Page 40

Chapter

2

System Installation Recommendations To help you install the SLC 500 programmable controller as safely and securely as possible, we have set up a few specific recommendations for you to follow. For general installation guidelines, also refer to article 70E of the National Fire Protection Association (NFPA). Article 70E describes electrical safety requirements for employee workplaces. This chapter covers the following: • typical installation • spacing your controllers • preventing excessive heat • grounding guidelines • master control relay • power considerations • safety considerations • preventative maintenance

Typical Installation

The figure below consists of some components that make up a typical installation. The following symbols are used:

1 1

NEMA rated enclosure suitable for your application and environment that shields your controller from electrical noise and airborne contaminants.

2 3

Disconnect, to remove power from the system Fused isolation transformer or a constant voltage transformer, as your application requires

4 5 6

Master control relay/emergency stop circuit Terminal blocks or wiring ducts Suppression devices for limiting EMI (electromagnetic interference) generation

2

4

Disconnect Device

MCR

6 3

Isolation Transformer

5 SLC 500 Controller

2–1

Page 41

Chapter 2 System Installation Recommendations

Spacing Your Components

Follow the recommended minimum spacing shown below to allow for convection cooling within the enclosure. Air in the enclosure must be kept within a range of 0° to +60° C (+32° to +140° F). Important: Be careful of metal chips when drilling mounting holes for the controllers. Do not drill holes above a mounted SLC 500 controller. Metal chips or clippings may short circuit electronic components of the controller and cause intermittent or permanent malfunction.

Greater than 152.4 mm (6 inches)

Greater than 101.6 mm (4 inches)

Greater than 101.6 mm (4 inches)

Enclosure Greater than 152.4 mm (6 inches)

Preventing Excessive Heat

For most applications, normal convection cooling will keep the controller components within the specified operating range. Proper spacing of components within the enclosure is usually sufficient for heat dissipation. In some applications, a substantial amount of heat is produced by other equipment inside or outside the enclosure. In this case, place blower fans inside the enclosure to assist in air circulation and to reduce “hot spots” near the controller. Additional cooling provisions might be necessary when high ambient temperatures are encountered. Important: Do not bring in unfiltered outside air. It may introduce harmful contaminants of dirt that could cause improper operation or damage to components. In extreme cases, you may need to use air conditioning to protect against heat build–up within the enclosure.

2–2

Page 42

Chapter 2 System Installation Recommendations

Grounding Guidelines

In solid–state control systems, grounding helps limit the effects of noise due to electromagnetic interference (EMI). The grounding path for the controller and its enclosure is provided by the equipment grounding conductor. Normal Electrical Noise Conditions

Severe Electrical Noise Conditions

#10 AWG to Ground Bus Chassis Mounting Tab

Ground Lug

Size 12 Internal Star Washer Chassis Mounting Tab

Size 12 Internal Star Washer

Size 12 Internal Star Washer Size 10 or 12 Hardware Screw

Size 10 or 12 Hardware Screw Tapped Hole (Minimum of Three Threads)

Scrape paint off panel to insure electrical connection between chassis and grounded metal panel.

Tapped Hole (Minimum of Three Metal Panel Threads) (Must be connected to earth Scrape paint off panel to insure Metal Panel (Must be connected to electrical connection between chassis ground.) and grounded metal panel. earth ground.)

!

ATTENTION: The SLC 500 controller, other control devices, and the enclosure must be properly grounded. All applicable codes and ordinances must be observed when wiring the controller system.

Ground connections should run from the chassis and power supply on each controller and expansion unit to the ground bus. Exact connections will differ between applications. An authoritative source on grounding requirements for most installations is the National Electrical Code. Also, refer to Allen–Bradley Programmable Controller Grounding and Wiring Guidelines, Publication Number 1770–4.1. In addition to the grounding required for the controller and its enclosure, you must also provide proper grounding for all controlled devices in your application. Care must be taken to provide each device with an acceptable grounding path.

2–3

Page 43

Chapter 2 System Installation Recommendations

The figure below shows you how to run ground connections from the chassis to the ground bus. SLC 500 Controller Only

#8 AWG Wire #10 AWG Wire

Ground Bus

Chassis Mounting Tabs Earth Ground SLC 500 Controller with 2-slot Expansion Chassis

#8 AWG Wire #10 AWG Wire

Ground Bus

Chassis Mounting Tabs Earth Ground

2–4

Page 44

Chapter 2 System Installation Recommendations

Master Control Relay

A hard–wired master control relay (MCR) provides a convenient means for emergency controller shutdown. Since the master control relay allows the placement of several emergency–stop switches in different locations, its installation is important from a safety standpoint. Overtravel limit switches or mushroom head push buttons are wired in series so that when any of them opens, the master control relay is de–energized. This removes power to input and output device circuits. Refer to the figure on page 2–6.

!

ATTENTION: Never alter these circuits to defeat their function, since serious injury and/or machine damage could result.

Important: If you are using a DC output power supply, interrupt the output side rather than the AC line to avoid the additional delay of power supply turn–on and turn–off. The power supply should receive its power directly from the fused secondary of the transformer. Connect the power to the DC input and output circuits through a set of master control relay contacts. Place the main power disconnect switch where operators and maintenance personnel have quick and easy access to it. If you mount a disconnect switch inside the controller enclosure, place the switch operating handle on the outside of the enclosure, so that you can disconnect power without opening the enclosure. Whenever any of the emergency–stop switches are opened, power to input and output devices is stopped. When you use the master control relay to remove power from the external I/O circuits, power continues to be provided to the controller’s power supply so that diagnostic indicators on the processor can still be observed. The master control relay is not a substitute for a disconnect to the controller. It is intended for any situation where the operator must quickly de–energize I/O devices only. When inspecting or installing terminal connections, replacing output fuses, or working on equipment within the enclosure, use the disconnect to shut off power to the rest of the system. Important: The operator must not control the master control relay with the SLC 500 controller. Provide the operator with the safety of a direct connection between an emergency–stop switch and the master control relay.

2–5

Page 45

Chapter 2 System Installation Recommendations

Emergency-Stop Switches Adhere to the following points concerning emergency–stop switches: • Do not program emergency–stop switches in the controller program. Any emergency–stop switch should turn off all machine power by turning off the master control relay. • Observe all applicable local codes concerning the placement and labeling of emergency–stop switches. • Install emergency–stop switches and the master control relay in your system. Make certain that relay contacts have a sufficient rating for your application. Emergency–stop switches must be easy to reach. The figure below shows the Master Control Relay Wired in Grounded System. L1

L2 230 VAC Disconnect Fuse

MCR 230 VAC I/O Circuits

Isolation Transformer X1

115 VAC Fuse

X2

Operation of either of these contacts will remove power from the controller external I/O circuits, stopping machine motion. Emergency-Stop Push Button

Overtravel Limit Switch

Master Control Relay (MCR) Cat. No. 700-PK400A1 Stop

Suppressor Cat. No. 700-N24

Start

MCR Suppr.

MCR MCR

115 VAC I/O Circuits DC Power Supply. Use N.E.C. Class 2 for UL Listing.

+ (Lo)

24 VDC I/O Circuits

(Hi)

Incoming Line Terminals. Connect to 115 VAC terminals of Power Supply.

2–6

MCR

Incoming line terminals. Connect to 24 VDC terminals of Power Supply.

Page 46

Chapter 2 System Installation Recommendations

Power Considerations

The following explains power considerations for the SLC 500 fixed controller.

Common Power Source We strongly recommend that the chassis power supply has the same power source as the input and output devices. This helps: • reduce the chance of electrical interference due to multiple sources and grounds • maintain system integrity if power is interrupted

Loss of Power Source The chassis power supply is designed to withstand brief power losses without affecting the operation of the system. The time the system is operational during power loss is called “program scan hold–up time after loss of power.” The duration of the power supply hold–up time depends on the number, type and state of the I/O, but is typically between 20 ms and 700 ms. When the duration of power loss reaches a limit, the power supply signals the processor that it can no longer provide adequate DC power to the system. This is referred to as a power supply shutdown. The POWER LED is turned off.

Input States on Power Down The power supply hold–up time as described above is generally longer than the turn–on and turn–off times of the input circuits. Because of this, the input state change from “On” to “Off” that occurs when power is removed may be recorded by the processor before the power supply shuts down the system. Understanding this concept is important. The user program should be written to take this effect into account. For example, hard wire power to one spare input. In the user program, check to be sure that one input is on; otherwise, jump to the end of the program and avoid scanning the logic. Use of a common power source as recommended in the previous section is assumed.

Other Types of Line Conditions Occasionally the power source to the system can be temporarily interrupted. It is also possible that the voltage level drops substantially below the normal line voltage range for a period of time. Both of these conditions are considered to be a loss of power for the system.

2–7

Page 47

Chapter 2 System Installation Recommendations

Safety Considerations

Safety considerations are an important element of proper system installation. Actively thinking about the safety of yourself and others, as well as the condition of your equipment, is of primary importance. Several safety areas are discussed below.

High Voltages SLC 500 Fixed Hardware Style Controller (Series C) (Applies to 1747-L20A, -L30A, -L40A, -L20C, -L30C, and -L40C controllers)

Front Cover

!

ATTENTION: The printed circuit board, located under the front cover of Series C Fixed Hardware Style Controllers, has high voltages (120 VAC and 240 VAC) available at certain points when the controller is powered up. If the front cover is removed, exercise extreme care and consider all points on the circuit board to be electrically hazardous. Therefore, whenever possible, turn off power to the controller before removing the front cover. Do not remove the protective insulation covering the circuit board. Cutouts in the insulation are provided to allow access to the high–speed counter jumper, memory module, and battery connector. If the insulation is missing, do not touch any portion of the circuit board. Failure to heed this warning may result in personal injury or death.

Disconnecting Main Power The main power disconnect switch should be located where operators and maintenance personnel have quick and easy access to it. Ideally, the disconnect switch is mounted on the outside of the enclosure, so that it can be accessed without opening the enclosure. In addition to disconnecting electrical power, all other sources of power (pneumatic and hydraulic) should be de–energized before working on a machine or process controlled by an SLC controller.

2–8

Page 48

Chapter 2 System Installation Recommendations

Wiring Safety Circuits Circuits installed on the machine for safety reasons, like overtravel limit switches, stop push buttons, and interlocks, should always be hard–wired directly to the master control relay. These devices must be wired in series so that when any one device opens, the master control relay is de–energized thereby removing power to the machine. Never alter these circuits to defeat their function. Serious injury or machine damage could result.

Distributing Power There are some points about power distribution that you should be aware of. First, the master control relay must be able to inhibit all machine motion by removing power to the machine I/O devices when the relay is de–energized. Second, if you are using a DC power supply, interrupt the load side rather than the AC line power. This avoids the additional delay of power supply turn–on and turn–off. The DC power supply should be powered directly from the fused secondary of the transformer. Power to the DC input and output circuits is connected through a set of master control relay contacts.

Testing the Master Control Relay Circuit Any part can fail, including the switches in a master control relay circuit. The failure of one of these switches would most likely cause an open circuit, which would be a safe power–off failure. However, if one of these switches shorts out, it no longer provides any safety protection. These switches should be tested periodically to assure they will stop machine motion when needed.

Preventive Maintenance

The printed circuit boards of the controller must be protected from dirt, oil, moisture, and other airborne contaminants. To protect these boards, the controller must be installed in an enclosure suitable for the environment. The interior of the enclosure should be kept clean and the enclosure door should be kept closed whenever possible. Regularly inspect your terminal connections for tightness. Loose connections may cause improper functioning of the controller or damage the components of the system.

!

ATTENTION: To ensure personal safety and to guard against damaging equipment, inspect connections with incoming power off.

The National Fire Protection Association (NFPA) provides recommendations for electrical equipment maintenance. Refer to article 70B of the NFPA for general requirements regarding safety related work practices. 2–9