Direct Communication Module (Cat. No. 1747-DCM) User Manual: 5 - Installation and Wiring

Pages 39 to 42 of 80, from Direct Communication Module (Cat. No. 1747-DCM) User Manual

The original document is the PDF (429 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-DCM

Page 39

Chapter

5

Installation and Wiring This chapter explains how to install the DCM into the SLC chassis and provides information about terminal wiring. Topics include: • DCM installation • network wiring

Compliance to European Union Directives

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2 EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

DCM Installation

Installation procedures for this module are the same as for any other discrete I/O or specialty module. Refer to the illustration on page 5–2 to identify chassis and module components listed in the procedures below.

!

ATTENTION: Disconnect power before attempting to install, remove, or wire the DCM.

Important: Make sure you have set the DIP switches properly before installing the DCM. Before installation make sure your modular SLC power supply has adequate reserve current capacity. The DCM requires 360mA @ 5 volts. Each Fixed SLC 500 controller can support up to one DCM in a 2-slot expansion chassis, depending on which I/O module is in the second slot. Refer to the Discrete I/O Modules Product Data, Publication Number 1746-2.35.

5–1

Page 40

Chapter 5 Installation and Wiring

Installation 1. Disconnect power. 2. Align the full-sized circuit board with the chassis card guides. The first slot (slot 0) of the first rack is reserved for the CPU. 3. Slide the module into the chassis until the top and bottom latches are latched. 4. Attach the RIO link cable to the connector on the front of the module behind the door. 5. Insert the cable tie in the slots. 6. Route the cable down and away from module, securing it with the cable tie. 7. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.

Module Release

Card Guide

.. .

Cable Tie

19627

Removal 1. Disconnect power. 2. Press the releases at the top and bottom of the module and slide the module out of the chassis slot. 3. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.

5–2

Page 41

Chapter 5 Installation and Wiring

Network Wiring

A 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each end (scanner and last physical device) of the network. The size of the resistor depends upon the baud rate and extended node capability, as shown below: Baud Rate

Terminating Resistor Size

Using Extended Node Capability

All Baud Rates

82W 1/2 Watt

Not Using Extended Node Capability

57.6K baud 115.2K baud 230.4K baud

150W 1/2 Watt 150W 1/2 Watt 82W 1/2 Watt

Maximum Cable Distance (Belden 9463) 10,000 feet at 57.6K baud 5,000 feet at 115.2K baud 2,500 feet at 230.4K baud 3048 meters (10,000 feet) 1524 meters (5,000 feet) 762 meters (2,500 feet)

Terminating Resistor Line 1 – Blue Shield – Shield

RIO Scanner

DCM

Line 2 – Clear

FAULT

CONFIGURATION SW1

RACK ADDR

RACK SIZE 1/4 1/2 3/4 1

(MSB)

SW2

1 2 3 4 5 6 7 8

DATA RATE (K B/S) 57.6 115.2 230.4

(LSB) RACK ADDRESS

X X RACK SIZE LAST RACK CLR ON FLT

DATA RATE

Line 1 – Blue

1747-DCM Shield – Shield Direct Communication Module Line 2 – Clear

O N

RIO Link Connector

I/O GROUP

O N

FIRST I/O GROUP 0 2 4 6

1 2 3 4 5 6 7 8

COMM

LINE 1 _______ SHIELD ______ LINE 2 _______

1747–DCM

Line 1 – Blue

1747-DCM Shield – Shield Direct Communication Module Line 2 – Clear Terminating Resistor

5–3