Page 455
Appendix
A–B
C
Memory Usage, Instruction Execution Times This appendix covers the following topics: • memory usage • instruction execution times for the fixed and SLC 5/01 processors • instruction execution times for the SLC 5/02 processor series A and B • instruction execution times for the SLC 5/02 processor series C and later
Memory Usage
SLC 500 controllers have the following user memory capacities: Type of Processor
Type of Controller
User Memory Capacity
Fixed I/O Controllers Fixed and SLC 5/01
1024 instruction words Modular Controllers 1747–L511
SLC 5/02
Modular Controllers 1747–L524
4096 instruction words
Definition: 1 instruction word = 4 data words = 8 bytes. The number of instruction words used by the individual instructions is indicated in the following table. Since the program is compiled by the programmer, it is only possible to establish estimates for the instruction words used by individual instructions. The calculated memory usage is normally greater than the actual memory usage, due to compiler optimization.
C–1
Page 456
Appendix C Memory Usage, Instruction Execution Times
Fixed and SLC 5/01 Processors
C–2
Instruction Words for the Fixed and SLC 5/01 Processors Instruction
Instruction Words (approx)
ADD AND
1.5 1.5
BSL BSR
2 2
CLR COP CTD CTU
1 1.5 1 1
DCD DDV DIV
1.5 1 1.5
EQU
1.5
FLL FRD
1.5 1
GEQ GRT
1.5 1.5
HSC
1
IIM IOM
1.5 1.5
JMP JSR
1 1
LBL LEQ LES
0.5 1.5 1.5
Instruction
Instruction Words (approx)
MCR MEQ MOV MUL MVM
0.5 1.5 1.5 1.5 1.5
NEG NEQ NOT
1.5 1.5 1
OR OSR OTE OTL OTU
1.5 1 0.75 0.75 0.75
RES RET RTO
1 0.5 1
SBR SQC SQO SUB SUS
0.5 2 2 1.5 1.5
TND TOD TOF TON
0.5 1 1 1
XIC XIO XOR
1 1 1.5
Page 457
Appendix C Memory Usage, Instruction Execution Times
Estimating Total Memory Usage of Your System Using a Fixed or SLC 5/01 Processor 1. Calculate the total instruction words used by the instructions in your program and enter the result. Refer to the table on page C–2. 2. Multiply the total number of rungs by .375 and enter the result. 3. Multiply the total number of data words (excluding the status file and I/O data words) by .25 and enter the result. 4. Add 1 word for each data table file and enter the result. 5. Multiply the highest numbered program file used by 2 and enter the result. 6. Multiply the total number of I/O data words by .75 and enter the result. 7. Multiply the total number of I/O slots, used or unused, by .75 and enter the result. 8. To account for processor overhead, enter 65 if you are using a fixed controller; enter 67 if you are using a 1747–L511 or 1747–L514. Total:
9. Total steps 1 through 8. This is the estimated total memory usage of your application system. Remember, this is an estimate, actual compiled programs may differ by ±12%. 10. If you wish to determine the estimated amount of memory remaining in the processor you have selected, do the following: If you are using a fixed controller or 1747–L511, subtract the total from 1024. If you are using a 1747–L514, subtract the total from 4096. The result of this calculation will be the estimated total memory remaining in your selected processor. Important: The calculated memory usage may vary from the actual compiled program by ±12%.
C–3
Page 458
Appendix C Memory Usage, Instruction Execution Times
Example: L20B Fixed I/O Controller 42 XIC and XIO 10 OTE instructions 10 TON instructions 1 CTU instruction 1 RES instruction Instruction Usage
42 x 1.00 = 42.00 10 x 0.75 = 7.50 10 x 1.00 = 10.00 1 x 1.00 = 1.00 1 x 1.00 = 1.00 61.50
21 rungs 37 data words User Program Total
21 x.375 = 37 x.250 =
7.87 9.25 78.62
2 I/O data words 1 slot Overhead I/O Configuration Total
2 x 0.75 = 1 x 0.75 =
1.50 0.75 65.00 67.25
Estimated total memory usage:
145.87 (round to 146)
1024 – 146 = 878 instruction words remaining in the processor
Example: 1747-L514 processor, 30-slot configuration, (15) 1746-IA16, (10) 1746-OA8, (1) 1747-DCM full configuration, (1) 1746-NI4, (1) 1746-NIO4I 50 XIC and XIO 15 OTE instructions 5 TON instructions 3 GRT instructions 1 SCL instruction 1 TOD instruction 3 MOV instructions 10 CTU instructions 10 RES instructions Instruction Usage
50 x 1.00 = 50.00 15 x 0.75 = 11.25 5 x 1.00 = 5.00 3 x 1.50 = 4.50 1 x 1.75 = 1.75 1 x 1.00 = 1.00 3 x 1.50 = 4.50 10 x 1.00 = 10.00 10 x 1.00 = 10.00 98.00
30 rungs 30 x 0.375 = 11.25 100 data words 100 x 0.25 = 25.00 10 is highest data table file number 10 x 1 = 10.00 4 is highest program file number 4 x 2 = 8.00 User Program Total 163.50 49 I/O data words 30 slot Overhead I/O Configuration Total Estimated total memory usage:
49 x 0.75 = 36.75 30 x 0.75 = 22.50 67.00 126.25 289.75 (round to 290)
4096 – 290 = 3806 instruction words remaining in processor
C–4
Page 459
Appendix C Memory Usage, Instruction Execution Times
Instruction Execution Times for the Fixed and SLC 5/01 Processors
Execution Time in Microseconds (approx.)
Instruction
False
Instruction
True
ADD AND
12 12
122 87
BSL BSR
12 12
144 + 24 per word 134 + 24 per word
CLR COP CTD CTU
12 12 12 12
40 45 + 21 per word 111 111
DCD DDV DIV
12 12 12
80 650 400
EQU➀
12
60
FLL FRD
12 12
37 +14 per word 223
GEQ➀ GRT➀
12 12
60 60
HSC
12
60
IIM IOM
12 12
372 475
JMP JSR
12 12
38 46
LBL LEQ➀ LES➀
2 12 12
2 60 60
Execution Time in Microseconds (approx.) False
True
MCR MEQ➀ MOV MUL MVM
10 12 12 12 12
10 75 20 230 115
NEG NEQ➀ NOT
12 12 12
110 60 66
OR OSR OTE OTL OTU
12 12 18 19 19
87 34 18 19 19
RES RET RTO
12 12 12
40 34 140
SBR SQC SQO SUB SUS
2 12 12 12 12
2 225 225 125 12
TND TOD TOF TON
12 12 12 12
32 200 140 135
XIC➀ XIO➀ XOR
4 4 12
4 4 87
For the rung example at the right: 1) If instruction 1 is false, instructions 2, 3, 4, 5, 6, 7 take zero execution time. Execution time = 4 + 18 = 22 microseconds. 2) If instruction 1 is true, 2 is true, and 6 is true, then instructions 3, 4, 5, 7 take zero execution time. Execution time = 4 + 4 + 4 + 18 = 30 microseconds. 1
2 ][
8
6 ][
3
][
()
7 ][
][
4 ][ 5 ][
➀
These instructions take zero execution time if they are preceded by conditions that guarantee the state of the rung. Rung logic is solved left to right. Branches are solved top to bottom.
C–5
Page 460
Appendix C Memory Usage, Instruction Execution Times
SLC 5/02 Processor
The number of instruction words used by an instruction is indicated in the following table. Since the program is compiled by the programmer, it is only possible to establish estimates for the instruction words used by individual instructions. The calculated memory usage will normally be greater than the actual memory usage, due to compiler optimization.
Instruction Words for the SLC 5/02 Processor
C–6
Instruction
Instruction Words (approx)
Instruction
Instruction Words (approx)
ADD AND
1.5 1.5
JMP JSR
1 1
BSL BSR
2 2
CLR COP CTD CTU
1 1.5 1 1
LBL LEQ LES LFL LFU LIM
0.5 1.5 1.5 1.5 1.5 1.5
DCD DDV DIV
1.5 1 1.5
EQU
1.5
FFL FFU FLL FRD
1.5 1.5 1.5 1
MCR MEQ MOV MSG MUL MVM
0.5 1.5 1.5 34.75 1.5 1.5
NEG NEQ NOT
1.5 1.5 1
GEQ GRT
1.5 1.5
OR OSR OTE OTL OTU
1.5 1 0.75 0.75 0.75
PID
23.25
HSC
1
IID IIE IIM INT IOM
1.25 1.25 1.5 0.5 1.5
Instruction
Instruction Words (approx)
REF RES RET RPI RTO
0.5 1 0.5 1.25 1
SBR SCL SQC SQL SQO SQR
0.5 1.75 2 2 2 1.25
STD STE STS SUB SUS SVC
0.5 0.5 1.25 1.5 1.5 0.5
TND TOD TOF TON
0.5 1 1 1
XIC XIO XOR
1 1 1.5
Page 461
Appendix C Memory Usage, Instruction Execution Times
Estimating Total Memory Usage of Your System Using a SLC 5/02 Processor 1. Calculate the total instruction words used by the instructions in your program and enter the result. Refer to the table on page C–6. 2. Multiply the total number of rungs by .375 and enter the result. 3. If you are using a 1747–L524 and have enabled the Single Step Test mode, multiply the total number of rungs by .375 and enter the result. 4. Multiply the total number of data words (excluding the status file and I/O data words) by .25 and enter the result. 5. Add 1 word for each data table file used and enter the result.
C–7
Page 462
Appendix C Memory Usage, Instruction Execution Times
Instruction Execution Times for the SLC 5/02 Processor Series A or B
Instruction (Series A or B SLC 5/02)
C–8
Execution Time in Microseconds (approx.) False
True
Instruction (Series A or B SLC 5/02)
Execution Time in microseconds (approx.) False
True
MSG MUL MVM
80 12 12
300➁ 234 119
NEG NEQ➀ NOT
12 12 12
114 64 70
84 654 404
OR OSR OTE OTL OTU
12 12 18 19 19
91 34 18 19 19
12
64
PID
150
6000
FFL FFU
85 85
REF
6
FLL FRD
12 12
250 250 + 18 x position value 41 + 14 per word 227
GEQ➀ GRT➀
RES RET RPI RTO
12 12 12 12
400 + 300 per word 44 34 400 144
12 12
64 64
IID IIE IIM INT IOM
12 12 12 0 12
65 70 552 0 767
SBR SCL SQC SQL SQO SQR
2 12 12 60 12 12
6 800 229 225 229 270
JMP JSR
12 12
38 46
LBL LEQ➀ LES➀ LFL LFU LIM
2 12 12 85 85 12
6 64 64 250 300 75
STD STE STS SUB SUS SVC
6 6 12 12 12 6
15 15 120 129 12 400
MCR MEQ➀ MOV
10 12 12
10 79 24
TND TOD TOF TON
12 12 12 12
36 204 144 139
XIC➀ XIO➀ XOR
4 4 12
4 4 91
ADD AND
12 12
126 91
BSL BSR
12 12
148 + 24 per word 138 + 24 per word
CLR COP CTD CTU
12 12 12 12
44 49 + 21 per word 115 115
DCD DDV DIV
12 12 12
EQU➀
For the rung example below: 1) If instruction 1 is false, instructions 2, 3, 4, 5, 6, 7 take zero execution time. Execution time = 4 + 18 = 22 microseconds. 2) If instruction 1 is true, 2 is true, and 6 is true, then instructions 3, 4, 5, 7 take zero execution time. Execution time = 4 + 4 + 4 + 18 = 30 microseconds. 1
2 ][
8
6 ][
3
][
()
7 ][
][
4 ][ 5 ][
➀
These instructions take zero execution time if they are preceded by conditions that guarantee the state of the rung. Rung logic is solved left to right. Branches are solved top to bottom.
➁
This only includes the amount of time needed to “set up” the operation requested. It does not include the time it takes to service the actual communications.
Page 463
Appendix C Memory Usage, Instruction Execution Times
Instructions Having Indexed Addresses For each operand having an indexed address, add 50 microseconds to the execution time for a true instruction. For example, if a MOV instruction has an indexed address for both the source and destination, the execution time when the instruction is true is 24 + 50 + 50 = 124 microseconds.
Instructions Having M0 or M1 Data File Addresses For each bit or word instruction, add 1928 microseconds to the execution time. For each multiple-word instruction, add 1583 microseconds plus 667 microseconds per word. M0:2.1 ] [ 1
M1:3.1 ]/[ 1
M0:2.1 ( ) 10
MOV MOVE Source
M1:10.7
Dest
N7:10
Example COP COPY FILE Source #B3:0 Dest #M0:1.0 Length 34
For the multi–word instruction above, add 1583 microseconds plus 667 microseconds per word. In this example, 34 words are copied from #B3:0 to M0:1.0. Add 1583 + (667 x 34) = 24261 microseconds to the execution time listed on page C–8. This comes to 763 (calculated from page C–8 table) plus 24261 = 25024 microseconds total, or 25.0 milliseconds.
C–9
Page 464
Appendix C Memory Usage, Instruction Execution Times
Instruction Execution Times for the SLC 5/02 Processor Series C and Later The SLC 5/02 series C processor performance is on the average 40% faster than that of the SLC 5/02 series B processor. The table below lists the instruction execution times for the SLC 5/02 series C processor.
Instruction (Series C SLC 5/02)
Execution Time in Microseconds (approx.) False
True
Instruction (Series C SLC 5/02)
Execution Time in Microseconds (approx.) False
True
MSG MUL MVM
48 7 7
180➁ 140 71
NEG NEQ➀ NOT
7 38 7
68 38 42
50 392 242
OR OSR OTE OTL OTU
7 7 11 11 11
55 20 11 11 11
38
38
PID
90
3600
FFL FFU
51 51
REF
4
FLL FRD
7 7
150 150 + 11 x position value 25 + 8 per word 136
GEQ➀ GRT➀
RES RET RPI RTO
7 7 7 30
240 + 180 per word 26 20 240 86
38 38
38 38
IID IIE IIM INT IOM
7 7 7 0 7
39 42 340 0 465
SBR SCL SQC SQL SQO SQR
1 7 36 36 36 7
4 480 137 135 137 162
JMP JSR
7 7
23 28
LBL LEQ➀ LES➀ LFL LFU LIM
1 38 38 51 51 7
4 38 38 150 180 45
STD STE STS SUB SUS SVC
4 4 7 7 7 4
9 9 72 77 7 240
MCR MEQ➀ MOV
6 7 7
6 47 14
TND TOD TOF TON
7 7 36 36
22 122 86 83
XIC➀ XIO➀ XOR
2.4 2.4 7
2.4 2.4 55
ADD AND
7 7
76 55
BSL BSR
36 36
89 + 14 per word 83 + 14 per word
CLR COP CTD CTU
7 7 7 7
26 29 + 13 per word 69 69
DCD DDV DIV
7 7 7
EQU➀
C–10
For the rung example below: 1) If instruction 1 is false, instructions 2, 3, 4, 5, 6, 7 take zero execution time. Execution time = 2.4 + 11 = 13.4 microseconds. 2) If instruction 1 is true, 2 is true, and 6 is true, then instructions 3, 4, 5, 7 take zero execution time. Execution time = 2.4 + 2.4 + 2.4 + 11 = 18.2 microseconds. 1
2 ][
8
6 ][
3
][
()
7 ][
][
4 ][ 5 ][
➀
These instructions take zero execution time if they are preceded by conditions that guarantee the state of the rung. Rung logic is solved left to right. Branches are solved top to bottom.
➁
This only includes the amount of time needed to “set up” the operation requested. It does not include the time it takes to service the actual communications.
Page 465
Appendix C Memory Usage, Instruction Execution Times
Example: 1747-L524 series C processor, 30-slot configuration, (15) 1746-IA16, (10) 1746-OA8, (1) 1747-DCM full configuration, (1) 1746-NI4, (1) 1746-NIO4I 50 XIC and XIO 15 OTE instructions 5 TON instructions 3 GRT instructions 1 SCL instruction 1 TOD instruction 3 MOV instructions 10 CTU instructions 10 RES instructions Instruction Usage
50 x 1.00 = 50.00 15 x 0.75 = 11.25 5 x 1.00 = 5.00 3 x 1.50 = 4.50 1 x 1.75 = 1.75 1 x 1.00 = 1.00 3 x 1.50 = 4.50 10 x 1.00 = 10.00 10 x 1.00 = 10.00 98.00
30 rungs 30 x 0.375 = 11.25 100 data words 100 x 0.25 = 25.00 10 is highest data table file number 10 x 1 = 10.00 4 is highest program file number 4 x 2 = 8.00 User Program Total 163.50 49 I/O data words 30 slot Overhead I/O Configuration Total Estimated total memory usage:
49 x 0.75 = 36.75 30 x 0.75 = 22.50 204.00 263.25 426.75 (round to 427)
4096 – 427 = 3669 instruction words remaining in processor
C–11
Page 466
Appendix C Memory Usage, Instruction Execution Times
Instructions Having Indexed Addresses For each operand having an indexed address, add 30 microseconds to the execution time for a true instruction. For example, if a MOV instruction has an indexed address for both the source and destination, the execution time when the instruction is true is 14 + 30 + 30 = 74 microseconds.
Instructions Having M0 and M1 Data File Addresses For each bit or word instruction, add 1157 microseconds to the execution time. For each multiple-word instruction, add 950 microseconds plus 400 microseconds per word. M0:2.1 ] [ 1
M1:3.1 ]/[ 1
M0:2.1 ( ) 10
MOV MOVE Source
M1:10.7
Dest
N7:10
Example COP COPY FILE Source #B3:0 Dest #M0:1.0 Length 34
For the multi–word instruction above, add 950 microseconds plus 400 microseconds per word. In this example, 34 words are copied from #B:3.0 to M0:1.0. Add 950 + (400 x 34) = 14550 microseconds to the execution time listed on page C–10. This comes to 471 (calculated from page C–10 table) plus 14550 = 15021 microseconds total, or 15.0 milliseconds.
C–12