Direct Communication Module (Cat. No. 1747-DCM) User Manual: 2 - Quick Start for Experienced Users

Pages 21 to 24 of 80, from Direct Communication Module (Cat. No. 1747-DCM) User Manual

The original document is the PDF (429 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-DCM

Page 21

Chapter

2

Quick Start for Experienced Users This chapter helps you to get started using the Direct Communication Module (DCM). We base the procedures here on the assumption that you have a basic understanding of SLC 500 products. You must: • understand electronic process control • be able to interpret the ladder logic instructions for generating the electronic signals that control your application Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more detailed information. It also references other documentation that may be helpful if you are unfamiliar with programming techniques or system installation requirements. If you have any questions, or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information. This chapter: • tells you what tools and equipment you need • lists preliminary considerations • describes when to address, configure and program the module • explains how to install and wire the module • discusses system power-up procedures

Required Tools and Equipment

Have the following tools and equipment ready: • medium blade screwdriver • (2) 1/2 watt terminating resistors (See chapter 5, Installation and Wiring, for correct size.) • programming equipment (All programming examples shown in this manual demonstrate the use of Allen-Bradley’s Advanced Programming Software [APS] for personal computers.)

2–1

Page 22

Chapter 2 Quick Start for Experienced Users

Procedures Check the contents of the shipping box.

1.

Reference

Unpack the module making sure that the contents include:

• • • •

Direct Communication Module (Catalog Number 1747-DCM) removable connector (factory-installed on module) – cable tie user manual (Catalog Number 1747-NM007)

If the contents are incomplete, call your local Allen-Bradley representative for assistance. 2. 2.

Select a scanner.

Reference

To begin configuration of your RIO system, you should know three things:

• which scanner is compatible with your PLC/SLC controller. Use the table below to select a scanner that is compatible with your processor. The DCM is compatible with all RIO scanners.

The manual for the scanner you select

Description

Catalog Number 1747-SN➀

SLC Remote I/O Scanner

1771-SN➁

Sub I/O scanner for Mini–PLC-2r and PLC-5 families

1772-SD, -SD2➂➃

Remote scanner/distribution panel for PLC-2 family

1775-S4A, -S4B, -S5➀

I/O scanner-programmer interface module for PLC-3r family

1775-SR, -SR5➀

Remote scanner/distribution panel for PLC-3/10 family

1785-L11B➀

PLC 5/11t (in scanner mode)

1785-LT/x➀➄

PLC 5/15 (in scanner mode)

1785-L20B➀

PLC 5/20t (in scanner mode)

1785-LT2➀➄

PLC 5/25 (in scanner mode)

1785-L30x➀

PLC 5/30t (in scanner mode)

1785-L40x➀

PLC 5/40t (in scanner mode)

1785-L60x➀

PLC 5/60t (in scanner mode)

5250-RS➀

Remote scanner for PLC 5/250

6008-SI➀

IBMr PC I/O Scanner Module

6008-SV➀

VMEbus I/O Scanner Module

6008-SQH1, -SQH2

Q-bus I/O Scanner Module

➀

Extended node capability.

➁

Revision D or later. ➂ Rev. 3 or later.

2–2

➃

Extended node capability not available with Series A.

➄

Rev. 3 or later.PLC 5/15 Series B Revision H or later have partial rack addressing. Earlier versions are limited to 3 devices. PLC 5/25 Series A Revision D or later have partial rack addressing. Earlier versions are limited to 7 devices.

Page 23

Chapter 2 Quick Start for Experienced Users

• • the maximum number of physical devices and logical racks your scanner supports. the logical rack size of each DCM. This depends on how many I/O data words you need to transfer. The first word is always the status word. The table below shows the number of data words transferred relative to the rack size.

If you configure the DCM as:

Then:

Including the Status Word

1/4 Rack

1 data word (16 bits of I/O data) are transferred.

Total transfer = 2 words

1/2 Rack

3 data words (48 bits of I/O data) are transferred.

Total transfer = 4 words

3/4 Rack

5 data words (80 bits of I/O data) are transferred.

Total transfer = 6 words

Full Rack

7 data words (112 bits of I/O data) are transferred.

Total transfer = 8 words

Choose the type of slot addressing you will use.

3.

Select DCM addressing. (A configuration worksheet is included in appendix B to assist you in DCM image table addressing.)

Configure the module using the DIP switches.

4.

!

Chapter 3 (Addressing) Appendix B (DCM Worksheet) Reference Chapter 4 (Module Configuration)

Configure your system by setting the DIP switches.

5.

Reference

Insert the 1747-DCM module into the chassis.

Reference

ATTENTION: Never install, remove, or wire modules with power applied to the chassis or devices wired to the module.

Chapter 5 (Installation and Wiring)

Review SLC/DCM power requirements to ensure your SLC power supply has adequate reserve power. Make sure system power is off; then insert the DCM into your 1746 chassis. In this example procedure, local slot 1 is selected.

Module Release

Card Guide

. Cable Tie

2–3

Page 24

Chapter 2 Quick Start for Experienced Users

To wire the network, a 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each end (scanner and last physical device) of the network. The size of the resistor depends on the baud rate and extended node capability, as shown below: Baud Rate Using Extended Node Capability Not Using Extended Node Capability

6.

Maximum Cable Distance (Belden 9463)

57.6K baud 115.2K baud 230.4K baud 57.6K baud 115.2K baud

3048 meters (10,000 feet) 1524 meters (5,000 feet) 762 meters (2,500 feet) 3048 meters (10,000 feet) 1524 meters (5,000 feet)

230.4K baud

762 meters (2,500 feet)

Resistor Size 82W 1/2 Watt Brown–Green–Brown–Gold 150W 1/2 Watt Brown–Green–Brown–Gold 82W 1/2 Watt Gray–Red–Black–Gold

Enter your ladder program.

Define the application requirements. Write and enter the ladder logic program.

7.

Go through the system start-up procedure.

Power up your system by performing standard start-up procedures as indicated in your processor manual. No special start-up procedures are required when using the DCM module.

2–4

Reference Chapter 6 (Programming) Chapter 8 (Application Examples) Reference –