–BA), the HHT retains a user program in memory for storage and later use. The display area accommodates 8 lines x 40 characters. You can display five rungs of a user program. The top row of keys are the menu function keys. Important: Using the HHT, you can program the SLC 5/01t and 5/02t processors and the SLC 500 fixed controllers. You cannot, however, program the SLC 5/03 processor. Refer to the Hand–Held Terminal User Manual, Catalog Number 1747–NP002, for information on programming your fixed controller with the HHT.
Programming with Advanced Programming Software (APS) on an IBM Compatible Computer The Advanced Programming Software (APS) can be used with an Allen-Bradley T45, T47, or T50 terminal, an IBMr-AT or XT, a Compaqr Portable, Portable II, Deskprot 286, 386/SX, 386, a Tandyt 3000HL, Toshibat 3100E, or GATEWAY 2000t models 386DX/25, 386DX/33, 486DX/33, and 486DX2/50 personal computer. Your computer must have: • 640 Kbytes of RAM (extended or expanded memory is recommended, but not required) • 10 Mbyte fixed-disk drive (APS requires a minimum or 2.5 MBytes of free disk space.) • DOS version 3.1 or higher
1–9
Page 29
Chapter 1 Selecting Your Hardware Components
Advanced Programming Software, 1747–PA2E APS, Catalog Number 1747–PA2E, comes on 5–1/4 and 3–1/2 inch disks. You must have DOS installed in your computer. You also must have at least 550 Kbytes of free memory to execute the APS software. Like the Hand–Held Terminal, APS lets you configure the SLC 500 controller, enter/modify a user program, restore/save programs to the SLC 500, monitor controller operation, and test/troubleshoot. You can also: • create and print ladder diagrams, data tables, instruction cross references, and configurations • use cut/copy/paste editor • store multiple programs in the memory of the computer (on the hard disk) Refer to the Advanced Programming Software User Manual, Catalog Number 1747–NM002, and the Advanced Programming Software Reference Manual, Catalog Number 1747–NR001, for information on programming your fixed controller with APS. DH–485 Interface Converter (1747–PIC) For communication, use an RS–232/DH–485 Interface Converter between the computer and SLC controller. The converter includes a 279.4 mm (11.0 in.) ribbon cable, already attached to the converter, for connection to the computer serial port and a Catalog Number 1746–C10 cable for connection to the controller.
Monitoring with a Data Table Access Module (1747-DTAM-E) The Data Table Access Module (DTAM) is a plant floor device that lets you access data file information, change operating modes, monitor and clear processor faults, and transfer the user program between RAM and an EEPROM memory module with any SLC 500 family processor. You cannot use it to create new programs. Important features of DTAM include: • shorthand addressing, which provides easier access to data files • display prompts in six, user–selectable languages: English, French, German, Italian, Spanish, and Japanese • UL listed, CSA Certified • NEMA type 12 and 13 enclosures • point–to–point interface to an SLC family processor, or as a network device on a DH–485 network Refer to the Data Table Access Module (DTAM) User Manual, Catalog Number 1747–ND013, for information on monitoring your fixed controller with the DTAM.
1–10