Direct Communication Module (Cat. No. 1747-DCM) User Manual: 4 - Module Configuration

Pages 31 to 38 of 80, from Direct Communication Module (Cat. No. 1747-DCM) User Manual

The original document is the PDF (429 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-DCM

Page 31

Chapter

4

Module Configuration This chapter provides DIP switch setting information for the DCM. Topics include: • DIP switches • DIP switch 1 settings • DIP switch 2 settings

O 1 N

SW1

DIP Switch 2 (SW2)

1 2 3 4 5 6 7 8

SW1

Rack Address

DIP Switch 1 (SW1)

1 2 3 4 5 6 7 8

Starting I/O Group Number

2 3 4 5 6 7 8

To configure the DCM for your application, you must set the DIP switches. These switches enable the DCM to properly interpret the RIO system addressing. The DCM has two banks of DIP switches mounted on its circuit board. Each bank contains eight switches. The default settings are shown below.

Rack Size Last Rack Clear On Fault Data Rate

1 2 3 4 5 6 7 8

SW2

Reserved

O N

DIP Switches

SW2

4–1

Page 32

Chapter 4 Module Configuration

DIP Switch 1 Settings

Starting I/O Group Number (SW1-7 and SW1-8) The starting I/O group number is the first word assigned to the DCM from the scanner’s image table. The starting I/O group number must be an even number from 0 to 6 and is dependent upon whether the DCM has been configured as a full, 3/4, 1/2, or 1/4 rack. The first word transferred is always the status word for the DCM. Rack Size

Number of RIO Words Transferred

Total Words

1/4 Logical Rack

1 Status and 1 Data

2

1/2 Logical Rack

1 Status and 3 Data

4

3/4 Logical Rack

1 Status and 5 Data

6

Full Logical Rack

1 Status and 7 Data

8

Reference the table below to set the starting I/O group number. Starting I/O Group Number

SW1-7

SW1-8

Valid Rack Configuration

0

ON

ON

All

2

ON

OFF

3/4, 1/2, 1/4

4

OFF

ON

1/2, 1/4

6

OFF

OFF

1/4

Example of different starting groups: Bit Number:

Starting Group 0

Octal Decimal

Group 0, Word 0

17 16 15 14 13 12 11 10 7 15 14 13 12 11 10 9 8 7

6 6

5 5

4 4

3 3

R R

S

T

A

T

U

S

W O R

D

S

T

A

T

U

S

W O R

D

Group 1, Word 1

Starting Group 2

Group 2, Word 2 Group 3, Word 3

2 2

1 1

0 0

DCM 1 Rack Size = 1/4 Rack DCM 2 Rack Size = 1/2 Rack

Group 4, Word 4 Group 5, Word 5

Starting Group 6

Group 6, Word 6 Group 7, Word 7

S

T

A

T

U

S

W O R

D

DCM 3 Rack Size = 1/4 Rack

In the above image map example, selecting I/O Group Number 2 instructs the scanner to address Word 2 as the beginning of DCM 2 image. In this example, a half rack is selected for DCM 2 (using SW2 switches 5 and 6). Since Word 2 is the first word assigned, it becomes the Status Word.

4–2

Page 33

Chapter 4 Module Configuration

Rack Address (SW1-1 through SW1-6) The rack address refers to the logical rack number from the scanner image that contains a particular DCMs image. The table on page 4–4 gives the switch settings that define possible rack address choices for all scanners. To use this table, first determine which of the following categories applies to your scanner: • PLC-2, mini PLCs, PLC-2/30 with 1772-SD, SD2 remote scanner • PLC-3 and PLC-5/250 processors. (This category includes those with built-in scanners, as well as the following without built-in scanners: catalog numbers 1775-54A, -54B, -S5, -SR, -SR5 and 5250-RS.) • PLC-5/11, PLC-5/15, PLC-5/20, PLC-5/25, PLC-5/30, PLC-5/40, or PLC-5/60 and 1771-SN. (This category includes all smaller in-rack processors and standalone scanners that have local and remote I/O and begin rack addressing at rack 1.) • SLC-5/02 (or above) with 1747-SN scanner After determining which category applies to your DCM application: 1. Find the column for the scanner used in your application. 2. Go down the column to the rack address that you assigned to the DCM. 3. Use the switch settings in the right-most columns of the table that correspond to your rack address.

4–3

Page 34

Chapter 4 Module Configuration

Use this table to set SW1 – switches 1 through 6. Logical Rack Number (Octal)

Switch Number (SW1)

1747SN

PLC2

PLC3

PLC5/15

PLC5/25

PLC5/40

PLC5/60

PLC5/250

1

2

3

4

5

6

0

1

0

–

–

–

–

0

ON

ON

ON

ON

ON

ON

1

2

1

1

1

1

1

1

ON

ON

ON

ON

ON

OFF

2

3

2

2

2

2

2

2

ON

ON

ON

ON

OFF

ON

3

4

3

3

3

3

3

3

ON

ON

ON

ON

OFF

OFF

5

4

4

4

4

4

ON

ON

ON

OFF

ON

ON

6

5

5

5

5

5

ON

ON

ON

OFF

ON

OFF

7

6

6

6

6

6

ON

ON

ON

OFF

OFF

ON

7

7

7

7

7

ON

ON

ON

OFF

OFF

OFF

10

10

10

10

ON

ON

OFF

ON

ON

ON

11

11

11

11

ON

ON

OFF

ON

ON

OFF

12

12

12

12

ON

ON

OFF

ON

OFF

ON

13

13

13

13

ON

ON

OFF

ON

OFF

OFF

14

14

14

14

ON

ON

OFF

OFF

ON

ON

15

15

15

15

ON

ON

OFF

OFF

ON

OFF

16

16

16

16

ON

ON

OFF

OFF

OFF

ON

17

17

17

17

ON

ON

OFF

OFF

OFF

OFF

20

20

20

ON

OFF

ON

ON

ON

ON

21

21

21

ON

OFF

ON

ON

ON

OFF

22

22

22

ON

OFF

ON

ON

OFF

ON

23

23

23

ON

OFF

ON

ON

OFF

OFF

24

24

24

ON

OFF

ON

OFF

ON

ON

25

25

25

ON

OFF

ON

OFF

ON

OFF

26

26

26

ON

OFF

ON

OFF

OFF

ON

27

27

27

ON

OFF

ON

OFF

OFF

OFF

30

30

ON

OFF

OFF

ON

ON

ON

31

31

ON

OFF

OFF

ON

ON

OFF

32

32

ON

OFF

OFF

ON

OFF

ON

33

33

ON

OFF

OFF

ON

OFF

OFF

34

34

ON

OFF

OFF

OFF

ON

ON

35

35

ON

OFF

OFF

OFF

ON

OFF

36

36

ON

OFF

OFF

OFF

OFF

ON

37

37

ON

OFF

OFF

OFF

OFF

OFF

40

OFF

ON

ON

ON

ON

ON

41

OFF

ON

ON

ON

ON

OFF

42

OFF

ON

ON

ON

OFF

ON

43

OFF

ON

ON

ON

OFF

OFF

44

OFF

ON

ON

OFF

ON

ON

Continued on next page.

4–4

Page 35

Chapter 4 Module Configuration

1747SN

PLC2

PLC3

PLC5/15

PLC5/25

PLC5/40

PLC5/60

PLC5/250

1

2

3

4

5

6

45

OFF

ON

ON

OFF

ON

OFF

46

OFF

ON

ON

OFF

OFF

ON

47

OFF

ON

ON

OFF

OFF

OFF

50

OFF

ON

OFF

ON

ON

ON

51

OFF

ON

OFF

ON

ON

OFF

52

OFF

ON

OFF

ON

OFF

ON

53

OFF

ON

OFF

ON

OFF

OFF

54

OFF

ON

OFF

OFF

ON

ON

55

OFF

ON

OFF

OFF

ON

OFF

56

OFF

ON

OFF

OFF

OFF

ON

57

OFF

ON

OFF

OFF

OFF

OFF

60

OFF

OFF

ON

ON

ON

ON

61

OFF

OFF

ON

ON

ON

OFF

62

OFF

OFF

ON

ON

OFF

ON

63

OFF

OFF

ON

ON

OFF

OFF

64

OFF

OFF

ON

OFF

ON

ON

65

OFF

OFF

ON

OFF

ON

OFF

66

OFF

OFF

ON

OFF

OFF

ON

67

OFF

OFF

ON

OFF

OFF

OFF

70

OFF

OFF

OFF

ON

ON

ON

71

OFF

OFF

OFF

ON

ON

OFF

72

OFF

OFF

OFF

ON

OFF

ON

73

OFF

OFF

OFF

ON

OFF

OFF

74

OFF

OFF

OFF

OFF

ON

ON

75

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

ON

76 77

77

77

77

77

77

77

77

Reserved

4–5

Page 36

Chapter 4 Module Configuration

DIP Switch 2 Settings

Rack Size (SW2-5 and SW2-6) The logical rack size allocates image space in the scanner for each DCMs I/O data. The DCM allows 1/4, 1/2, 3/4, and full rack addressing. SW2 switches 5 and 6 define the rack size. Rack Size

SW2-5

SW2-6

1/4 Logical Rack

ON

ON

1/2 Logical Rack

ON

OFF

3/4 Logical Rack

OFF

ON

Full Logical Rack

OFF

OFF

Important: The DCM image cannot cross logical rack boundaries. Therefore, as an example, configuring the module for 1/2 logical rack with starting group 6 will cause a configuration error. Refer to Starting I/O Group Number on page 4–2.

Last Rack (SW2-4) Switch 4 of SW2 must be set to the OFF position if the DCM shares its logical rack with at least one other adapter and has been assigned the highest I/O group number in that logical rack. Last Rack

SW2-4

Yes

OFF

No

ON Direct Communications Module 1

Remote I/O Scanner

Module 1 Configured As: Logical Rack Address 1 I/O Group 0 Module Rack Size 1/4

SLC Output Image (to the PLC) Bit Number:

Decimal Octal

Module 1 Logical Rack 1

Module 2

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

17 16 15 14 13 12 11 10 7

6

5

4

3

2

1

0

Group 0, Word 0 Group 1, Word 1 Group 2, Word 2 Group 3, Word 3 Group 4, Word 4

Module 3 Module 4

Module 2 Configured As: Logical Rack Address 1 I/O Group 2 Module Rack Size 1/4

Module 3 Configured As: Logical Rack Address 1 I/O Group 4 Module Rack Size 1/4

Group 5, Word 5 Group 6, Word 6 Group 7, Word 7

Module 4 is the last device in the logical rack. Because Module 4 is the last RIO adapter in a logical rack shared by other adapter(s), SW2 switch 4 must be in the OFF position.

4–6

Module 4 Configured As: Logical Rack Address 1 I/O Group 6 Module Rack Size 1/4

Page 37

Chapter 4 Module Configuration

Clear On Fault (SW2-3) ATTENTION: Before setting SW2-3 to ON, make sure that holding all DCM input bits in their last state, in the event a communication error occurs, does not create an unsafe condition in the distributed SLC processor.

!

Clear On Fault

SW2-3

Yes

OFF

No

ON

Turn switch to OFF position if you want the DCM to clear and hold clear all data bits in its input image table, in the event of an RIO communication failure or when the supervisory processor enters Program/Test/Fault Mode. Status bits will not be cleared. Turn switch to ON position if you want the DCM to hold all input data bits in their last state when an RIO communication failure occurs or when the supervisory processor enters Program/Test/Fault Mode.

Data Rate (SW2-1 and SW2-2) Data Rate

SW2-1

SW2-2

Cable Length (Belden 9463)

57.6K baud

ON

ON

3048 meters (10,000 feet)

115.2K baud

ON

OFF

1524 meters (5,000 feet)

OFF

ON

OFF

OFF

230.4K baud

762 meters (2,500 feet)

4–7

Page 38