Direct Communication Module (Cat. No. 1747-DCM) User Manual: 1 - Overview

Pages 15 to 20 of 80, from Direct Communication Module (Cat. No. 1747-DCM) User Manual

The original document is the PDF (429 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-DCM

Page 15

Chapter

1

Overview This chapter provides a hardware and system overview including physical features and connectivity illustrations. It also explains data exchange between processors and discusses rack size. Topics include: • hardware overview • system overview • scanner image division • communications flow

Hardware Overview

FAULT LED (Red)

The Direct Communication Module, Catalog Number 1747–DCM, is used to connect an SLC 500 Fixed Programmable Controller with expansion chassis or any SLC 500 Modular Programmable Controller to a supervisory Allen–Bradley Programmable Controller via the RIO Link, thereby providing a distributed processing system. The DCM occupies one slot in any SLC 500 chassis. Self–Locking Tab Side Label DIP Switches DCM SW1 1 2 3 4 5 6 7 8

SW1

DATA RATE (K B/S) 57.6 115.2 230.4

(LSB) RACK ADDRESS

(MSB) O N

FIRST I/O GROUP 0 2 4 6

SW2

Front Label

RACK SIZE 1/4 1/2 3/4 1

I/O GROUP

X X RACK SIZE LAST RACK CLR ON FLT

SW 1 I/O GROUP (LSB) RACK ADDR

SW2

DATA RATE

(MSB)

8 7 6 5 4 3 2 1

O N

RIO Link Connector

1 2 3 4 5 6 7 8

Door Label

1 2 3 4 5 6 7 8

CONFIGURATION RACK ADDR

1 2 3 4 5 6 7 8

COMM

COMM LED (Green)

SLC 500 DIRECT COMMUNICATION CATMODULE

SERIAL NO.

FAULT

SW 2

LINE 1 _______

8 7 6 5 LAST RACK 4 CLR ON FLT 3 DATA 2 RATE 1 X X RACK SIZE

SHIELD ______ LINE 2 _______ MADE IN USA

Cable Tie Slots 1747–DCM

Self–Locking Tab Hardware Features Hardware

Function

FAULT LED

Displays operating status

COMM LED

Displays communication status

Front, Side and Door Labels

Provide module configuration information

RIO Link Connector

Provides physical connection to RIO network

Cable Tie Slots

Secure and route wiring from module

DIP Switches

Establish configuration parameters for the module

Self–Locking Tabs

Secure module in chassis slot

1–1

Page 16

Chapter 1 Overview

System Overview

The Direct Communication Module is an SLC 500 family Remote I/O (RIO) adapter. It allows supervisory processors, such as PLC–5s, and distributed SLC–500 processors residing on an Allen–Bradley RIO Communication Link to transfer data between each other. The DCM appears as an RIO adapter to: • a PLC processor with integral RIO scanner on the RIO Communication Link • an RIO scanner, Catalog Number 1771–SN or 1747–SN, on the RIO Communication Link RIO Scanner

Distributed SLCs with DCMs (adapters)

Supervisory PLC or SLC

DCM 1

PanelViewt (adapter) DCM 2

DCM 3 RIO Communication Link

DCM modules are connected in a daisy–chain configuration using Belden 9463 cable.

What Is a Remote I/O Adapter? A remote I/O adapter (RIO adapter) is any module that acts as a slave to an RIO scanner, the master on the RIO link. The DCM is an RIO adapter. All RIO scanners have defined physical and logical specifications. Physical specifications are the maximum number of adapters that can be connected to the scanner. (See Extended Node Capability on page 1–4.) Logical specifications are the maximum number of logical racks the scanner can address, the ways logical racks can be assigned, and the ability of the scanner to perform block transfers. Refer to the appropriate scanner manual for details concerning physical and logical specifications. The DCM can physically reside on the RIO link with any other adapter. The following table lists the adapters available for use with an RIO link.

1–2

Page 17

Chapter 1 Overview

Compatible Adapters Catalog Number

Device

Extended Node Capability

Comments

1785-LT/x

PLC-5/15

Yes

In adapter mode

1785-LT2

PLC-5/25

Yes

In adapter mode

1785-LT3

PLC-5/12

Yes

In adapter mode

1785-L30x

PLC-5/30

Yes

In adapter mode

1785-L40x

PLC-5/40

Yes

In adapter mode

1785-L60x

PLC-5/60

Yes

In adapter mode

1771-ASC

Remote I/O Adapter Module

No

1771-ASB

Remote I/O Adapter Module

Series B and C only

1771-AM1

1-Slot I/O Chassis with Integral Power Supply and Adapter

Yes

1771-AM2

2-Slot I/O Chassis with Integral Power Supply and Adapter

Yes

1784-F30D

Plant Floor Terminal Remote I/O Expansion Module

Yes

1771-RIO

Remote I/O Interface Module

No

1771-JAB

Single Point I/O Adapter Module

Yes

1771-DCM

Direct Communication Module

No

1778-ASB

Remote I/O Adapter Module

Yes

1747-ASB

Remote I/O Adapter Module

Yes

2706-xxxx

DL40 Datalinert

Yes

2705-xxx

RediPANELt

Yes

2711-xx

PanelView Terminal

Yes

1336-RIO

Remote I/O Adapter for 1336 AC Industrial Drives

Yes

1395-NA

Remote I/O Adapter for 1395 DC Industrial Drives

Yes

1747-ASB

SLC 500 Remote I/O Adapter Module

Yes

Series A, B, and C

Must be catalog number 2706-ExxxxxB1.

1–3

Page 18

Chapter 1 Overview

Extended Node Capability Both scanners and adapters can have extended node capability. Extended node capability allows you to have up to 32 adapters on the RIO link using an 82 Ohm termination resistor at both ends of the RIO link for all baud rates. Extended node capability can only be used if the scanner and all adapters on the RIO link have extended node capability. The DCM has extended node capability.

Scanner Image Division

The scanner allows each adapter to use a fixed amount (user defined) of its input and output image. The scanner image is divided into logical racks and further divided into logical groups. A full logical rack consists of eight input and eight output image words. A logical group consists of one input and one output word in a logical rack. Each logical group is assigned a number from 0–7. The number of racks available for data and I/O transfer depends on the scanner you are using.

Local I/O

Logical Rack 0

Remote I/O

Logical Rack 1

(Scanner Image)

Logical Rack 2 Logical Group 0 Logical Rack 3 Logical Group 7

Processor I/O Image

Scanner I/O Image

Adapter Image

The scanner image also contains the image of each adapter on the RIO link. The adapter is assigned a portion of the scanner image, which is referred to as the adapter image.

1–4

Page 19

Chapter 1 Overview

Scanner Image Division Configuration Example The example presented here can help you configure your RIO architecture. Refer to it as necessary. The following figure shows how a portion of a scanner’s input image table might be configured. An output image table would be identically configured.

Decimal Bit Number

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Octal Bit Number

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Rack 0 Group 0

Logical Rack 0

Rack 0 Group 1

Word 1

Rack 0 Group 2

Word 2

Rack 0 Group 3

Word 3

Rack 0 Group 4

Word 4

Rack 0 Group 5

Word 5 Word 6

Rack 0 Group 6

Logical Rack 1

Logical Rack 2

Word 0

Rack 0 Group 7

Word 7

Rack 1 Group 0

Word 8

Device 1 (Full logical rack)

Rack 1 Group 1

Word 9

Rack 1 Group 2

Word 10

Device 2

Rack 1 Group 3

Word 11

(3/4 logical rack)

Rack 1 Group 4

Word 12

Rack 1 Group 5

Word 13

Rack 1 Group 6 Rack 1 Group 7 Rack 2 Group 0

Word 14 Word 15 Word 16

Device 3 (1/4 logical rack)

Rack 2 Group 1

Word 17

Device 4

Rack 2 Group 2

Word 18

(1/2 logical rack)

Rack 2 Group 3

Word 19

Rack 2 Group 4 Rack 2 Group 5

Word 20 Word 21

Device 5

Rack 2 Group 6

Word 22

(1/2 logical rack)

Rack 2 Group 7

Word 23

Important: The configured image size of a DCM cannot cross logical rack boundaries; it cannot use a portion of rack 0 and a portion of rack 1.

1–5

Page 20

Chapter 1 Overview

Data Exchange Between RIO Scanners and the DCM

Information is transferred between the RIO scanner and the DCM every RIO scan. RIO transmissions are asynchronous to the processor scans. Important: The DCM provides word integrity on all words transferred via the SLC backplane. The DCM communicates with supervisory PLC or SLC controllers through RIO scanners, as if they were addressing a logical rack. However, the DCM does not scan the I/O in its local I/O chassis, rather it passes the supervisory data to the distributed SLC processor. In the DCM, outputs from the SLC output image table are inputs to the supervisory processor input image table. Likewise, outputs from the supervisory processor output image table are inputs to the SLC input image table. The diagram that follows depicts the communications flow between an RIO scanner and the DCM. Distributed Processor Scan

Processor Scan SLC Distributed Processor DCM Supervisory PLC or SLC

I/O Module

I/O Module

Scanner RIO Scan

Outputs from PLC, Input Data to DCM SLC Chassis Inputs to PLC, Output Data from DCM Inputs to Modules

SLC Expansion Chassis Outputs from Modules Output Device

Input Device

What Is the Status Word? The first word of the DCM input and output image is the status word. The status word indicates the status of communication and data between the RIO scanner and the DCM. For more information on status words and their applications, see chapter 6, Programming.