Page 441
Appendix
A
HHT Messages and Error Definitions This appendix provides details about the messages that appear on the prompt line of the HHT display. These messages prompt you regarding programming procedures, restrictions, and limitations. They also bring your attention to errors such as incorrect procedures, incorrect data entry, failure of selftest functions, and hardware/software incompatibility. The messages in this chapter refer specifically to HHT operations. They are listed in alphabetical order. For a list of SLC 500 family processor error codes, refer to chapter 27. Message:
Appears when:
Respond by:
5/02 INSTRUCTION, FILE X, RUNG Y
This processor type is incompatible with your present ladder program. There are references to inputs and outputs in your program which do not exist in this processor type.
Choosing a different processor type or modifying your ladder program.
BATTERY TEST FAILED
The HHT battery is not present or has lost power. Important: If a ladder program is stored in the HHT, it may be lost.
Connecting or replacing the battery or connecting the battery jumper.
BRANCH LEVEL LIMIT EXCEEDED
You have reached the limit of extend up or extend down branching instructions.
Using storage bits and programming a separate rung for the additional branches.
BRANCH WILL EXCEED NEST LIMIT
You are attempting to begin a branch within an existing branch for 500 or 5/01. Or, you are attempting to exceed the nest level for a 5/02.
Referring to page 5–7 in this manual.
The processor is in a fault condition and try to enter the Run mode.
Correcting the fault.
You are trying to enable forces where none exist.
Installing the desired force.
You are trying to copy a processor RAM ladder program to a memory module (EEPROM) that is not installed in the processor.
Installing the memory module.
CHANGE PROCESSOR TO PROGRAM MODE
The function you are attempting cannot be done while the processor is in the run or Test mode.
Using the [MODE] function to change the processor to the Program mode.
CHANGE PROGRAM NAME FROM DEFAULT
You are trying to access the edit file function for a program that does not exist.
Changing the program name from DEFAULT.
CONTINUE AND GO OFFLINE?
You want to exit online communications.
Answering YES to go offline. Answering NO to continue online monitoring.
The HHT program compiler cannot successfully compile your program.
Answering YES to save your program in a state that allows future edits to be made. Answering NO abandons the save operation. Important: You can SAVE the program with errors (to correct at a later time), but you cannot download the program to the processor.
CANNOT GENERATE CONDITION
CONTINUE AND SAVE WITH ERRORS?
A–1
Page 442
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
Respond by:
The instruction or rung you are attempting to delete may contain the only reference to a data location.
Answering YES if you want to continue the deletion. Answering NO if you wish to abort the deletion.
Forces are present on the instruction or in the rung you are attempting to delete.
Answering YES if you want to continue the deletion. Answering NO if you wish to abort the deletion.
DATA INTEGRITY TEST FAILED
The ladder program file stored in the HHT RAM is lost. The HHT battery may be missing or the voltage is low.
Connecting or replacing the battery.
DEFAULT FILE IN PROCESSOR
The processor contains a default ladder program.
Downloading a non–default ladder program.
DELETED RUNG BUFFER EMPTY
You undelete a rung and the rung buffer is empty.
No response.
DESTRUCTIVE RAM TEST FAILED
The battery–backed RAM chip of the HHT is corrupted.
Contacting your A–B service representative.
DIRECTORY FILE CORRUPTED
The ladder program file directory of the processor is inaccurate.
No response. The HHT is unable to read or monitor this program.
DOWNLOAD DENIED, COMPILER ERRORS
The ladder program has been saved with errors (possibly I/O configuration errors).
Using the ladder program editor to correct your program.
You attempt to program multiple HSC instructions. Your ladder program is allowed to contain only one HSC instruction (processor must be DC type).
Removing duplicate HSC instructions.
ERROR EXPANDING THE DATA TABLE
The length parameter of an instruction is trying to create a data file larger than 256 elements.
Entering a smaller length.
ERROR: INVALID FORCE
The cursored instruction is not an input or output instruction.
Choosing the correct type of instruction or abandoning this attempt.
ERROR: UNDEFINED I/O ADDRESS
A mismatch exists between the I/O addresses used in the ladder program and the configured I/O modules.
Either editing the program and changing the address to agree with the configured I/O modules, or re–configuring the I/O to match the entered address. For the latter, refer to chapter 4 for more help. Important: You can SAVE the program with errors (to correct at a later time), but you cannot download the program to the processor.
FILE CANNOT BE CREATED
You are creating a ladder program file where the number entered is illegal or the file already exists.
Choosing a different file number.
FILE CANNOT BE DELETED
The entered program or data file number does not exist or is incorrect. Important: Data File numbers 0, 1, and 2 and program files 0 and 1 cannot be deleted.
Choosing a different file or aborting the procedure.
FILE OVERWRITE ERROR
A file overwrite has occurred. SQO, SQC, BSL, BSR, FLL, or COP instruction operation has crossed file boundaries.
Correcting the file length in the appropriate instruction.
HSC ALREADY EXISTS
You attempt to program multiple HSC instructions. Your ladder program is allowed to contain only one HSC instruction (processor must be DC type).
Remove duplicate HSC instructions.
DATA FORCES IN LAST STATE, DELETE?
DUPLICATE ‘(HIGH SPEED COUNTER)’ INSTRUCTION
A–2
Page 443
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
Respond by:
HSC INSTRUCTION, FILE X, RUNG Y
This processor type does not allow HSC instructions.
Removing any HSC instructions in your ladder program.
ILLEGAL ADDRESS
The processor is requested to read/write data to a non–existent ladder program file address or non–existent data table.
Creating the ladder program file address or aborting the procedure.
The processor does not understand the command received from the HHT. Communications may have been interrupted.
Checking power and communications connections to the HHT and processor and retry the procedure.
The HHT attempts to attach to an SLC 5/03 processor.
Aborting the procedure. The HHT is not compatible with the 5/03 processor.
ILLEGAL ENTRY TO PROG ATTEMPTED
You have tried to enter an incorrect password or master password three times for offline monitoring/editing.
Entering a valid password for the specified program file.
ILLEGAL NETWORK
There are duplicate nodes or the nodes are operating at different baud rates.
Use the offline WHO display to set node numbers and baud rates.
ILLEGAL OPERAND
The address entered is not in the correct format.
Entering the valid format.
The address entered is not a valid data file operand.
Entering a valid address.
ILLEGAL OSR LOCATION
An OSR instruction is placed within a branch and is not immediately adjacent to an output instruction.
Inserting the OSR instruction at a permissible location within the rung.
ILLEGAL SIZE
The processor does not understand the command received from the HHT due to invalid size of advanced I/O setup.
Checking power and communication connections to the HHT and processor and retry the procedure.
The HHT is attempting to communicate with an invalid processor type.
Aborting the procedure or changing the configuration.
The processor that you have configured in your program does not match the processor your HHT is communicating with.
Going offline and changing the processor type in the Processor Configuration.
INCORRECT PASSWORD
You have tried to enter an incorrect password or master password three times for online monitoring of a processor.
Entering a valid password for that processor program file.
INITIALIZING HHT MEMORY TO DEFAULT
A new memory pak is installed.
Uploading a valid ladder program to the HHT.
The ladder program data stored in the HHT has become corrupt and it is necessary to replace it with a default program.
Uploading a valid ladder program to the HHT.
INSIDE A BRANCH
You are attempting to begin a branch within an existing branch for 500 or 5/01.
Referring to page 5–7 in this manual.
INVALID ADDRESS
The data file address entered does not correspond to a valid address in this ladder program.
ILLEGAL COMMAND
INCOMPATIBLE PROCESSOR TYPE
INVALID DATA FILE
You are attempting to create or monitor a data file and the address entered is not in the correct format, the file type is invalid, or it already exists as a different type.
Entering a valid address. Entering a valid address or file type.
The data file address entered does not correspond to a valid address in this ladder program.
Entering a valid address.
INVALID ERROR CODE
The HHT has encountered an unknown error. This should not occur in a properly functioning HHT.
Cycling power to the HHT. If that does not work contact your A–B service representative.
INVALID FILE TYPE
This data file type is not allowed in this instruction.
Entering a valid data file type.
INVALID ID
When you are configuring I/O and the HHT is unable to find a slot configuration which matches this ID number.
Entering a valid ID number.
A–3
Page 444
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
Respond by:
INVALID OPERAND
The address entered is not a valid data file operand.
Entering a valid address.
INVALID PROCESSOR TYPE
This processor type is incompatible with your present ladder program. There are references to inputs and outputs in your program which do not exist in this processor type.
Choosing a different processor type or modifying your ladder program.
INVALID PROCESSOR TYPE, HSC PRESENT
This processor type does not allow HSC instructions.
Removing any HSC instructions in your ladder program.
KEYPAD TEST FAILED
The internal test of the keypad has determined that there are one or more inoperable keys.
Contacting your A–B service representative.
LABEL (LBL) DOES NOT EXIST FOR JUMP (JMP)
The JMP instruction does not have a valid LBL destination.
Correcting the ladder program.
LABEL (LBL) VALUE IS NOT UNIQUE
The LBL number is assigned elsewhere in the ladder program.
Choosing a different LBL number.
LENGTH IS TOO LARGE
The operand of the instruction is larger than what is defined as valid.
Entering a smaller length.
MASTER CONTROL RESETS (MCR) NOT MATCHED
A beginning MCR instruction is missing an end MCR instruction.
Programming the required end MCR instruction.
MCR IS NOT ONLY INSTRUCTION ON RUNG
An end MCR instruction is not the only instruction in the rung.
Removing the other instructions in that rung.
MISSING DESTINATION
There is an internal compiler error.
Contacting your A–B service representative.
MODULE ID CODE NOT SUPPORTED
When you are configuring I/O and the HHT is unable to find a slot configuration which matches this ID number.
Entering a valid ID number.
MULTIPLE OSR INSTRUCTIONS
When you attempt to enter multiple OSR instructions in a rung. Only one OSR instruction per rung is allowed for a 500 or 5/01.
Aborting the entry.
MUST SELECT AN INSTRUCTION
You attempt to accept a rung without instructions. A ladder rung must contain at least one output instruction to be accepted.
Entering output instructions or aborting the rung edit.
NO MEMORY MODULE
You are trying to copy a processor RAM ladder program to a memory module (EEPROM) that is not installed in the processor.
Installing the memory module.
NO RESPONSE FROM PROCESSOR
The processor is not answering requests from the HHT to communicate.
Checking power and communication connections to the HHT and processor. Also check online configuration such as baud rate and the number of devices on the network.
NO SLOTS AVAILABLE
You are attempting to define more slots than are physically available in this rack.
Aborting the procedure.
NO SUCH SUBROUTINE FILE
The subroutine number in the JSR instruction does not exist.
Creating the subroutine or changing the number in the JSR instruction.
NOT A BIT
The address entered does not specify a legal bit in a data file.
Entering a valid bit address.
A–4
Page 445
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
Respond by:
You are trying to attach the HHT to either itself or a non–processor device while in the WHO utility.
Using the [ ↓ ] or [ ↑ ] keys to change the order of the nodes listed on the WHO screen. Put the processor at the top of the list and try to attach.
You are trying to attach the HHT to a non–existent device, or no devices are shown on the WHO screen.
Changing the communication parameters of the HHT in the node configuration menu. From the WHO screen, press [F4], NODE_CFG. Try changing the baud rate by pressing [F3], BAUD; the node address by pressing [F1], CHG_ADR; or the maximum node address by pressing [F2], MAX_ADR. Try different combinations. (The processor defaults to node address 1 and baud rate 19200.)
NOT A SUBELEMENT
The address entered does not specify a valid subelement in a data file.
Entering a valid address (may require a decimal point and word value in address).
NOT A SUBROUTINE FILE
You attempted to enter an SBR instruction in the main program file.
Entering a valid address.
NOT AN ELEMENT
The address entered does not specify a valid element in a data file.
Entering a valid address.
NOT DIRECT
You have entered the [#] symbol for indirect addressing where it is not allowed.
Entering a valid address (remove # symbol).
NOT FILE OWNER
The processor files have been configured to be accessed only by another programming device.
Pressing [F5], CLR_OWNR from the WHO display to clear the previous owner.
NOT FOUND
During a search, the entered instruction, address, or force is not present in the ladder program.
Aborting the search or entering the correct information.
NOT IMMEDIATE
Data file addresses are not allowed.
Entering an immediate value.
NOT IN A BRANCH
You are attempting to extend or close a branch without first beginning the branch.
Beginning a branch.
NOT INDEXED
The address entered is not an indexed address.
Beginning the address with the [#] symbol.
NOT ON THE FIRST RUNG
An SBR instruction is not located on the first rung of the subroutine program.
Placing the instruction on the first rung of the subroutine file.
NOT PROGRAM OWNER
The processor program has been configured to be accessed only by another programming device.
Pressing [F5], CLR_OWNR from the WHO display to clear the previous owner.
NOT THE FIRST INSTRUCTION
An SBR instruction is not located as the first instruction in the subroutine program.
Inserting this instruction as the first instruction of the subroutine file.
ONLY ONE IMMEDIATE ALLOWED
You are attempting to enter more than one immediate value in an instruction.
Entering a valid data file address for this parameter.
OPCODE NOT RECOGNIZED
An invalid instruction has been entered.
Correcting the instruction.
OUT OF MEMORY
The HHT does not have enough memory to store this ladder file or program.
Decreasing the size of the program.
OUT OF MEMORY IN PROCESSOR IMAGE
The user program and data files are too large for the processor type.
Aborting the procedure or changing to a processor with additional memory.
OUTPUT FILE CANNOT BE EDITED
You are attempting to change output file data while the processor is in the Run mode.
Aborting the procedure or changing the Program mode.
NOT A PROCESSOR
A–5
Page 446
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
PASSWORD NOT CHANGED
The password or master password currently protecting the ladder program or processor has not been entered correctly. You must enter the old password before changing it.
Entering the current password correctly.
POSITION IS TOO LARGE
The position parameter entered is larger than the data file indicated.
Correcting the position value.
PROCESSOR FILES CORRUPTED
The HHT is unable to read or monitor the ladder program stored in the processor.
Downloading an uncorrupted ladder program to the processor then uploading that program to the HHT.
PROCESSOR PROGRAM INCOMPATIBLE
The processor ladder program was either programmed by a non–HHT compatible programmer or contains non–HHT compatible instructions for branching.
Aborting the procedure.
PROC PROGRAM IS LOCKED
The future access bit in the processor ladder program is set. This denies monitoring the program.
Aborting the procedure, downloading an unprotected program, or clearing memory.
PROGRAM FILES DIFFER
The ladder program in the processor does not match the program in the HHT.
Uploading or downloading the appropriate ladder program. Important: The program which is overwritten will be lost.
RACK CANNOT BE MODIFIED
The slot size of this rack cannot be modified because a higher numbered rack exists.
Aborting the procedure or deleting higher numbered racks, modifying this rack, then re–configuring the higher numbered racks.
RACK MUST CONTAIN A SLOT
A rack that must have one slot configured for the processor in slot 0 is not configured correctly.
Configuring the slot.
RESET (RST) USED ON A TIMER OFF–DELAY (TOF)
A reset (RST) instruction has been used to reset a Timer Off Delay instruction (TOF). You cannot use a RST to reset a TOF.
Remove the RST instruction.
ROM TEST FAILED – FATAL ERROR
The memory pak of the HHT has failed. The HHT is inoperable.
Replacing the memory pak.
RUNG HAS NO OUTPUT INSTRUCTION
You attempt to accept a rung without instructions. A ladder rung must contain at least one output instruction to be accepted.
Entering output instructions or aborting the rung edit.
RUNG HAS NO OUTPUT INSTRUCTION
The rung you are editing does not contain an output instruction. Each rung must contain at least one output instruction.
Entering an output instruction.
RUNG HAS SHORTED OUTPUT
The rung you are editing contains a branch around an output that does not contain its own output instruction. Any branch around an output must contain at least one output instruction.
Entering an output instruction within the branch.
RUNG TOO LARGE
You have reached the limit of instructions and/or branches allowed on one rung. There are 127 instructions allowed per rung.
Using storage bits and programming a separate rung for the additional instructions and/or branches.
SERIAL LINK DOWN
The communication link between the HHT and the processor is not functioning.
Checking power and communication connections to the HHT and processor.
SUBROUTINE (SBR) OR LABEL (LBL) ALREADY EXISTS
A subroutine or label instruction having this number already exists in this ladder program.
Choosing a different label or subroutine number.
SUBROUTINE FILE IS INVALID TYPE
The file accessed in a subroutine (SBR) instruction is not a ladder file.
Changing the number in the SBR instruction.
A–6
Respond by:
Page 447
Appendix A HHT Messages and Error Definitions
Message:
Appears when:
Respond by:
The syntax of the current rung is incorrect.
Correcting the rung.
The syntax of the current rung is incorrect.
Correcting the rung.
TOO MANY INSTRUCTIONS ON RUNG
The rung contains more than 127 instructions.
Changing the rung to contain fewer instructions.
TOO MANY INSTRUCTIONS ON RUNG
The rung contains more than 127 instructions.
Changing the rung to contain fewer instructions.
UNABLE TO BEGIN BRANCH
A branch cannot be inserted at the cursor location.
Aborting the procedure or moving the cursor.
UNABLE TO DELETE INSTRUCTION
Removing this instruction results in an illegal rung structure.
Aborting the procedure.
The file number entered does not exist in this program.
Entering a valid file number.
The file number entered does not exist in this ladder program.
Choosing the correct file number.
UNABLE TO INSERT INSTRUCTION
Inserting this instruction results in an illegal rung structure.
Aborting the procedure.
UNABLE TO MONITOR FILE
The file number entered either does not exist in the processor ladder program or it is a file type not capable of being monitored.
Choosing a different file number or downloading the program with the program file number.
UNABLE TO REPLACE INSTRUCTION
Replacing this instruction results in an illegal rung structure.
Aborting the procedure.
The file type returned by the data base is unknown to the compiler.
Using only S2, O0, I1, Bx, Rx, Cx, and Nx file types.
The file type returned by the data base is unknown to the compiler.
Using only S2, O0, I1, Bx, Rx, Cx, and Nx file types.
There is an internal compiler error.
Contacting your A–B service representative.
There is an internal compiler error.
Contacting your A–B service representative.
SYNTAX ERROR
UNABLE TO EDIT FILE
UNKNOWN FILE TYPE
UNKNOWN OPERATOR
A–7
Page 448
Appendix A HHT Messages and Error Definitions
Message: UPDATE ACCUMULATOR (UA) IN OUTPUT ENERGIZE/ OUTPUT LATCH (OTE/OTL) AND NO HIGH SPEED COUNTER (HSC)
Appears when:
Respond by:
You have programmed an update accumulator (UA) bit without first programming a high–speed counter (HSC).
Programming the high–speed counter (HSC) instruction.
You have programmed an update accumulator (UA) bit without first programming a high–speed counter (HSC).
Programming the high–speed counter (HSC) instruction.
The ladder program stored in the processor contains errors. The HHT cannot load this program into its memory. If the HHT is unable to recover its existing program, it initializes to a default program.
Downloading an error free ladder program to the processor then uploading that program to the HHT.
The HHT does not have enough memory to store this ladder file or program.
Decreasing the size of the program.
The programming device does not have enough memory to compile the current user program.
Aborting the procedure or shortening the current user program.
UPLOAD PROGRAM TO SAVE DATA EDITS
The program data changes you have entered are stored only in the processor program. If you wish to save the data changes in the HHT, you must upload the program.
Uploading the ladder program to the HHT.
WARNING: PRG REFERNCES UNDEFINED
You are attempting to delete a rack or reduce the slot size of a rack where the ladder program indicates there are input or output instructions referencing slots in this rack.
Removing or changing the addresses in your ladder program or aborting the procedure.
You are attempting to accept an instruction where the I/O address has not been configured in your program.
Configuring the I/O slot for that address.
A mismatch exists between the I/O addresses used in the ladder program and the configured I/O modules.
Either editing the program and changing the address to agree with the configured I/O modules, or re–configuring the I/O to match the entered address. For the latter, refer to chapter 4 for more help. Important: You can SAVE the program with errors (to correct at a later time), but you cannot download the program to the processor.
UPLOAD DENIED, DECOMPILER ERRORS UPLOAD DENIED, OUT OF MEMORY
WARNING: UNDEFINED I/O REFERENCED
The address you entered while editing does not match the I/O configuration.
A–8
Either changing the address to agree with the configured I/O modules or exiting the edit mode and re–configuring the I/O to match the entered address.