The text of a manual · part 31 of 55
Hand-Held Terminal (Catalog Number 1747-PT1) User Manual: 19 - Comparison Instructions
Pages 267 to 276 of 486, from Hand-Held Terminal (Catalog Number 1747-PT1) User Manual
The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-PT1
Page 267
Chapter
A–B
19
Comparison Instructions This chapter covers input instructions that allow you to compare values of data. Instructions for use with fixed, SLC 5/01, and SLC 5/02 processors: • Equal (EQU) • Not Equal (NEQ) • Less Than (LES) • Less Than or Equal (LEQ) • Greater Than (GRT) • Greater Than or Equal (GEQ) • Masked Comparison for Equal (MEQ) Instruction for use with SLC 5/02 processors only • Limit (LIM)
Comparison Instructions Overview
The following general information applies to comparison instructions.
Indexed Word Addresses With SLC 5/02 processors, you have the option of using indexed word addresses for instruction parameters specifying word addresses. Indexed addressing is discussed in chapter 4.
19–1
Page 268
Chapter 19 Comparison Instructions
Equal (EQU)
Equal
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
EQU
Input Instruction
EQU
ZOOM on EQU –|EQU|– NAME: EQUAL SOURCE A: N7:1 SOURCE B: 612
2.3.0.0.1 0 612
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: EQU EQUAL Source A Source B
N7:1 0 612
When the values at source A and source B are equal, the instruction is logically true. If these values are not equal, the instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–2
Page 269
Chapter 19 Comparison Instructions
Not Equal (NEQ)
Not Equal
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
NEQ
Input Instruction
NEQ
ZOOM on NEQ –|NEQ|– NAME: NOT EQUAL SOURCE A: N7:1 SOURCE B: 612
2.3.0.0.1 0 612
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: NEQ NOT EQUAL Source A Source B
N7:1 0 612
When the values at source A and source B are not equal, the instruction is logically true. If the two values are equal, this instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–3
Page 270
Chapter 19 Comparison Instructions
Less Than (LES)
Less Than
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
LES
Input Instruction
LES
ZOOM on LES –|LES|– NAME: LESS THAN SOURCE A: N7:1 SOURCE B: 612
2.3.0.0.1 0 612
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: LES LESS THAN Source A Source B
N7:1 0 612
When the value at source A is less than the value at source B, this instruction is logically true. If the value at source A is greater than or equal to the value at source B, this instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–4
Page 271
Chapter 19 Comparison Instructions
Less Than or Equal (LEQ)
Less Than or Equal
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
LEQ
Input Instruction
LEQ
ZOOM on LEQ –|LEQ|– NAME: LESS THAN OR EQUAL SOURCE A: N7:1 0 SOURCE B: 612 612
2.3.0.0.1
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: LEQ LESS THAN OR EQUAL Source A N7:1 0 Source B 612
When the value at source A is less than or equal to the value at source B, this instruction is logically true. If the value at source A is greater than the value at source B, this instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–5
Page 272
Chapter 19 Comparison Instructions
Greater Than (GRT)
Greater Than
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
GRT
Input Instruction
GRT
ZOOM on GRT –|GRT|– NAME: GREATER THAN SOURCE A: N7:1 0 SOURCE B: 612 612
2.3.0.0.1
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: GRT GREATER THAN Source A Source B
N7:1 0 612
When the value at source A is greater than the value at source B, this instruction is logically true. If the value at source A is less than or equal to the value at source B, this instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–6
Page 273
Chapter 19 Comparison Instructions
Greater Than or Equal (GEQ)
Greater Than or Equal
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
GEQ
Input Instruction
GEQ
ZOOM on GEQ –|GEQ|– 2.3.0.0.1 NAME: GREATER THAN OR EQUAL SOURCE A: N7:1 0 SOURCE B: 612 612
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: GEQ GRTR THAN OR EQUAL Source A N7:1 0 Source B 612
When the value at source A is greater than or equal to the value at source B, this instruction is logically true. If the value at source A is less than the value at source B, this instruction is logically false.
Entering Parameters You must enter a word address for source A. You can enter a program constant or a word address for source B. Signed integers are stored in two’s complementary form.
19–7
Page 274
Chapter 19 Comparison Instructions
Masked Comparison for Equal (MEQ)
Masked Comparison for Equal
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
MEQ
Input Instruction
MEQ
ZOOM on MEQ –|MEQ|– 2.3.0.0.1 NAME: MASKED EQUAL SOURCE A: B3:10 0100 0110 0000 0000 MASK: 00FF 00FF COMPARE: B3:11 0000 0000 0111 0101
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: MEQ MASKED EQUAL Source B3:10 0100011100000000 Mask 00FF Compare B3:11 0000000001110101
This input instruction compares data at a source address with data at a reference address and allows portions of the data to be masked by a separate word.
Entering Parameters • Source – the address of the value you want to compare. • Mask – a hex value or the address of the mask through which the instruction moves data. Refer to appendix B for more information regarding masks and hexadecimal numbering. • Compare – an integer value or the address of the reference. If the 16 bits of data at the source address are equal to the 16 bits of data at the compare address (less masked bits), the instruction is true. The instruction becomes false as soon as it detects a mismatch. Bits in the mask word mask data when reset, they pass data when set.
19–8
Page 275
Chapter 19 Comparison Instructions
Limit Test (LIM)
SLC 5/02 Processors Only Limit Test
HHT Ladder Display:
HHT Zoom Display: (online monitor mode)
LIM
Input Instruction
LIM
ZOOM on LIM –|LIM|– NAME: LIMIT TEST LOW LIM: N7:0 14 TEST: 50 50 HIGH LIM: N7:1 70
2.3.0.0.1
EDT_DAT F1
F2
F3
F4
F5
Ladder Diagrams and APS Displays: LIM LIMIT TEST Low Lim Test High Lim
N7:0 14 50 N7:1 70
This input instruction tests for values within or outside a specified range, depending on how you set the limits.
Entering Parameters Low Limit, Test, and High Limit values you program can be word addresses or decimal values, restricted to the following combinations: • If the Test parameter is a program constant, both the Low Limit and High Limit parameters must be word addresses. • If the Test parameter is a word address, the Low Limit and High Limit parameters can be be either a program constant or a word address.
19–9
Page 276
Chapter 19 Comparison Instructions
True/False Status of the Instruction If the Low Limit has a value equal to or less than the High Limit, the instruction is true when the Test value is between the limits or is equal to either limit. If the Test value is outside the limits, the instruction is false. This is illustrated in the figure below. False –32,768
True
False
Low Limit
+ 32,767
High Limit
Example, low limit less than high limit: Low Limit
High Limit
Instruction is true when Test value is
Instruction is false when Test value is
5
8
5 thru 8
–32,768 thru 4 and 9 thru 32,767
If the Low Limit has a value greater than the High Limit, the instruction is false when the Test value is between the limits. If the Test value is equal to either limit or outside the limits, the instruction is true. This is illustrated in the figure below. True –32,768
False High Limit
True + 32,767
Low Limit
Example, low limit greater than high limit:
19–10
Low Limit
High Limit
Instruction is true when Test value is
Instruction is false when Test value is
8
5
–32,768 thru 5 and 8 thru 32,767
6 thru 7