Page 30
Chapter 1 Selecting Your Hardware Components
EEPROM and UVPROM Memory Modules
These optional memory modules provide a non–volatile memory back–up in a convenient modular form. The modules plug into a socket on the controller. You can store (save) your program in the EEPROM by inserting it into the processor and using either the Hand–Held Terminal or Advanced Programming Software. Use of the UVPROM provides you with an extra degree of program security because the user program cannot be altered while it is installed in the controller. You can program the UVPROM with commercially available UVPROM programming and erasing equipment. You can use an EEPROM module as a master, or you can use an archived processor file as the source by using the APS PROM translator utility. Adapter sockets are required when inserting memory modules into commercially available PROM programmer. The memory module fits into the adapter socket and then into a PROM programmer.
!
ATTENTION: Make sure the adapter is inserted properly or damage could result.
The following table lists the types of memory modules that are available for the fixed controller. Also listed are the manufacturer part number for determining compatibility with an external PROM burner.
Description
1K User Words EEPROM
4K User Words EEPROM
Catalog Number
1747-M1
1747-M2
Manufacturer
Manufacturer's Part Number
NEC uPD28C64 - 250
OKI
MSM28C64ARS - 20
XICOR
X28C64BP - 25
SEEQ
PE28C64 - 250
XICOR
X28C256DI - 25 X28256DI - 25
SEEQ
DE28C256 - 25 MBM27C64 - 25
1K User Words UVPROM
1747-M3
Fujitsu
4K User Words UVPROM
1747-M4
Not compatible with the fixed controller.
Adaptor Socket
1747-M5
NA
NA
1–11
Page 31
Chapter 1 Selecting Your Hardware Components
Selecting Isolation Transformers
If there is high frequency conducted noise in or around your distribution equipment, we recommend that you use an isolation transformer in the AC line to the power supply. This type of transformer provides isolation from your power distribution system and is often used as a “step down” transformer to reduce line voltage. Any transformer used with the controller must have a sufficient power rating for its load. This power rating is generally expressed in voltamperes (VA). To select an appropriate isolation transformer, you must calculate the power required by the fixed I//O chassis and any input circuits and output loads that are connected through this transformer. The power requirement of any fixed I/O unit is 50 VA. The power requirement for the input circuits is determined by the number of inputs, the operating voltage, and the nominal input current. The power requirement for output loads is determined by the number of outputs, the load voltage, and load current. For example, if you have a 1747–L30B fixed unit with 18 AC inputs (12mA at 120 VAC) and 12 triac outputs (0.5A at 120 VAC), the power consumed would be: 50 + (18)(120)(0.012) + (12)(120)(0.5) = 796 VA
Important: In this case, 0.5 Amp is the maximum rating of the triac output (at +30° C). If your load draws less than 0.5 Amp, this figure may be reduced accordingly. The output portion of the VA calculation should reflect the current requirements of your loads. In general, we recommend that the transformer is oversized to provide some margin for line voltage variations and other factors. Typically a transformer that is 25% larger than the calculated VA is sufficient.
1–12
Page 32
Chapter 1 Selecting Your Hardware Components
Special Considerations
The recommendations given previously provide favorable operating conditions for most controller installations. Your application may involve one or more of the following adverse conditions. Additional measures can be taken to minimize the effect of these conditions.
Excessive Line Voltage Variations The best solution for excessive line voltage variation is to correct any feeder problems in your distribution system. Where this does not solve the line variation problem, or in certain critical applications, use a constant voltage transformer. If you require a constant voltage transformer, connect it to the power supply and all input devices connected to the SLC 500 controller. Connect output devices on the same power line, but their connection along the power line is normally made before the constant voltage transformer. A constant voltage transformer must have a sufficient power rating for its load.
Excessive Noise When you operate the SLC 500 controller in a “noise polluted” industrial environment, special consideration should be given to possible electrical interference. The following reduces the effect of electrical interference: • SLC 500 controller design features • proper mounting of controller within an enclosure • proper equipment grounding • proper routing of wiring • proper suppression added to noise generating devices Potential noise generators include inductive loads, such as relays, solenoids, and motor starters when operated by “hard contacts” like push buttons or selector switches. Suppression may be necessary when such loads are connected as output devices or when connected to the same supply line that powers the controller. Lack of surge suppression on inductive loads may attribute to processor faults and sporadic operation, RAM memory can be corrupted (lost) and I/O modules may appear to be faulty or reset themselves. For extremely noisy environments, use a memory module and program it for auto loading on processor fault or power cycle for quick recovery.
1–13
Page 33
Chapter 1 Selecting Your Hardware Components
Selecting Surge Suppressors Most output modules have built–in surge suppression to reduce the effects of high voltage transients. However, we recommend that you use an additional suppression device if an output module is being used to control an inductive device such as: • relays • motor starters • solenoids • motors Additional suppression is especially important if your inductive device is in series with or parallel to a hard contact such as: • pushbuttons • selector switches By adding a suppression device directly across the coil of an inductive device, you will reduce the effects of voltage transients caused by interrupting the current to that inductive device and prolong the life of the switch contacts. The diagram below shows an output module with a suppression device. + DC or L1 VAC/VDC OUT 0
Snubber
OUT 1 OUT 2
AC or DC Output Module
OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 COM
DC COM or L2
If you connect an SLC 500 controller triac output to control an inductive load, we recommend that you use varistors to suppress noise. Choose a varistor that is appropriate for the application. The surge suppression we recommend for triac outputs when switching 120 VAC inductive loads is Harris MOV, part number V220 MA2A. For a 509 motor starter, use a 599–K04 or 599–KA04 series C or later MOV with triac outputs. Consult the varistor manufacturer’s data sheet when selecting a varistor for your application.
! 1–14
ATTENTION: Damage could occur to SLC 500 triac outputs if you use suppressors having RC networks. Allen–Bradley AC surge suppressors not recommended for use with triacs include Catalog Numbers 199–FSMA1, 199–FSMA2, 1401–N10, and 700–N24.
Page 34
Chapter 1 Selecting Your Hardware Components
Allen–Bradley surge suppressors recommended for use with Allen–Bradley relays, contactors, and starters are shown in the table below. Device
Coil Voltage
Suppressor Catalog Number
Bulletin 509 Motor Starter Bulletin 509 Motor Starter
120 VAC 240 VAC
599-K04➀ 599-KA04➀
Bulletin 100 Contactor Bulletin 100 Contactor
120 VAC 240 VAC
199-FSMA1 ➁ 199-F5MA2 ➁
Bulletin 709 Motor Starter
120 VAC
1401-N10 ➁
Bulletin 700 Type R, RM Relays
AC coil
None Required
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
12 VDC 12 VDC
700-N22 700-N28
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
24 VDC 24 VDC
700-N10 700-N13
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
48 VDC 48 VDC
700-N16 700-N17
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
115-125 VDC 115-125 VDC
700-N11 700-N14
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
230-250 VDC 230-250 VDC
700-N12 700-N15
150V max, AC or DC
700-N24➁
Bulletin 700 Type N, P, or PK Relay Miscellaneous electromagnetic devices limited to 35 sealed VA
➀ This is an MOV without a capacitor. The 599-K04 or 599-KA04 MOV must be series C or later when used ➁ with triac outputs. Do not use series A or B with triac outputs. Not recommended for use with triac outputs.
1–15
Page 35
Chapter 1 Selecting Your Hardware Components
Selecting Contact Protection Inductive load devices such as motor starters and solenoids may require the use of some type of surge suppression to protect the controller output contacts. Switching inductive loads without surge suppression can significantly reduce lifetime of relay contacts. The figure below shows the use of surge suppression devices. Surge Suppression for Inductive AC Load Devices
Output Device
Output Device
Output Device Surge Suppressor
Varistor
RC Network
Surge Suppression for Inductive DC Load Devices
+ Output Device
Diode (A surge suppressor can also be used.)
Contact Protection Methods for Inductive AC and DC Output Devices
These surge suppression circuits connect directly across the load device. This reduces arcing of the output contacts. Suitable surge suppression methods for inductive AC load devices include a varistor, an RC network, or an Allen–Bradley surge suppressor. These components must be appropriately rated to suppress the switching transient characteristic of the particular inductive device. For inductive DC load devices, a diode is suitable. A 1N4004 diode is acceptable for most applications. A surge suppressor can also be used. See table on page 1–15. We recommend that you locate the suppression device as close as possible to the load device.
1–16
Page 36
Chapter 1 Selecting Your Hardware Components
Transistor Output Transient Pulses This section applies to the following SLC 500 Fixed I/O processors and SLC 500 I/O modules that have transistor outputs. Fixed I/O Processors
I/O Modules
1747-L20E
1746-OB8
1747-L20G
1746-OV8
1747-L20L
1746-OB16
1747-L20N
1746-OBP16
1747-L30L
1746-OV16
1747-L40E
1746-OB32
1747-L40L
1746-OV32
For the SLC 500 products listed above, the maximum duration of the transient pulse occurs when minimum load is connected to the output. However, for most applications the energy of the transient pulse is not sufficient to energize the load.
!
ATTENTION: A transient pulse occurs in transistor outputs when the external DC supply voltage is applied to the common output terminals (e.g., via the master control relay). The sudden application of voltage creates this transient pulse. (See the following graph.) This condition is inherent in transistor outputs and is common to solid state devices. A transient pulse can occur regardless of the processor having power or not.
Current
Transient (I)
(On-State Load Current)
Duration of Transient (T)
Time
1–17
Page 37
Chapter 1 Selecting Your Hardware Components
To reduce the possibility of inadvertent operation of devices connected to transistor outputs, adhere to the following guidelines: • Either ensure that any programmable device connected to the transistor output is programmed to ignore all output signals until after the transient pulse has ended, • or add an external resistor in parallel to the load to increase the on–state load current. The duration of the transient pulse is reduced when the on–state load current is increased. The duration of the transient pulse is proportional to the load impedance. This is illustrated in the following graph. 10 9
Time
Duration of Transient (ms)
8 7 6 5 4 3 2 1 0 1
100
200
300
400
500
600
On-State Load Current (mA)
1–18
700
800
900 1000
Page 38
Chapter 1 Selecting Your Hardware Components
Example Increasing the load current by 100mA decreases the transient time from approximately 7 ms to less than 2.5 ms. To calculate the size of the resistor added in parallel to increase the current, use the following information: 24V = your applied voltage Need 100mA of load current to reduce the transient to < 2.5 ms. (taken from graph on previous page) R (Ohms) =
V (Volts) I (Amps)
Resistor value (Ohms) = Applied voltage (Volts) / Desired current (Amps) = 24 / 0.1 = 240 (Ohms) P (Watts) = I2 (Amps) x R (Ohms) Actual Power (Watts) = (Desired Current)2 x Resistor Value = (0.1)2 x 240 = 2.4 (Watts) Resistor size = 2 x Actual power (Watts) = 2 x 2.4 = 4.8 (Watts) Round resistor size to 5 Watts.
You need a resistor rated for 240 Ohms at 5 Watts to increase the load current by 100mA; thus decreasing the transient time from approximately 7 ms to less than 2.5 ms.
1–19